background image

14

Technical Information

Service Manual

Pressure—Temperature Chart

 HC Refrigerant R-290  

 Temperature  

 Absolute pressure  

 Gauge pressure  

 °C  

°F 

 kPa  

 bar  

 PSI  

 kPa(g)  

 bar(g)  

 PSI(g)  

 -40  

 -40  

 111,12  

 1,11  

 16,12  

 11,12  

 0,11  

 1,61  

 -39  

 -38,2  

 116,00  

 1,16  

 16,83  

 16,00  

 0,16  

 2,32  

 -38  

 -36,4  

 121,05  

 1,21  

 17,56  

 21,05  

 0,21  

 3,05  

 -37  

 -34,6  

 126,27  

 1,26  

 18,31  

 26,27  

 0,26  

 3,81  

 -36  

 -32,8  

 131,66  

 1,32  

 19,10  

 31,66  

 0,32  

 4,59  

 -35  

 -31  

 137,23  

 1,37  

 19,90  

 37,23  

 0,37  

 5,40  

 -34  

 -29,2  

 142,97  

 1,43  

 20,74  

 42,97  

 0,43  

 6,23  

 -33  

 -27,4  

 148,90  

 1,49  

 21,60  

 48,90  

 0,49  

 7,09  

 -32  

 -25,6  

 155,02  

 1,55  

 22,48  

 55,02  

 0,55  

 7,98  

 -31  

 -23,8  

 161,33  

 1,61  

 23,40  

 61,33  

 0,61  

 8,89  

 -30  

 -22  

 167,83  

 1,68  

 24,34  

 67,83  

 0,68  

 9,84  

 -29  

 -20,2  

 174,54  

 1,75  

 25,31  

 74,54  

 0,75  

 10,81  

 -28  

 -18,4  

 181,44  

 1,81  

 26,32  

 81,44  

 0,81  

 11,81  

 -27  

 -16,6  

 188,56  

 1,89  

 27,35  

 88,56  

 0,89  

 12,84  

 -26  

 -14,8  

 195,89  

 1,96  

 28,41  

 95,89  

 0,96  

 13,91  

 -25  

 -13  

 203,43  

 2,03  

 29,51  

 103,43  

 1,03  

 15,00  

 -24  

 -11,2  

 211,19  

 2,11  

 30,63  

 111,19  

 1,11  

 16,13  

 -23  

 -9,4  

 219,18  

 2,19  

 31,79  

 119,18  

 1,19  

 17,29  

 -22  

 -7,6  

 227,39  

 2,27  

 32,98  

 127,39  

 1,27  

 18,48  

 -21  

 -5,8  

 235,84  

 2,36  

 34,21  

 135,84  

 1,36  

 19,70  

 -20  

 -4  

 244,52  

 2,45  

 35,46  

 144,52  

 1,45  

 20,96  

 -19  

 -2,2  

 253,44  

 2,53  

 36,76  

 153,44  

 1,53  

 22,26  

 -18  

 -0,4  

 262,61  

 2,63  

 38,09  

 162,61  

 1,63  

 23,58  

 -17  

 1,4  

 272,03  

 2,72  

 39,45  

 172,03  

 1,72  

 24,95  

 -16  

 3,2  

 281,70  

 2,82  

 40,86  

 181,70  

 1,82  

 26,35  

 -15  

 5  

 291,62  

 2,92  

 42,30  

 191,62  

 1,92  

 27,79  

 -14  

 6,8  

 301,81  

 3,02  

 43,78  

 201,81  

 2,02  

 29,27  

 -13  

 8,6  

 312,27  

 3,12  

 45,29  

 212,27  

 2,12  

 30,79  

 -12  

 10,4  

 323,00  

 3,23  

 46,85  

 223,00  

 2,23  

 32,34  

 -11  

 12,2  

 334,00  

 3,34  

 48,44  

 234,00  

 2,34  

 33,94  

 -10  

 14  

 345,28  

 3,45  

 50,08  

 245,28  

 2,45  

 35,58  

 -9  

 15,8  

 356,85  

 3,57  

 51,76  

 256,85  

 2,57  

 37,25  

 -8  

 17,6  

 368,70  

 3,69  

 53,48  

 268,70  

 2,69  

 38,97  

 -7  

 19,4  

 380,85  

 3,81  

 55,24  

 280,85  

 2,81  

 40,73  

 -6  

 21,2  

 393,29  

 3,93  

 57,04  

 293,29  

 2,93  

 42,54  

 -5  

 23  

 406,04  

 4,06  

 58,89  

 306,04  

 3,06  

 44,39  

 -4  

 24,8  

 419,09  

 4,19  

 60,78  

 319,09  

 3,19  

 46,28  

 -3  

 26,6  

 432,45  

 4,32  

 62,72  

 332,45  

 3,32  

 48,22  

 -2  

 28,4  

 446,13  

 4,46  

 64,71  

 346,13  

 3,46  

 50,20  

 -1  

 30,2  

 460,13  

 4,60  

 66,74  

 360,13  

 3,60  

 52,23  

 0  

 32  

 474,46  

 4,74  

 68,82  

 374,46  

 3,74  

 54,31  

 1  

 33,8  

 489,11  

 4,89  

 70,94  

 389,11  

 3,89  

 56,44  

 2  

 35,6  

 504,10  

 5,04  

 73,11  

 404,10  

 4,04  

 58,61  

 3  

 37,4  

 519,43  

 5,19  

 75,34  

 419,43  

 4,19  

 60,83  

 4  

 39,2  

 535,10  

 5,35  

 77,61  

 435,10  

 4,35  

 63,11  

 5  

 41  

 551,12  

 5,51  

 79,93  

 451,12  

 4,51  

 65,43  

 6  

 42,8  

 567,49  

 5,67  

 82,31  

 467,49  

 4,67  

 67,80  

 7  

 44,6  

 584,22  

 5,84  

 84,74  

 484,22  

 4,84  

 70,23  

 8  

 46,4  

 601,31  

 6,01  

 87,21  

 501,31  

 5,01  

 72,71  

 9  

 48,2  

 618,77  

 6,19  

 89,75  

 518,77  

 5,19  

 75,24  

 10  

 50  

 636,60  

 6,37  

 92,33  

 536,60  

 5,37  

 77,83  

Summary of Contents for GPC12AL-K5NNA3A

Page 1: ...Service Manual Models Change for life GREE ELECTRIC APPLIANCES INC OF ZHUHAI GPC12AL K5NNA3A GPH12AL K5NNA3A Refrigerant R290 ...

Page 2: ...fety Precautions 33 8 Installation Precaution 39 9 Install 41 9 1 Install Wire Hook 41 9 2 Removing Collected Water 41 9 3 Installation in a double hung sash window 43 9 4 Installation in a sliding sash window 44 9 5 Installation and Disassembly of heat Discharge Pipe 46 9 6 Operation test 47 10 Maintenance 48 10 1 Error Code 48 10 2 Malfunction Detection Flowchart 50 10 3 Maintenance Method for C...

Page 3: ...easy access as it is needed for reference during installation maintenance service and operation of the unit This manual does not cover all aspects of installation maintenance and service of the chiller units if additional information is General Information Warning and cautions appear at appropriate locations throughout this manual book Abbreviations Used Within this Manual INTRODUCTION Abbreviatio...

Page 4: ...rules of air conditioning electrics and refrigerant handling of the country within which the equipment is installed attention to this information Information window highlighting section or additional information to consider This sign will indicate that you are and the surrounding environment can possibly contain it This is a general warning sign The Label is used to indicate that present within th...

Page 5: ...efrigerant R 290 propane This condition requires special safety precautions to be observed While working on the system the presence of any kind of ignition sources e g sparks open flames hot surfaces static electricity are strictly prohibited At the X Q X Likewise ensure the installation site is well ventilated For further details as far as it concerns the handling of the refrigerant R 290 propane...

Page 6: ...ge of potential leakage points of refrigeration air conditioning and heat pump equipment Making a visual and manual inspection of the whole system Carry out a check for leakage of the system using an indirect method and or one of the direct methods Direct leak detection methods 1 Fixed leakage detection systems 2 Portable electronic gas detectors 4 Weak soapy water solution bubble test also in com...

Page 7: ...usting the safety and control switches Checking the hot gas and liquid lines in correct positions Start up and shut down a condenser and check the good working conditions including by making measurements during operation Checking the surface of the condenser The basic functioning of an evaporator including defrosting system Installation of an evaporator including control and safety equipment Adjus...

Page 8: ...purities which would damage the refrigeration system and may Please notice that the unit is filled with propane Details to this refrigerant are found in chapter refrigerant Propane is highly Q X of people and material The structural formula of HC R 290 propane HC R 290 refrig erant has a high grade of purity Propane as a cooking gas is not useful for refrigeration purpose Important Refrigerant Pro...

Page 9: ...m skin eye contact with liquid Liquid release or vapour pressure jets present a risk of serious damage to the eyes Abuse involving inhalation of high concentrations of vapour even for short periods which can produce unconsciousness or may prove fatal Inhalation may cause irritation to the nose and throat headache nausea vomiting dizziness and drowsiness In poorly ventilated areas unconsciousness o...

Page 10: ...n with sterile dressings Do not use ointments or powders Obtain medical assistance immediately Eyes with a sterile dressing and obtain medical assistance immediately Z J X X etc Q Use water spray to cool heat exposed containers and to protect surroundingareas and personnel effecting the shut off Every precaution must be taken to keep containers cool to avoid the possibilityof a boiling liquid expa...

Page 11: ... to avoid damage for people and property particular requirements are listed hereafter Before servicing the unit the surrounding area were the work will be done must be clear of safety hazards to ensure safe working Nevertheless it is required to carry out a risk assessment in order to minimise the risk of ignition of R 290 2 It is recommended to isolate the working environment in order to keep out...

Page 12: ... to place and then to leave the cylinder on a digital scale Pay attention V J complete volume by liquid refrigerant The pressure must be controlled in order to ensure that the permissible pressure of the cylinder is not exceeded at any time After filling the cylinder must be marked with the mass and the type of refrigerant recovered The recovery machine should be operated until the pressure reduce...

Page 13: ...vention into a refrigeration system repairing leaks replacing components brazing the system must be subject to a leak test and following strength test of the system Repair of Leaks Regular professional brazing experience is an important pre condition for the work with hydrocarbon refrigerants The use OFDN is an important precondition for professional leak repair 1 System flush ing from HC 2 Inert ...

Page 14: ...evant emergency procedures Portable HC Gas Detector R 290 is available in a large variety of different cylinders which are to be distinguished valves often with own special construction of valves in order to distinguish them from the cylinders of different refrigerants Q different countries These requirements must be studied and adhered to Principally the following regulations in dealing with R 29...

Page 15: ...rs should be stored and operated only in an upright position 6 Choose appropriate measures to prevent static charges 7 Please remember that the maximum quantity of stored refrigerant sometimes might be regulated by national regulations Basically the following must be regarded concerning the transport of R290 cylinders 1 During the transportation of R290 always carry along printed information about...

Page 16: ...2 53 36 76 153 44 1 53 22 26 18 0 4 262 61 2 63 38 09 162 61 1 63 23 58 17 1 4 272 03 2 72 39 45 172 03 1 72 24 95 16 3 2 281 70 2 82 40 86 181 70 1 82 26 35 15 5 291 62 2 92 42 30 191 62 1 92 27 79 14 6 8 301 81 3 02 43 78 201 81 2 02 29 27 13 8 6 312 27 3 12 45 29 212 27 2 12 30 79 12 10 4 323 00 3 23 46 85 223 00 2 23 32 34 11 12 2 334 00 3 34 48 44 234 00 2 34 33 94 10 14 345 28 3 45 50 08 245...

