                                         Z series combination household (townhouse)central air conditioning unit

8

5. Daily Operation and Maintenance 

When adjustment and test had completed, daily operation such as turn on/off unit, switch cooling and 

heating, and set parameter etc. are to be done through the manual control that installed indoor. 

1) All safety protection equipments have been set  before outgoing, please don’t modify them to prevent 

damage to the unit. 

2) On-off control of fan coil in each room should be individually operated by thermostat and 3-speed 

switch installed in each room. When there is no network control between host and fan coil, after the last fan 
coil is turned off, host should be stopped. 

3) Don’t cut off power after the unit is stopped. If off time is too long (more than 2 days) and power 

supply has been cut after stop, power should be supplied for the unit before restarting the unit to reheat the 
compressor for more than 6hr ,so that the unit can operate normally. 

4) Don’t put things on the unit or its accessories. Keep the space around the unit dry, clean and ventilation 

well. Clean it on time when there is much dust on fin of condenser to prevent the dust from affecting the 
performance. 

5) Don’t block the air outlet and air inlet of indoor fan coil. Filter at air inlet should be periodically 

cleaned. 

6) Antifreeze must be added into water system of heat pump unit according to proportion shown in this 

manual. For cooling only unit, when it is not used in winter, do drain out all water in the unit and pipeline to 
avoid cracking of heat exchanger, pipes and water pump. If it is not sure whether water in pipeline has been 
drained completely, antifreeze must be added into system pipeline. Don’t cut off power after the unit is off to 
make automatic antifreeze operation protection effective. 

7) For heat pump unit, after long time for not operation, water in the pipeline will share the same 

temperature with ambient water, thus, note to anti cool wind in winter when unit is heating; to the situation of 
no connected control system between host and fan coil, it is better to turn on host 5~10min before turning on 
the unit for heating, then turn on indoor fan coil to heat directly after water in pipeline become warmer; when 
there is connected control between host and fan coil, turn on a fan coil first and turn on host for 5~10min, turn 
on the fan coil in room that needs heating after water in pipeline become warmer. These can prevent cool wind 
from blowing out in the first few minutes when fan coil is just turned on. 

6. Common Malfunction and Solution 

When problem occurs during operation, please contact with local dealer or office. 

The following phenomena are not malfunctions: 

1) When cooling (heating in winter), if load is low (i.e. quantity of fan coils that operate is small), 

temperature of system water will be decreased (increased) rapidly, so that antifreeze (anti high-temp) 
protection may occur until water temperature return (decline) to setting temp.

 

2) During heating, heat exchanger will frost for surface temperature of it is lower than outer ambient 

temperature and lower than 0

 so that heat exchanging efficiency is affected, thus the control system will 

periodically defrost to melt the frost on the surface of heat exchanger. 

3) When unit is used in the area where temperature in winter is below 0

, if system is in standby state 

(power is not cut off), and ambient temp. and system water temp. are about 0

, in order to prevent water 

system from freezing and damaging equipments, control system will conduct auto antifreeze operation, and 
start water pump and compressor until water temperature reaches safe point.

 During dealing with problems, professional personnel can remove malfunctions by referring to the 

following table: 

Summary of Contents for HL10WSZ-K

Page 1: ...tion Manual Z Series Combination Household Townhouse Central Air Conditioning Unit GREE ELECTRIC APPLIANCES INC OF ZHUHAI Please read this manual carefully before using this product and keep it properly for future reference ...

Page 2: ... breaking if it is not sure whether water in pipeline is drained clearly do add antifreeze into the system pipeline 3 Don t cut off power when unit is off or auto antifreeze operation protection will be ineffective Warning 1 Please have the unit installed by authorized service center Improper installation may cause water leakage electric shock and fire etc 2 Don t use or store flammable and explos...

Page 3: ...ditions Ambient outdoor temperature for heat pump operation must be from 20 to 24 At the same time Ambient outdoor temperature range for cooling operation must be from 16 to 43 Furthermore water temperature must be under 50 In order to avoid freezing the double tube heater exchanger water temperature must be beyond 5 9 To be in compliance EN 61000 3 11 the product shall be connected only to a supp...

Page 4: ...7 5 Daily Operation and Maintenance 8 6 Common Malfunction and Solution 8 7 Terminal Facilities and Selection Guideline 10 8 System Installation 10 8 1 Unit Installation 10 8 2 Installation of terminal facilities 12 8 3 Water Pipe Connection 13 8 4 Anti freezing Notices 14 9 System Adjustment 15 9 1 Charge of Refrigerated Water to Air Conditioning System 15 9 2 Check before Trial Run 15 9 3 Trial ...

Page 5: ...galvanized pipe or seamless steel pipe It can also adopt new types of pipes such as PVC pipe PPR pipe or aluminum plastic pipe etc 2 Product Features 1 Humanized design i e both split installation and integral installation are available 2 Ultra thin indoor unit design whose height is only 288mm to make hoisting easy 3 Adopting casing heat exchanger to enhance unit performance antifreeze ability an...

Page 6: ...ectric heater is recommended This part is optional users can choose according to following table after consulting professionals HL R 8WZ K HL R 10WSZ K HL R 12 5WSZ K HL R 15WSZ K 2 kW 3 kW 5 kW 7 kW 3 2 Outline Sketch of Unit 3 2 1 Outline Dimension of Outdoor Unit Outline dimension diagram of HLR8WZNa M O Unit mm 950 572 412 378 340 840 Outline dimension diagram of HLR10WZNa M O HLR12 5WZNa M O ...

