Service Manual
9. Maintenance
9.1 Error Code List
NO.
Malfunction
Name
Display Method of Indoor Unit
Display Method of Outdoor
Unit
A/C status
Possible Causes
Dual-8
Code
Display
Indicator Display (during
blinking, ON 0.5s and OFF
0.5s)
Indicator has 3 kinds of
display status and during
blinking, ON 0.5s and OFF
0.5s
Operation
Indicator
Cool
Indicator
Heating
Indicator
Yellow
Indicator
Red
Indicator
Green
Indicator
1
High
pressure
protection of
system
E1
During cooling and drying
operation, except indoor
fan operates, all loads stop
operation.
During heating operation, the
complete unit stops.
Possible reasons:
1. Refrigerant was superabundant;
2. Poor heat exchange (including
filth blockage of heat exchanger
and bad radiating environment );
Ambient temperature is too high.
2
Antifreezing
protection
E2
OFF 1S
and blink
3 times
During cooling and drying
operation, compressor and
outdoor fan stop while indoor
fan operates.
1. Poor air-return in indoor unit;
2. Fan speed is abnormal;
3. Evaporator is dirty.
3
Refrigerant
leakage
protection
F0
OFF 1S
and
blink
9 times
The Dual-8 Code Display will
show F0 and the complete unit
stops.
1.Refrigerant leakage;
2.Indoor evaporator temperature
sensor works abnormally;
3.The unit has been plugged up
somewhere.
4
High
discharge
temperature
protection of
compressor
E4
OFF 1S
and blink
7 times
During cooling and drying
operation, compressor and
outdoor fan stop while indoor
fan operates. During heating
operation, all loads stop.
Please refer to the malfunction
analysis (discharge protection,
overload).
5
Overcurrent
protection
E5
OFF 1S
and blink
5 times
During cooling and drying
operation, compressor and
outdoor fan stop while indoor
fan operates. During heating
operation, all loads stop.
1. Supply voltage is unstable;
2. Supply voltage is too low and
load is too high;
3. Evaporator is dirty.
6
Communi
cation
Malfunction
E6
Always
During cooling operation,
compressor stops while
indoor fan motor operates.
During heating operation, the
complete unit stops.
Refer to the corresponding
malfunction analysis.
7
High
temperature
resistant
protection
E8
OFF 1S
and blink
6 times
During cooling operation:
compressor will stop while
indoor fan will operate.
During heating operation, the
complete unit stops.
Refer to the malfunction analysis
(overload, high temperature
resistant).
8
EEPROM
malfunction
EE
OFF 1S
and blink
11 times
During cooling and drying
operation, compressor will stop
while indoor fan will operate;
During heating operation, the
complete unit will stop
Replace outdoor control panel AP1
9
Limit/
decrease
frequency
due to high
temperature
of module
EU
All loads operate normally,
while
operation frequency for
compressor is decreased
Discharging after the complete unit
is de-energized for 20mins, check
whether the thermal grease on
IPM Module of outdoor control
panel AP1 is sufficient and whether
the radiator is inserted tightly.
If its no use, please replace control
panel AP1.
10
Malfunction
protection of
jumper cap
C5
Wireless remote receiver and
button are effective, but can
not dispose the related
command
1. No jumper cap insert on
mainboard.
2. Incorrect insert of jumper cap.
3. Jumper cap damaged.
4. Abnormal detecting circuit of
mainboard.
62
£
Installation and Maintenance
Summary of Contents for GWH18YE-S6DBA2A/I
Page 10: ...Service Manual Technical Information 7 ...
Page 24: ...Service Manual Technical Information 21 ...
Page 76: ...Service Manual 5 C om m unica tion M alfunction E6 Installation and Maintenance 73 ...
Page 77: ...Service Manual 6 M a lfu nction o f d e tecting plate W IFI JF Installation and Maintenance ...
Page 83: ...Service Manual 80 Installation and Maintenance ...