Technical Information

Service Manual

5) System high-pressure protection

a. When the high-pressure switch detects the system pressure higher than limit ,then the high-pressure switch cuts off, the system will stop 
to run.
b.If high-pressure protection is detected for two times within one hour, only by cutting off the power and then reenergize that the compressor 
can restart.

6) Compressor overload protection

No matter the compressor is on or off, when the compressor overload switch is detected activated, the system will stop and indoor unit 
will display H3. If the compressor overload protection appears for more than 6 times, in this case, only by cutting off the power and then 
reenergize that the compressor can restart. If the running duration of the compressor is longer than 30min, the protection times will be 
cleared to zero. 

7) Antifreeze protection

Under cooling and dry mode, 6minutes after the compressor is started:
When it is detected for 3 minutes successively that Tevap. Is less than -2

O

C(varying with indoor unit), the antifreeze protection will be 

activated, in which case the outdoor unit will immediately shut off the indoor electronic expansion valve and the capacity will be set to “0”.
If Tevap. exceed 13

O

C and the compressor has remained at OFF for at least 3minutes, the compressor will resume its original operation 

state. 

8) IPM Protection

 

a. When the IPM module protection is detected, the unit will stop as the indoor temperature reaching set temperature, PFC is closed, 
display IPM protection malfunction. After the compressor stops for 3min, the unit will resume operation status automatically; if the IPM 
protection is detected for more than 6 times continuously (If the running time of the compressor is longer than 10min, the protection times 
record will be cleared), the system will stop and send the signal of module protection to indoor unit. The unit can not resume operation 
status automatically, but can resume running only after cutting off the power and then putting through the power. 
b. IPM module overheating protection 
(a) When TIPM

88

O

C, prohibit to raise frequency; 

(b) When 88

O

C

TIPM

95

O

C, the operation frequency of compressor lows down 1HZ/1s; 

(c) When TIPM

100

O

C, the compressor stops. After the compressor stops for 3min, if TIPM

77

O

C, the compressor and the outdoor fan 

will resume operation. 

9) DRED function

If the power of DRED device is supplied by switching power supply, when different DRED signals are received, the corresponding 
optocouplers are put through to make the AD sample circuit on the main board detect the different voltages. Different voltages are 
corresponding to different DRED modes. After entering DRED mode, the indoor unit displays the corresponding operation code of DRED 
mode. 
d1: Outdoor compressor stops; 
d2: The electricity consumption of complete unit in 30min is less than or equals to 50% of rated electricity consumption; 
d3: The electricity consumption of complete unit in 30min is less than or equals to 75% of rated electricity consumption

Summary of Contents for GWHD(36)NK3JO

Page 1: ...1 Technical Information Service Manual 1 Summary Part Technical Information Outdoor Unit GWHD 36 NK3JO GWHD 42 NK3JO...

Page 2: ...thod Electron expansion valve Electron expansion valve Cooling Operation Ambient Temperature Range O C 7 48 7 48 Heating Operation Ambient Temperature Range O C 15 30 15 30 Condenser Material Aluminum...

Page 3: ...Diameter of Gas Pipe GREE Allocation Metric 2 9 52 9 52 Outer Diameter of Liquid Pipe GREE Allocation Metric 3 6 6 Outer Diameter of Gas Pipe GREE Allocation Metric 3 9 52 9 52 Outer Diameter of Liqu...

Page 4: ...4 Technical Information Service Manual 3 Outline Dimension Diagram 631 401 1016 1098 1106 361 440 Unit mm...

Page 5: ...ve Compressor Silencer Gas Liqiud Separator Heat Exchanger Heat Exchanger Heat Exchanger Heating Cooling Outdoor Unit Indoor Unit Electronic Expansion Valve High Pressure Swicth Filter Filter Stop Val...

Page 6: ...IC UNIT INDOOR REACTOR A 50K 15K CN803 RT1D RT2A RT2B RT2C RT2D RT3A RT3B RT3C RT3D CN802 20K 20K 20K 20K 20K 20K 20K RT1C RT1B RT1A 20K 20K SAT X1 PE PE 4YV EKV A LX1 2 LX1 1 LX2 1 LX2 2 XTC N 1 2 3...

Page 7: ...N 1 2 3 XTB XTA N L N 1 2 3 N 1 2 3 PE N 1 2 3 N 1 2 3 N 1 2 3 XT RT2A E RT1B C RT1D RT1A XTA E XT 4YV EKV A E AP1 RT3A E 1 3 5 7 9 EKV B EKV C EKV D PE PE PE 20K BU BN BU BN BU BU BU BN BU RD BK YE W...

Page 8: ...overload protector 7 HPP terminals of high pressure switch 8 EVA EVE terminals of EXV electronic expansion valve 9 CN802 CN803 terminals of temperature sensor 10 Network wire of DRED 11 COMU terminal...

Page 9: ...rst then restart under the required mode e Defrosting function When the defrosting condition is satisfied the 4 way valve reverses the direction the outdoor fan stop After the 4 way valve reverses the...

Page 10: ...ected the unit will stop as the indoor temperature reaching set temperature PFC is closed display IPM protection malfunction After the compressor stops for 3min the unit will resume operation status a...

Reviews: