DC Inverter U-match Series Floor Ceiling Type Unit
30
Reference A
Coupler heat insulation
(large) on the pipe
Front outlet
Reference A:
Cover this portion with heat
insulating material also without fail
Coupler heat
insulation (small)
on the pipe
No gap
Heat insulation pipe
Liquid pipe
Gas pipe
3.2.3.6 Sealing of the Knock-off Hole
As for the built-in valve model, during the installation process for
connection pipe, when the connection pipe is passing through the
knock-off hole, conduct sealing with insulated cotton in the knock-off
hole of outdoor unit to prevent small animals from entering. See the
following figure.
Notice:
Only for the GUD100W/NhA-T, GUD125W/NhA-T,
GUD140W/NhA-T, GUD100W/NhA-X, GUD125W/NhA-X,
GUD140W/NhA-X, GUD160W/NhA-X units.
3.2.4 Connection Pipe Vacuum Pumping and Leak Detection
3.2.4.1 Vacuum Pumping
NOTICE
Make sure the outlet of vacuum pump is away from fire source and is
well-ventilated.
(1) Remove the caps of the liquid valve, gas valve and also the service
port.
(2) Connect the hose at the low pressure side of the manifold valve