BACnet Gateway Kit for Central Air Conditioners
40
7-off;
8-heat preservation and standby;
9-heating water.
Note:
1) This parameter is only for the GMV water heater.
(23) Water tank(setting)
Member number :22
Object name:WaterTankCommand_XX_YYY_ZZ (XX means Air condition type, like GMV
is 01;YYY means Outdoor Unit's number, like GMV is between 001 and 004 now; ZZ means
Indoor Unit's number, like GMV is between 01 and 16 now, otherwise 00 means device YYY's
Parameters.)
Object type: Multistate Value
Object ID: MV(19)+YYY*8192+ZZ*64+1
Instance Number: YYY*8192+ZZ*64+1
Description: this object is used to monitor the status setting of the water tank of GMV water
heater.
Present_Value:
7-off;
8-heat preservation and standby;
9-heating water.
Note :
1) Present_Value “7” and “8” can be set successfully only when they comply with the
temperature control logic of the unit.
2) This parameter is only for the GMV water heater.
(24) Water tank mode(status)
Member number :23
Object name:WaterTankModeStatus_XX_YYY_ZZ (XX means Air condition type, like GMV
is 01;YYY means Outdoor Unit's number, like GMV is between 001 and 004 now; ZZ means
Indoor Unit's number, like GMV is between 01 and 16 now, otherwise 00 means device YYY's
Parameters.)
Object type: Multistate Input
Object ID: MI(13)+YYY*8192+ZZ*64+3
Instance Number: YYY*8192+ZZ*64+3
Description: this object is used to monitor the status of the water tank of GMV water heater.
Present_Value:
1-energy saving mode;
2-reservation mode;
3-night mode;
4-hot water mode.
Notes:
1) This parameter is only for the GMV water heater.