Page 17: ... 87 34 93 2 1189 12 11 89 172 47 1089 12 10 89 157 97 35 95 1217 88 12 18 176 64 1117 88 11 18 162 14 36 96 8 1247 16 12 47 180 89 1147 16 11 47 166 38 37 98 6 1276 94 12 77 185 21 1176 94 11 77 170 70 38 100 4 1307 24 13 07 189 60 1207 24 12 07 175 10 39 102 2 1338 07 13 38 194 07 1238 07 12 38 179 57 40 104 1369 42 13 69 198 62 1269 42 12 69 184 12 41 105 8 1401 31 14 01 203 25 1301 31 13 01 188...

Page 18: ...rt Ė Technical Information YB1F2 XFAN Remote Controller FAN AUTO OPER AIR HEALTH FILTER TURBO ON OFF X FAN HOUR HUMIDITY ON OFF MODE FAN X FAN TURBO TEMP TIMER SLEEP LIGHT Model Product Code Remote Controller GPC12AL K5NNA3A CK010031700 YB1F2 XFAN GPH12AL K5NNA3A CK010031600 YB1F2 XFAN ...

Page 19: ...lication Area m2 15 22 15 22 Climate Type T1 T1 Isolation I I Moisture Protection IPX0 IPX0 Permissible Excessive Operating Pressure for the Discharge Side MPa 3 0 3 0 Permissible Excessive Operating Pressure for the Suction Side MPa 1 5 1 5 Throttling Method Capillary Capillary Defrosting Method Fuse current A 3 15 3 15 Operation Temp o C 16 30 16 30 Ambient Temp Cooling o C 16 35 16 35 Ambient T...

Page 20: ...trifugal Diameter Length DXL mm J J Fan Motor Speed H M L rpm 1050 960 870 1050 960 870 Output of Fan Motor W 16 16 Fan Motor RLA A 0 3 0 3 Fan Motor Capacitor 3 5 3 5 Form Aluminum Fin copper Tube Aluminum Fin copper Tube Pipe Diameter mm Z mm 3 1 3 3 1 3 Coil Length LXDXW mm 442X38 1X228 6 442X38 1X228 6 Swing Motor Model Output of Swing Motor W Condenser Fan Type Centrifugal Centrifugal Fan Dia...

Page 21: ...19 Technical Information Service Manual 390 820 405 Unit mm GPC12AL K5NNA3A GPH12AL K5NNA3A 3 Outline Dimension Diagram ...

Page 22: ...S HOT DISCHARGED AIR COOLED AIR COMPRESSOR CENTRIFUGAL FAN CAPILLARY CENTRIFUGAL FAN REFRIGERANT FLOW DIRECTION NOTES COOLING MODE HEATING MODE HOT AIR INDOOR COILS COOLED AIR 4 Way valve OUTDOOR COILS HOT DISCHARGED AIR COMPRESSOR CENTRIFUGAL FAN CENTRIFUGAL FAN CAPILLARY REFRIGERANT FLOW DIRECTION COOLED AIR INDOOR COILS ...

Page 23: ...K Black VT Violet OG Orange 5 Electrical Part 5 1 Wiring Diagram Model GPC12AL K5NNA3A 5 0 2 5 63 5 5 9 5 2 5 6 7 7 5 9 28778 57 78 1 1 57 57 32 5 1 1 1 1 8 8 1 6 203 1 63 5 5 63 63 3 3 0 2 1 1 02725 2 1 1 5 83 1 02725 1 0 1 3 3 0 1 2 5 203 3 3 5 1 3 1 3 3 3 63 0 1 3 5 8 3 6 1625 78 7 03 5220 5220 7 03 6 1625 28778 7 03 6 1625 2 1 2 1 1 1 203 3 0 1 2 5 7 1 7 5 7 5 1 8 8 1 1 8 6 60000700085201 ...

