background image

Specialist’s Manual

Repair to intrinsically safe components

Do  not  apply  any  permanent  inductive  or  capaci-

tance loads to the circuit without ensuring that this 

will not exceed the permissible voltage and current 

permitted for the equipment in use.

Intrinsically safe components are the only types that 

can be worked on while live in the presence of a fl- 

ammable atmosphere. The test apparatus shall be 

at the correct rating.

Replace components only with parts specified by the 

manufacturer. Other parts may result in the ignition 

of refrigerant in the atmosphere from a leak.

● 

Cabling

Check that cabling will not be subject to wear, cor- 

rosion, excessive pressure, vibration, sharp edges 

or  any  other  adverse  environmental  effects.  The 

check  shall  also  take  into  account  the  effects  of 

aging or continual vibration from sources such as 

compressors or fans.

● 

Detection of flammable refrigerants

Under no circumstances shall potential sources of 

ignition be used in the searching for or detection of 

refrigerant leaks. A halide torch (or any other detec- 

tor using a naked flame) shall not be used.

● 

Leak detection methods

Leak detection fluids are suitable for use with most 

refrigerants but the use of detergents containing ch- 

lorine shall be avoided as the chlorine may react 

with the refrigerant and corrode the copper pipe-work.

● 

Decommissioning

Before carrying out this procedure, it is essential that 

the technician is completely familiar with the equip- 

ment and all its detail. It is recommended good pr- 

actice  that  all  refrigerants  are  recovered  safely. 

Prior to the task being carried out, an oil and refri- 

gerant sample shall be taken in case analysis is re- 

quired prior to re-use of reclaimed refrigerant. It is 

essential  that  electrical  power  is  available  before 

the task is commenced.

a) Become familiar with the equipment and its opera- 

tion.

b) Isolate system electrically.

c) Before attempting the procedure, ensure that:

– mechanical handling equipment is available, if

required, for handling refrigerant cylinders;

– all  personal  protective  equipment  is  available

and being used correctly;

– the recovery process is supervised at all times

by a competent person;

● 

d) Pump down refrigerant system, if possible.

e) If a vacuum is not possible, make a manifold so

that refrigerant can be removed from various parts 

of the system.

f) Make sure that cylinder is situated on the scales

before recovery takes place.

g) Start the recovery machine and operate in accor- 

dance with manufacturer's instructions.

h) Do not overfill cylinders. (No more than 80% vo- 

lume liquid charge).

i) Do not exceed the maximum working pressure of

the cylinder, even temporarily.

j) When the cylinders have been filled correctly and

the process completed, make sure that the cylinders 

and the equipment are removed from site promptly 

and all isolation valves on the equipment are closed 

off.

k) Recovered refrigerant shall not be charged into

another refrigeration system unless it has been clean- 

ed and checked.

Labelling

● 

Recovery

When  removing  refrigerant  from  a  system,  either 

for servicing or decommissioning, it is recommend-

ed good practice that all refrigerants are removed 

safely.

When transferring refrigerant into cylinders, ensure 

that only appropriate refrigerant recovery cylinders 

are employed. Ensure that the correct number of cy- 

linders for holding the total system charge are av- 

ailable. All cylinders to be used are designated for 

the recovered refrigerant and labelled for that refri- 

gerant (i.e. special cylinders for the recovery of refri- 

gerant). Cylinders shall be complete with pressure-re- 

lief valve and associated shut-off valves in good work- 

ing order. Empty recovery cylinders are evacuated 

and, if possible, cooled before recovery occurs.

The recovery equipment shall be in good working 

order  with  a  set  of  instructions  concerning  the 

equipment that is at hand and shall be suitable for 

the recovery of all appropriate refrigerants includ-

ing, when applicable, flammable refrigerants. In ad- 

● 

– recovery  equipment  and  cylinders  conform  to

the appropriate standards.

2

5

Equipment shall be labelled stating that it has been 

de-commissioned and emptied of refrigerant. The 

label shall be dated and signed. For appliances con-

taining flammable refrigerants, ensure that there are 

labels on the equipment stating the equipment con-

tains flammable refrigerant.

Summary of Contents for GWC09ACC-K6DNA1C/I

Page 1: ...t s Manual 21 Configuration of connection pipe 05 Installation notice Installation of indoor unit 07 Thank you for choosing our product Please read this Owner s Manual carefully before operation and retain it for future reference If you have lost the Owner s Manual please contact the local agent or visit www gree com or send an email to global cn gree com for the electronic version NOTE Actual pro...

Page 2: ...09ACC K6DNA4A I GWH09ACC K6DNA5A I GWC12ACC K6DNA1D I GWH12ACC K6DNA1D I GWH12ACC K6DNA1F I GWH12ACC K6DNA1X I GWH12ACC K6DNA1Z I GWH12ACC K6DNA2D I GWH12ACC K6DNA3D I GWH12ACC K6DNA4D I GWH12ACC K6DNA5D I GWH12ACC K6DNA5F I GWC18ACD K6DNA1D I GWH18ACD K6DNA1D I GWH18ACD K6DNA1I I GWH18ACD K6DNA2D I GWH18ACD K6DNA3D I GWH18ACD K6DNA4D I GWH18ACD K6DNA5D I GWH18ACD K6DNA5I I GWH18ACD K6DNA1Z I GWH1...

Page 3: ...g reasons This symbol indicates the possibility of death or serious injury This symbol indicates the possibility of injury or damage to property Indicates important but not hazard related information used to indicate risk of property damage If it needs to install move or maintain the air conditioner please contact dealer or local service center to conduct it at first Air conditioner must be instal...

Page 4: ...ears the qualification for using the flamm operating electric heater Do not pierce or burn Appliance shall be installed operated and stored in a room with a floor area larger than Xm 2 including children with reduced physical sensory or d n a e c n e i r e p x e f o k c a l r o s e i t i l i b a p a c l a t n e m knowledge unless they have been given superv ision or instruction concerning use of t...

Page 5: ...gerant If you should cut or weld the refrigerant system pipes in the process of maintaining please foll ow the steps as below c Vacuuming d e Cutting or welding Clean it with N2 gas f Carry back to the service spot for welding Filling the refrigerant The refrigerant should be recycled into the sp ecialized storage tank Make sure that there isn t any naked flame ne ar the outlet of the vacuum pump ...

Page 6: ...air conditioner Unstable power supply or incorrect wiring may result in electric shock fire haza rd or malfunction Please install proper power supply cables before using the air conditioner The grounding resistance should comply with nation al electric safety regula tions Air Conditioner should be properly grounded Inco rrect grounding may cause electric shock Do not put through the power before f...

Page 7: ... must be po sitioned so that the plug is accessible For the air conditioner with plug the plug should be re achable after finishing in stallation For the air conditioner with out plug a circuit breaker must be installed in the line The yellow green wire in air conditioner is ground ing wire which can t be us ed for other purposes The air conditioner is the first class electric applian ce It must b...

Page 8: ... by the manufacturer its ser vice agent or similarly qua lified persons in order to avoid a hazard Do not connect air condi tioner to multi purpose soc ket Otherwise it may cau se fire hazard Do disconnect power supp ly when cleaning air condi tioner Otherwise it may cause electric shock Do not wash the air condi tioner with water to avoid electric shock Do not spray water on in door unit It may c...

Page 9: ...t It may cause mal function Do not step on top panel of outdoor unit or put heavy objects It may cause dam age or personal injury When below phenomenon occurs please turn off air conditioner and disconnect power immediately and then contact the dealer or qualified professionals for service Power cord is overheat ing or damaged There s abnormal sound during operation Circuit breaker trips off frequ...

Page 10: ...n serious safety accident Tools for installation 5 Safety precautions for installing and relocating the unit sure that the unit is running in cooling mode Then fully close the valve at high pressure side liquid valve About 30 40 seconds later fully close the valve at low pressure side gas valve immediately stop the unit and disconnect power Please note that the time for refrigerant recovery should...

Page 11: ...the requirement of air conditioner Unstable power supply or incorrect wiring or malfunction Pl ease install proper power supply cables before using the air conditioner grounding wire of power socket 5 Be sure to cut off the power supply before pr oceeding any work related to electricity and safety 8 2 Select a location where the condensation water 3 Select a location which is convenient to conne c...

Page 12: ...res when opening the hole bellmouth Pretighten the union nut with hand Please refer to the actual circumstances for the number of screws and the position of screws rear right 1 7 The pipe can be led out in the direction of right Choose the position of piping hole according Adjust the torque force by referring to the wrench on the union nut Tighten the union nut with torque wrench When installation...

Page 13: ...ue N m NOTE Add insulating pipe in the indoor drain hose in order to prevent condensation The plastic expansion particles are not provided All wires of indoor unit and outdoor unit should be If the length of power connection wire is insufficient For the air conditioner with plug the plug should be NOTICE connected by a professional Make the power connection wire go through the cable cross hole at ...

Page 14: ...d pipes in the wall pipe and then make them pass through the wall hole Hang the indoor unit on the wall mounting frame Stuff the gap between pipes and wall hole with sealing gum Fix the wall pipe Check if the indoor unit is installed firmly and closed to the wall Remove the wire clip connect the power conn ection wire to the wiring terminal according to the color tighten the screw and then fix the...

Page 15: ...ng bracket for outdoor unit is damaged or corroded If yes please contact dealer The filter should be cleaned every three months If there is much dust in the operation environme After removing the filter do not touch fins to avoid injury Do not use fire or hair dryer to dry the filter to avoid deformation or fire hazard When air conditioner status is abnormal tempe rature indicator on indoor unit w...

Page 16: ...nd or contraction of panel or other parts due to the change of temp erature In order to prevent blowing out cold air indoor unit will be started after delaying for several minutes which is a normal phenomenon Phenomenon Heating mode is turned on just now Reinsert the plug Odours are emitted Set tempe Air switch trips off or fuse is burnt out Set temperature Signal receiving range is 8m Whether the...

Page 17: ... please use aux button to turn on or turn off the air conditioner The operation in details is as below As shown in the figure open panel and press aux button to turn off the air conditioner When the air conditioner is turned on it will operate under auto mode aux button filter air inlet panel horizontal louver air outlet Temp indicator Dry mode Power indicator Heat mode Cool mode R only for heat m...

Page 18: ...nt temp Sleep mode Clock Health mode I feel Quiet TIMER ON TIMER OFF Auto mode Cool mode Dry mode Fan mode Left right swing Up down swing Child lock Send signal Turbo mode Heat mode Operation mode Set fan speed Temp display type Introduction for icons on display screen Buttons on remote controller Operation and introduction of remote controller ...

Page 19: ...have turn ed off the unit After energization X FAN OFF is defaulted X FAN is not available in auto fan or heat mode This function indicates that moisture on evaporator of indoor unit will be blowed after the unit is stopped to avoid mould NOTE button to adjust fan blowing angle When selecting heat mode the air conditioner operates under heat mode Press or button to adjust set temperature Press FAN...

Page 20: ...tomat ically swing up down at maximum angle When selecting air condition er is blowing fan at fixed position Horizontal louver will stop at the fixed position When selecting air conditioner is blowing fan at fixed angle Horizontal louver will send air at the fixed angle Hold button above 2s to set your required swing angle When reaching your required angle release the button no display horizontal louv...

Page 21: ...emperature In Heat mode sleep status after run for one hour the setting tem perature will decrease 1 two hours setting temperature will decrease 2 then the unit will run at this setting temperature Sleep 2 is sleep mode 2 that is air conditioner will run according to the presetting a group of sleep temperature curve Sleep 3 the sleep curve setting under Sleep mode by DIY 1 Under Sleep 3 mode press...

Page 22: ...status Operation for TIMER ON TIMER OFF is the same Press this button to set clock time icon on remote controller will blink Press or button within 5s to set clock time Each pressing of or button clock time will increase or decrease 1 minute If hold or button 2s later time will change quickly Release this button when reaching your required time Press CLOCK button to confirm the time icon stops bli...

Page 23: ...t temperature when turning on the unit There is no display in the remote control ler Only for the models whose indoor unit has dual 8 dis play When selecting displaying of indoor or outdoor ambi ent temperature indoor temperature indicator dis plays corresponding temperature and automatically turn to display set temperature after three or five se conds 8 C heating function Under heat mode press TE...

Page 24: ... along the arrow direction Replace two 7 AAA 1 5V dry batteries and make sure the position of polar and polar are correct Reinstall the cover of battery box 2 1 3 battery remove reinstall Cover of battery box signal sender Auto clean function This function is only available for some models NOTE Under unit off status hold MODE and FAN buttons simultaneously for 5s to turn on or turn off the auto cl...

Page 25: ...lfunction or damage the parts Is there any obstruction in the air inlet and outlet Is heat insulation of pipe line sufficient It may cause malfunction or damage the parts The gas valve and liquid valve of connection pipe are open completely The dust and sundries caused during installation are removed It may cause condensation and water dripping It may cause electric leakage Is the inlet and outlet...

Page 26: ...5m and 8m the min length of con nection pipe is 3m Max length of connection pipe is shown as below 4 1 2 The calculation method of additional refrigerant oil and refrigerant charging amount after prolong ing connection pipe After the length of connection pipe is prolonged for 10m at the basis of standard length you should add 5ml of refrigerant oil for each additional 5m of connection pipe The cal...

Page 27: ...s from getting into the pipe pipe any blemish expand the port again according to the steps above 43 26 Outdoor side Indoor side DB WB C DB WB C 32 23 24 18 Maximum cooling 27 GWH18ACD K6DNA1X I heating For some models Maximum NOTE 48 30 Outdoor side Indoor side DB WB C DB WB C 24 18 Maximum cooling GWC24ACE K6DNA1A I 27 32 23 heating Maximum NOTE NOTE ture for cooling only unit is 15 C 48 C The op...

Page 28: ...oling NOTE ature for Low temperature cooling only unit is 15 C 50 C for heat pump unit is 15 C 50 C Indoor side DB WB C Outdoor side DB WB C Maximum cooling Maximum heating NOTE Indoor side DB WB C Maximum heating GWH09ACC K6DNA1F I LC GWH12ACC K6DNA1F I LC GWH18ACD K6DNA1I I LC GWH18ACD K6DNA5I I LC GWH09ACC K6DNA1F I LCLH GWH12ACC K6DNA1F I LCLH GWH12ACC K6DNA5F I GWH18ACD K6DNA1I I LCLH GWH18AC...

Page 29: ...eal ed or intrinsically safe Presence of fire extinguisher If any hot work is to be conducted on the refrigera tion equipment or any associated parts appropriate Ventilated area Ensure that the area is in the open or that it is ad equately ventilated before breaking into the system or conducting any hot work A degree of ventilation shall continue during the period that the work is carri ed out The...

Page 30: ...e and being used correctly the recovery process is supervised at all times by a competent person d Pump down refrigerant system if possible e If a vacuum is not possible make a manifold so that refrigerant can be removed from various parts of the system f Make sure that cylinder is situated on the scales before recovery takes place g Start the recovery machine and operate in accor dance with manuf...

Page 31: ...d refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder and the relevant waste transfer note arranged Do not mix refrigerants in recovery units and especially not in cylinders If compressors or compressor oils are to be remov ed ensure that they have been evacuated to an ac ceptable level to make certain that flammable refri gerant does not remain within the lu...

Page 32: ...GREE ELECTRIC APPLIANCES INC OF ZHUHAI 600005060453 Add West Jinji Rd Qianshan Zhuhai Guangdong China 519070 Tel 86 756 8522218 Fax 86 756 8669426 E mail global cn gree com Web www gree com ...

Reviews: