background image

2

0

1.

15

15

15

Max. length of 

connection pipe(m)

20

25

25

30

30

30

30

5000Btu/h (1465W)

7000Btu/h (2051W)

9000Btu/h (2637W)

12000Btu/h (3516W)

18000Btu/h (5274W)

24000Btu/h (7032W)

28000Btu/h (8204W)

36000Btu/h (10548W)

42000Btu/h (12306W)

48000Btu/h (14064W)

Cooling capacity 

Max. length of connection pipe

Pipe expanding method

pipe cutter

pipe

Configuration of connection pipe

A: Cut the pipe

2.

3.

 

Additional refrigerant charging amount for R32

Liquid pipe

Gas pipe

1/4''

1/4'' or 3/8''

1/2''

5/8''

3/4''

7/8''

_

3/8'' or 1/2''

5/8'' or 3/4''

3/4'' or 

7/8''

Piping size

_

(g / m)

(g / m)

1'' or 1 1/4''

Coolin

on

ly

cooling and

heating

16

40

Coolin

onl

y,

cooling and heating

(g / m)

80

136

200

200

280

280

48

24

12

12

200

280

96

96

40

16

Indoor unit throttle

Outdoor unit throttle

leaning   uneven      burr

Standard length of connection pipe: 5m, 7.5m, 

8m.

Min. length of connection pipe.

For the unit with standard connection pipe of 5m, 

there is no limitation for the min length of con- 

nection pipe. For the unit with standard connec- 

tion pipe of 7.5m and 8m, the min length of con- 

nection pipe is 3m.

Max. length of connection pipe is shown as below.

4.

(1)

(2)

The calculation method of additional refrigerant oil 

and refrigerant charging amount after prolong-

ing connection pipe.

After the length of connection pipe is prolonged 

for 10m at the basis of standard length, you should 

add 5ml of refrigerant oil for each additional 5m 

of connection pipe.

The calculation method of additional refrigerant 

charging amount (on the basis of liquid pipe):

Confirm the pipe length according to the distance 

of indoor unit and outdoor unit.

Cut the required pipe with pipe cutter.

NOTICE

The additional refrigerant charging amount in Sheet is 

recommended value, not compulsory.

NOTICE

Improper pipe expanding is the main cause of refriger-

ant leakage. Please expand the pipe according to the 

following steps:

Additional refrigerant charging amount=

prolonged length of liquid pipe × additional 

refrigerant charging amount per meter

Basing on the length of standard pipe, add 

refrigerant according to the requirement as 

shown in the table. The additional refrigerant 

charging amount per meter is different accord- 

ing to the diameter of liquid pipe.

See Sheet .

Summary of Contents for GWH07AGA-K6DNA1A/I

Page 1: ...on and introduction of remote controller 20 Configuration of connection pipe Specialist s Manual 22 NOTE Actual product may be different from graphics please refer to actual products Thank you for cho...

Page 2: ...9AGB K6DNA1B I GWH09AGC K6DNA1F I GWH12AGB K6DNA1A I GWH12AGB K6DNA4A I GWH12AGC K6DNA1A I GWH12AGC K6DNA1F I GWH18AGD K6DNA1A I GWH18AGD K6DNA1D I GWH18AGD K6DNA1E I GWH18AGD K6DNA4A I GWH24AGD K6DNA...

Page 3: ...reasons This symbol indicates the possibility of death or serious injury This symbol indicates the possibility of injury or damage to property Indicates important but not hazard related information u...

Page 4: ...aware that refrigerants may not contain an odour Read specialist s manual All the work men who are engaging in the refrig eration system should bear the valid certification awarded by the authoritati...

Page 5: ...erant If you should cut or weld the refrigerant system pipes in the process of maintaining please foll ow the steps as below c Vacuuming d e Cutting or welding Clean it with N2 gas f Carry back to the...

Page 6: ...ir conditioner Unstable power supply or incorrect wiring may result in electric shock fire haza rd or malfunction Please install proper power supply cables before using the air conditioner The groundi...

Page 7: ...must be po sitioned so that the plug is accessible For the air conditioner with plug the plug should be re achable after finishing in stallation For the air conditioner with out plug a circuit breaker...

Page 8: ...by the manufacturer its ser vice agent or similarly qua lified persons in order to avoid a hazard Do not connect air condi tioner to multi purpose soc ket Otherwise it may cau se fire hazard Do discon...

Page 9: ...It may cause mal function Do not step on top panel of outdoor unit or put heavy objects It may cause dam age or personal injury When below phenomenon occurs please turn off air conditioner and discon...

Page 10: ...ystem pre ssure rise or compressor rupture resulting in injury Measuring tape spanner Inner hexagon When installing or moving this unit do not charge the refrigerant which is not comply with that on t...

Page 11: ...e requirement of air conditioner Unstable power supply or incorrect wiring or malfunction Pl ease install proper power supply cables before using the air conditioner grounding wire of power socket 5 B...

Page 12: ...es when opening the hole bellmouth Pretighten the union nut with hand Please refer to the actual circumstances for the number of screws and the position of screws rear right 1 7 The pipe can be led ou...

Page 13: ...ross hole at the back of indoor unit and then pull it out from the front side panel screw wiring cover outlet pipe drain hose All wires of indoor unit and outdoor unit should be If the length of power...

Page 14: ...on pipe drain hose with the band drain hose band indoor power cord Put the bound pipes in the wall pipe and then Bind up the connection pipe power cord and NOTICE make them pass through the wall hole...

Page 15: ...on 1 2 3 Clean and maintenance 2 WARNING WARNING Please contact qualified professionals for service Error Code Error code F2 E8 Troubleshooting C5 F0 F1 U8 H6 H3 E1 E5 E6 Notice for recovery 1 Clean s...

Page 16: ...ck the batteries If the power of batter s e i o l is too w please rep lace them Under heating mode indoor temperature is reached to set temp erature Power failure Is plug loose In order to prevent blo...

Page 17: ...turn off the air conditioner When the air conditioner is turned on it will operate under auto mode Display Temp indicator Power indicator This is the general introduction and the color of indicator i...

Page 18: ...t Clock Operation mode Set time TIMER ON TIMER OFF Turbo mode Send signal Auto mode Cool mode Left right swing Up down swing Child lock Dry mode Fan mode Heat mode Temp I feel Set fan speed display ty...

Page 19: ...multifunction For the functions which the model doesn t have if press the corresponding button on the remote controller the unit will keep the original running status After putting through the power...

Page 20: ...ngle When selecting air condition er is blowing fan at xed position Horizontal louver will stop at the xed position Press or button once increase or decr ease set temperature 1 F Holding or button 2s...

Page 21: ...display the corresponding temperature of last setting sleep curve and blink The first entering will display according to the initial curve setting value of original factory 2 Adjust and button could...

Page 22: ...usted Under 8 heating function set temperature can t be adjusted Press TURBO button and the remote controller won t send signal Sleep function and 8 heating function can t operate at the same time If...

Page 23: ...f the auto clean function When the auto clean func tion is turned on indoor unit displays CL During the auto clean process of evaporator the unit will perform fast cooling or fast heating There may be...

Page 24: ...function or damage the parts Is there any obstruction in the air inlet and outlet Is heat insulation of pipe line sufficient It may cause malfunction or damage the parts The gas valve and liquid valve...

Page 25: ...m and 8m the min length of con nection pipe is 3m Max length of connection pipe is shown as below 4 1 2 The calculation method of additional refrigerant oil and refrigerant charging amount after prolo...

Page 26: ...fferent according to the diameter please refer to the sheet below DB WB C any blemish expand the port again according to the steps above Outdoor side DB WB C Maximum GWH12AGC K6DNA1F I LC GWH09AGC K6D...

Page 27: ...al ed or intrinsically safe Presence of fire extinguisher If any hot work is to be conducted on the refrigera tion equipment or any associated parts appropriate Ventilated area Ensure that the area is...

Page 28: ...and being used correctly the recovery process is supervised at all times by a competent person d Pump down refrigerant system if possible e If a vacuum is not possible make a manifold so that refrige...

Page 29: ...refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder and the relevant waste transfer note arranged Do not mix refrigerants in recovery units and especially not i...

Page 30: ...GREE ELECTRIC APPLIANCES INC OF ZHUHAI Tel 86 756 8522218 Fax 86 756 8669426 E mail global cn gree com Web www gree com Add West Jinji Rd Qianshan Zhuhai Guangdong China 519070 600005062912...

Reviews: