DC Inverter U-match Series Duct Type Unit
48
GUD160PH/B-S+GUD160W/NhB-X,
GUD160PHS/B-S+GUD160W/NhB-X
Ś
Power cords 5×1.5mm
2
ś
Power cords 3×1.0mm
2
Ŝ
Communication cords 2×0.75mm²
ŝ
Communication cords 2×0.75mm²
Ş
Connection wires of DRED module
(5) Electrical wiring of indoor unit and outdoor unit.
WARNING!
(1) High and low voltage wires should be led through different rubber rings of the
electric box cover.
(2) Do not bundle up the connection wire and communication wire of wired
controller or lay them side by side, otherwise errors will occur.
(3) High and low voltage wires should be secured separately. Secure the former
ones with big clamps and the latter ones with small clamps.
(4) Use screws to tighten up the connection wires and power cords of indoor and
outdoor units on the terminal board. Wrong connection may lead to fire hazard.
(5) If the connection wires of indoor unit (outdoor unit) and power cords are not
correctly connected, the air conditioner may get damaged.
(6) Ground the indoor and outdoor units through connecting the ground wire.
(7) The units should comply with applicable local and national rules and
regulations on power consumption.
(8) When connecting the power cord, make sure the phase sequence of the power
supply matches with the corresponding terminals, otherwise the compressor
will get reversed and operate abnormally.