Page 7: ...I HLR10WZNa M I HLR12 5WZNa M I HLR15WZNa M I Unit mm 572 1100 450 512 288 3 2 3 Outer Wiring Diagram of Unit PE L PE L1 L2 L3 N N L1 L2 L3 N L N Power 220 240V 50Hz Power 380 415V 50Hz Electric conteol box for indoor unit Electric conteol box for outdoor unit Main board Display board Main board 4 core twisted pair wire 2 core twisted pair wire ...

Page 8: ...n when it is code it displays specific error refer to Malfunction Error List but no temperature unit Individual temperature or parameter may exceed 99 then adopt AX for 100 109 bX for 110 119 CX for 120 129 dX for 130 139 EX for 140 149 FX for 150 159 and X stands for a number between 0 9 Under normal state it shows temperature for back water 7 Parameter list It means the value shown at present ma...

Page 9: ... when electrified reset and quick test It also sounds when button is pressed and when there is key error under unit on state When unit is operating in anti high temperature or antifreeze buzzer doesn t sounds 4 5 Basic operation 1 Turn On Press On once when unit is off then unit be in waiting state and LCD displays temperature of water back and operation mode cooling or heating When it detected th...

Page 10: ... no meaning to cooling only unit 18 Communication state 19 Error in history 5 Turn On Off Auxiliary Heater It is only available for heat pump unit Press Check once to enter Check mode Press and to change check object press Check again till the present check object becomes 17 value 17 switches between 01 03 auxiliary heater on and 00 02 auxiliary heater off That is 00 Off 01 On 00 Off or 02 Off 03 ...

Page 11: ...matically F1 Antifreeze temp sensor 1 error Resumes automatically F2 Antifreeze temp sensor 2 error Resumes automatically F3 Defrost temp sensor 1 error Resumes automatically F4 Defrost temp sensor 2 error Resumes automatically F5 Exhaust temp sensor 1 error Resumes automatically F6 Exhaust temp sensor 2 error Resumes automatically F7 Outdoor ambient temp sensor error Resumes automatically F8 Wate...

Page 12: ...ation protection effective 7 For heat pump unit after long time for not operation water in the pipeline will share the same temperature with ambient water thus note to anti cool wind in winter when unit is heating to the situation of no connected control system between host and fan coil it is better to turn on host 5 10min before turning on the unit for heating then turn on indoor fan coil to heat...

Page 13: ... Cooling effect is bad A Freon in cooling system leaks B Heat preservation of water pipe is bad C Water flow quantity is not enough D Heavy dust on condenser E Cooling system is blocked Check and repair or recharge Freon Strengthen heat preservation Clean water filter Clean condenser Check or replace dry filter 6 ompressor frequently is on and off A Too much refrigerant B Circulation of water syst...

Page 14: ...apacity of the fan coil 8 System Installation 8 System Installation Do have the unit installed by authorized company or professional central air conditioning installation project company don t try to install it by yourself 8 1 Unit Installation 8 1 1 Selection of installation location 1 This Household Townhouse unit can be installed on roof ceiling special flat or other place that is easy for inst...

Page 15: ...r unit Whole installation Indoor unit M10 bolt Outdoor unit L4 L2 L1 Air outlet vent L2 Air intake vent Unit mm Shown distance L1 L2 L3 L4 Distance 500 1000 500 500 Split type installation Installation for outdoor unit L2 L4 L1 L3 Air intake vent Air outlet vent Unit mm Shown distance L1 L2 L3 L4 Distance 500 1000 500 500 ...

Page 16: ...ete base with expand bolts 2 It is also available to adopt angle iron or steel supporter that make off channel steel add shake absorbing gaskets and then place the unit on floor or roof Ensure to keep the unit horizontally 8 2 Installation of terminal facilities Installation of indoor terminal fan coil should obey the installation regulation for air conditioning facilities 1 Suspend the fan coil a...

Page 17: ...board to live wire short connected before outgoing Method of shutting off the power is cutting off the air switch Contact diatance between the electrodes of the air switch must be beyond 3 mm Installation should conform to the local electric standard The appliance shall be installed in accordance with natioal wiring regulations 8 3 Water Pipe Connection During connecting water pipe please screw of...

Page 18: ...eaving air in the pipe Auto exhaust valve must be prepared at the highest point at water return pipe 11 Drainage valve should be installed at the lowest point of water pipe 12 Thermometer and hydraulic pressure meter must be set at water in and water out pipe of unit for convenient check when unit is operating 13 Water pipe must conduct heat preservation and moisture proof to prevent loss of cooli...

Page 19: ...here is gas inside fan coil 9 2 2 Check unit 1 Check if the outer appearance of unit and pipeline system is damaged when transporting or conveying 2 Check if wiring terminals for electric components inside unit is loose if phase sequence is correct 3 Check if vane of fan motor would intervene the outer case and net cover when rotating 4 Check if temperature sensor had inserted well if it is loose ...

Page 20: ... long time Note For above mentioned trial run parameters please take the latest released control logic as reference 10 Usage Instruction for Accessories 10 1 Auto water fill valve Application specification water replenishing valve with stabilivolt and pressure relief equipment can automatically keep hydraulic pressure of system at a stable value If pressure of the system decreases the valve will o...

Page 21: ...gher than operation pressure of system and be installed at place that is easier to product pressure convergence such as near expand water case or water pump There usually is a drainage pipe at outlet of valve for easy drainage User can manually turn the hand wheel to release pressure Note This accessory h ad been installed inside the unit unprofessional personnel please don t turn or assemble it 1...

Page 22: ...Gree Electric Appliances Inc of Zhuhai Jin Ji West Road Qianshan Zhuhai Guangdong 519070 P R China http www gree com GREE 66172102 ...

Reviews: