
BACnet Gateway Kit for Central Air Conditioners
36
1) Present_Value is ACTIVE, the wired or wireless controller is disabled to set the room
temperature�
2) Present_Value is ACTIVE,the BMS is enabled to control the room temperature.
(14) Remote mode shield mark(setting)
Member number :13
Object name:RemoteModeShieldCommand_XX_YYY_ZZ (XX means Air condition type,like
GMV is 01;YYY means Outdoor Unit's number, like GMV is between 001 and 004 now;ZZ means
Indoor Unit's number, like GMV is between 01 and 16 now, otherwise 00 means deviceYYY's
Parameters.)
Object type:Binary Value
Object ID: BV(5)+YYY*8192+ZZ*64+4
Instance Number: YYY*8192+ZZ*64+4
Description: this object is used to enable or disable the wired or wireless controller to set the
running mode the unit.
Present_Value:
ACTIVE: Shield
INACTIVE: Without shield
Note :
1) When Present_Value is ACTIVE, the wired or wireless controller is disabled to set the
running mode of the unit.
2) When Present_Value is ACTIVE, the BMS is enabled to control the running mode of the unit.
(15) Remote On/Off shield mark (setting)
Member number :14
Object name:RemoteOnOffShieldCommand_XX_YYY_ZZ (XX means Air condition type,like
GMV is 01;YYY means Outdoor Unit 's number, like GMV is between 001 and 004 now;ZZ means
Indoor Unit's number ,like GMV is between 01 and 16 now, otherwise 00 means device YYY's
Parameters.)
Object type: Binary Value
Object ID: BV(5)+YYY*8192+ZZ*64+5
Instance Number: YYY*8192+ZZ*64+5
Description: this object is used to enable the wired or wireless controller to start or stop the unit.
Present_Value:
ACTIVE:Shield
INACTIVE:Without shield
Note :
1) When Present_Value is ACTIVE, the wired or wireless controller is enabled to start or stop
the unit.
2) When Present_Value is ACTIVE, the BMS is enabled to control the start or stop of the unit.
(16) RemoteLockCommand_XX_YYY_ZZ
Member number :15
Object name:RemoteLockCommand_XX_YYY_ZZ (XX means Air condition type,like GMV
is 01;YYY means Outdoor Unit's number, like GMV is between 001 and 004 now; ZZ means