TROUBLESHOOTING
The Gree Ductless Mini-Splits units have onboard diagnostics. Informational and error codes will be
displayed on the Wired Controller display.
Informational codes are not signs of system malfunctions or failures. The following is a list of system
informational codes and descriptions:
Description
Info
Code Possible Causes
Mode Conflict
E7
Some Indoor Units are Requesting Heat and Some cooling.
Defrosting
H1
Defrosting Indoor Coil during Heating Mode
Error codes are an indicator of a system malfunction or failure. The following list of error codes and
descriptions:
Equipment Fault
Error
Codes Possible Causes
Indoor Ambient Temp. Sensor
F1
Short/Open of the Indoor Ambient Temperature Sensor
Indoor Evaporator Temp Sensor
F2
Short/Open of the Indoor Evaporator Temperature Sensor
Outdoor Ambient Temp Sensor
F3
Short/Open of the Outdoor Ambient Temperature Sensor
Outdoor Coil Temp Sensor
F4
Short/Open of the Condenser Coil Temperature Sensor
Outdoor Discharge Air Temp Sensor
F5
Short/Open of the Outdoor Discharge Temperature Sensor
Liquid Valve Inlet Temp Sensor
b5
Short/Open of the Liquid Valve Temperature Sensor
Suction/Gas Valve Outlet Temp Sensor
b7
Short/Open of the Gas/Suction Valve Temperature Sensor
Indoor Configuration Jumper
C5
Missing Configuration Jumper on Indoor Control Board
High Pressure Protection
E1
Too much refrigerant or High Ambient conditions or low airflow.
High Discharge Temp Protection
E4
Compressor Discharge High Temperature Protection
High Current Protection
E5
Power Supply is Not Stable and Voltage Range too large
Communication Error
E6
Communication Failure or mis-wired between Indoor/Outdoor
Overload Protection
E8
Overload Protection
Indoor Condensate Full
E9
Indoor condensate pan is full and needs to be drained.
Compressor Overheat Protection
H3
Compressor Thermal Overload Protection
IPM Protection
H5
Module Current Protection(namely IPM Protection)
Indoor fan Malfunction
H6
Indoor Fan Stopped or Running too Slow
Motor Desynchronizing
H7
Compressor Desynchronizing
PFC Error
Hc
PFC Protection
Startup Failure
Lc
Compressor Startup Failure
Phase Loss
Ld
Compressor phase Failure/Reverse Protection
Indoor/Outdoor Mismatch
LP
Indoor and Outdoor Units Unmatched (Model or Capacity)
Compressor Current Protection
P5
Phase Over-Current Protection
Radiator Temp Sensor Error
P7
Short/Open Circuit of the Module Temperature Sensor
Radiator Overheat Protection
P8
Module Temperature Protection
4-Way Valve Malfunction
U7
Bad Connection, Solenoid Failure or Valve Malfunction
For additional error codes not listed above, see the Gree Multi+ Service &Troubleshooting manual.
21