U-MATCH SERIES DC INVERTER AIR CONDITIONERS SERVICE MANUAL
6
3 PRODUCT DATA
3.1 Product Data of Indoor Unit
Duct Type
Model
Indoor unit
UMAT18HP230V1BD
UMAT24HP230V1BD
Product Code
CF022N1000
CF022N0940
Outdoor unit
UMAT18HP230V1BO
UMAT24HP230V1BO
Product Code
CF090W1040
CF090W1060
Capacity
Cooling Capacity
kW
5.0(1.60-5.80)
7.0(2.40-8.20)
Heating Capacity
kW
5.6(1.40-6.80)
8.0(2.40-9.00)
Power Input
Cooling
kW
1.55(0.55-1.75)
2.35(0.85-2.50)
Heating
kW
1.65(0.50-1.90)
2.40(0.80-2.75)
SEER / HSPF
(Btu/h)/W
16.00/9.00
16.00/9.00
Indoor Unit
UMAT18HP230V1BD
UMAT24HP230V1BD
Power Supply
208/230V~60Hz
Heat Exchange
Cross Fin Coil
Cross Fin Coil
Fan
Drive
Direct
Direct
Motor Output
kW
0.06×1
0.15×1
Air Flow
m
3
/h(CFM)
1000(585)
1400(820)
Rated Ext. Static
Pressure
Pa(InWg)
50(0.2)
50(0.2)
Ext. Static Pressure
Range
Pa(InWg)
0-100(0-0.4)
0-200(0-0.8)
Sound Pressure Level(H/M/L)
dB(A)
40/39/36/28
47/46/44/40
Air Filter
—
PP
PP
Drain Piping
mm(inch)
Φ30×1.5
(
Φ1.18×0.06)
Φ20×1.2
(
Φ0.79×0.05)
Outline Dimensions (W×H×D)
mm(inch)
1280×270×560
(50.4×10.6×22.0)
1225×290×775
(48.3×11.4×30.5)
Net Weight
kg(lb)
34.0(75.0)
47.0(103.6)
Outdoor Unit
UMAT18HP230V1BO
UMAT24HP230V1BO
Power Supply
208/230V~60Hz
Heat Exchange
Cross Fin Coil
Cross Fin Coil
Compressor
Type
Rotary
Rotary
Power Input
W
1400
2550
Refrigerant
Control
Electronic
Expansion Valve
Electronic
Expansion Valve
Charge
kg(oz)
1.40(49.39)
2.20(77.62)
Outline Dimensions (W×H×D)
mm(inch)
955×700×395
(37.6×27.6×15.6)
980×790×425
(38.6×31.1×16.8)
Net Weight
kg(lb)
48.0(105.8)
69.0(152.1)
Piping
Connections
Liquid
Inch
Φ1/4
Φ3/8
Gas
Inch
Φ1/2
Φ5/8
Max. Length
m(ft)
50(164)
50(164)
Max. Height
m(ft)
15(49.2)
15(49.2)
Summary of Contents for U-MATCH B Series
Page 4: ...U MATCH SERIES DC INVERTER AIR CONDITIONERS SERVICE MANUAL 1 PRODUCT ...
Page 14: ...U MATCH SERIES DC INVERTER AIR CONDITIONERS SERVICE MANUAL 11 CONTROL ...
Page 52: ...U MATCH SERIES DC INVERTER AIR CONDITIONERS SERVICE MANUAL 49 INSTALLATION ...
Page 75: ...U MATCH SERIES DC INVERTER AIR CONDITIONERS SERVICE MANUAL 72 MAINTENANCE ...
Page 96: ...U MATCH SERIES DC INVERTER AIR CONDITIONERS SERVICE MANUAL 93 ...