70
Installation and Maintenance
Service Manual
ƹ
Malfunction display: E4 Compressor Exhaust High Temperature Protection
ƹ
Malfunction display: E5 Compressor Overheat
Abnormal overcurrent
Check if compressor’s connection line is
properly connected
Adjust compressor’s connection line
Check if current value is higher than the protector’s setting
Replace overcurrent protector
If unit’s high pressure is norma
R
l
efer to high pressure protection
If voltage is normal
Contact the power supply
company
Replace mainboard
Discharge temperature protection
Measure if compressor’s discharge
temperature has reached 115
℃
System pipeline leaks so complementation is needed.
Please add refrigerant according to the amount
specified in the nameplate
Measure if temperature sensor’s
resistance value is correct
Replace the outdoor
unit mainboard
Replace relevant discharge
temperature sensor
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No