BACnet Gateway Kit for Central Air Conditioners
35
Object type:Binary Value
Object ID: BV(5)+YYY*8192+ZZ*64+1
Instance Number: YYY*8192+ZZ*64+1
Description: this object is used to monitor the Swing setting of the indoor fan.
Present_Value:
ACTIVE:On
INACTIVE:Off
Note:
1) The Present_Value can reflect the real-time Swing state of the unit. That is, it varies as the
change of the Swing setting of the wired controller or the wires controller.
(12) Energy saving(setting)
Member number:11
Object name:EnergySavingCommand_XX_YYY_ZZ (XX means Air condition type,like GMV is
01;YYY means Outdoor Units's number,like GMV is between 001 and 004 now;ZZ means Indoor
Units's number,like GMV is between 01 and 16 now,otherwise 00 means deviceYYY's Parameters.)
Object type:Binary Value
Object ID: BV(5)+YYY*8192+ZZ*64+2
Instance Number: YYY*8192+ZZ*64+2
Description: this object is used to monitor the energy saving setting of the indoor unit.
Present_Value:
ACTIVE: On
INACTIVE:Off
Notes:
1) the Present_Value can reflect the real-time energy saving setting of the unit. That is, it varies
as the change of the energy saving setting of the wired controller or the wires controller.
2) When Present_Value is ACTIVE, under either the “COOL” or “HEAT” mode, the unit will run
among the energy saving temperature limit so as to save more energy.
(13) Remote temp shield mark (setting)
Member number: 12
Object name:RemoteTempShieldCommand_XX_YYY_ZZ (XX means Air condition type,like
GMV is 01;YYY means Outdoor Unit's number, like GMV is between 001 and 004 now; ZZ means
Indoor Unit's number, like GMV is between 01 and 16 now, otherwise 00 means device YYY's
Parameters.)
Object type: Binary Value
Object ID: BV (5)+YYY*8192+ZZ*64+3
Instance Number: YYY*8192+ZZ*64+3
Description: this object is used to enable or disable the wired or wireless controller to set the
room temperature�
Present_Value:
ACTIVE:Shield
INACTIVE: Without shield