U-MATCH SERIES DC INVERTER AIR CONDITIONERS SERVICE MANUAL
27
4.9.8 Selecting door control function
Under debugging state, press Mode button to adjust to ―08‖ in temperature displaying zone. Timer
zone displays setting state and press ▲ or ▼ button to adjust. There are 2 selections:
①
Without door control function (LCD displays 00)
②
With door control function (LCD displays 01)
4.9.9 Selecting human sensitive function
Under debugging state, press Mode button to adjust to ―09‖ in temperature displaying zone. Timer
zone display
s setting state and press ▲ or ▼ button to adjust. There are 2 selections:
①
Without human sensitive function (LCD displays 00)
②
With human sensitive function (LCD displays 00)
4.9.10 Selecting long-distance monitoring or centralized controller
Under debuggin
g state, press Mode button to adjust to ―10‖ in temperature displaying zone. Timer
zone displays setting state and press ▲ or ▼ button to adjust. There are 2 selections:
①
Centralized controller (LCD displays 00)
②
Long-distance monitoring (LCD displays 01)
4.9.11 Selecting fan mode of indoor fan motor
Under debugging state, press Mode button to adjust to ―11‖ in temperature displaying zone. Timer
zone
displays setting state and press ▲ or ▼ button to adjust. There are 4 selections:
①
P0 (LCD displays 00)
②
P1 (LCD displays 01)
③
P3 (LCD displays 02)
④
P3 (LCD displays 03)
Note:
You can select P01, P02, P03, P04, P05, P06, P07, P08, P09 in fan mode of indoor fan motor,
which means different fan mode combinations are corresponding to different static pressure. Ex-factory
defaulted mode is P05. You can set the mode through wired controller. S01, S02,
S03……S12, S13
means the rotation speed of indoor unit is from low to high.
Table 2-4-2 Combination relationship of P01, P02, P03, P04, P05, P06, P07, P08, P09
Static pressure
selection
Super high
speed
High
speed
Medium
high speed
Medium
speed
Medium
low speed
Low
speed
Quiet
R1
spee
d
Quiet
R2
spee
d
Quiet
R13
speed
P01
S05
S03
S02
S02
S01
S01
S01
S01
S01
P02
S06
S04
S03
S03
S02
S02
S02
S02
S02
P03
S07
S05
S04
S04
S03
S03
S03
S03
S03
P04
S08
S06
S05
S05
S04
S04
S04
S04
S04
P05
S09
S07
S06
S06
S05
S05
S05
S05
S05
P06
S10
S08
S07
S07
S06
S06
S06
S06
S06
P07
S11
S09
S08
S08
S07
S07
S07
S07
S07
P08
S12
S10
S09
S09
S08
S08
S08
S08
S08
P09
S13
S11
S10
S10
S09
S09
S09
S09
S09
Summary of Contents for U-MATCH B Series
Page 4: ...U MATCH SERIES DC INVERTER AIR CONDITIONERS SERVICE MANUAL 1 PRODUCT ...
Page 14: ...U MATCH SERIES DC INVERTER AIR CONDITIONERS SERVICE MANUAL 11 CONTROL ...
Page 52: ...U MATCH SERIES DC INVERTER AIR CONDITIONERS SERVICE MANUAL 49 INSTALLATION ...
Page 75: ...U MATCH SERIES DC INVERTER AIR CONDITIONERS SERVICE MANUAL 72 MAINTENANCE ...
Page 96: ...U MATCH SERIES DC INVERTER AIR CONDITIONERS SERVICE MANUAL 93 ...