SYSTEM REQUIREMENTS
PIPE SIZE:
Model #
Capacity
Size (Btu)
Voltage
Liquid Line
Suction/Gas
Line
Net/Gross
Weight
CAS12HP230V1AC
12,000
208/230 - 1ph 60 hz
1/4-in (6mm)
3/8-in (9.5mm)
44/51 lbs.
CAS18HP230V1AC
18,000
208/230 - 1ph 60 hz
1/4-in (6mm)
1/2-in (12-mm)
48/55 lbs.
CAS24HP230V1AC
24,000
208/230 - 1ph 60 hz
3/8-in (9.5mm)
5/8-in (16-mm)
66/84 lbs.
INTERCONNECTING CABLE:
Recommended 14/4 AWG stranded bare copper conductors THHN 600V unshielded wire
Note:
Use shield cable if installation is in close proximity of RF and EMI transmitting devices.
CONDENSATE DRAINAGE:
Recommended condensate drainage system use pipe either the same diameter or with the diameter
larger (excluding the raising section) than that of the connecting pipe (nominal diameter 1-in, outside
diameter 1-1/4-in.)
Note:
Insulate condensate all condensate drain pipes to prevent sweating and possible water damage.
NOMENCLATURE:
Series Designation
Product Type
S - System
O - Outdoor units
CAS - Ceiling Cassette
H - Indoor High Wall
D - Indoor Duct
C - Indoor Cassette
Cooling Capacity
F - Indoor Floor/Ceiling
12 - 12,000 BTUH
18 - 18,000 BTUH
Revision Level
24 - 24,000 BTUH
(ect..)
Style/Color Designation
Model Type
AC -Cooling Only
Electrical Rating
HP -Heat Pump
230V - 208/230V 60Hz 1PH
HC - Heat/Cool
115V - 115V 60Hz 1PH
Example: CAS18HP230V1AC
CAS
42
HP 230V
1
A
C
4