Page 24: ... 02725 2 1 1 5 83 1 02725 1 0 1 3 3 0 1 2 5 203 3 3 5 1 3 1 3 3 3 63 0 1 3 5 8 3 6 1625 78 7 03 5220 5220 7 03 6 1625 28778 7 03 6 1625 2 1 2 1 1 1 203 3 0 1 2 5 7 1 7 5 7 5 1 8 2 8 1 1 8 6 1 9 9 9 97 97 97 These wiring diagrams are subject to change without notice please refer to the one supplied with the unit Model GPH12AL K5NNA3A 600007061057 ...

Page 25: ...al between two main boards Interface of up fan motor between two main boards Interface of four way valve between two main boards Interface of water motor between two main boards Interface of water motor between two main boards Compressor relay Interface of live wire between two main boards Interface of down fan motor between two main boards 5 6 7 8 9 10 NO NAME 1 2 3 4 5 6 7 8 9 10 ...

Page 26: ...24 Technical Information Service Manual TOP VIEW BOTTOM VIEW Interface of main board 2 Silk screen on display board ...

Page 27: ...splay Note You must connect the heat discharge pipe before operating cooling or drying mode No need for only fan mode Heat Cool Heat Unit only Under this mode heating mode indicator is bright Dual 8 nixie tube displays set temperature Temperature setting range is 16 C 30 C 4 FAN button 5 Timer button ª ª ª Z ª V J ª ª ª Z ª J ª ª ª Z ª J 5s If timer function is started up the upper indicator will ...

Page 28: ...status How to use the remote control Point the remote control toward the Signal receiver and press the desired button The unit generates a beep when it receives the signal X X V CAUTION Y Q This may adversely affect its operation This may adversely affect its operation Y moisture and shock To prevent the remote control from beingmisplaced hook it to the unit when not in use When attached to remove...

Page 29: ...tdoor ambient temp FAN OPER AUTO HEALTH AIR FILTER TURBO ON OFF X FAN HOUR HUMIDITY TIMER ON TIMER OFF Set time Light Send signal Health mode X fan Set fan speed Set temperature Turbo mode This is a general use remote controller it could be used for the air conditionerswith multifunction For some function which the model doesn t have if pressthe corresponding button on the remote controller that t...

Page 30: ...utton simultaneously to switch between simple swing setting and fixed angle swing setting During switching the two swing settings icon will blink for 2s Press this button to turn on the unit Press this button again to turn off the unit This indicator is not This indicator is not This indicator is available for some models available for some models not available for some models ...

Page 31: ...no display no display swing angle is displayed dynamically horizontal louvers stops at current position swing angle is displayed dynamically Note This function is applicable to partial of models NOY L TIZOUT OY GVVROIGHRK ZU VGXZOGR UL SUJKRY ...

Page 32: ...Battery Cover of battery box Remove Reinstall Press this button under cooling heating mode can start up sleep function Press this button again to cancel sleep function icon on remote controller will be displayed icon will be displayed on remote controller ...

Page 33: ...auto fan shift 3 4 TIMER Function a TIMER ON It can set timer on when the system is off the setting time range is 0 5h 24h when the time of setting timer on reaches and the system runs with the previous setting mode b TIMER OFF It can set timer on when the system is on the setting time range is 0 5h 24h when the time of setting timer off reaches the system stop to work K a TIMER ON If set timer on...

Page 34: ... off the light 5S later Remote control light button does not controlled by failure display 3 9 Protection Function Q When the anti freeze protection is inspected the compressor stops fan motor runs with setting fan speed When the anti freeze protection is canceled and reaches to the 3min time delay it runs with the original status Temperature sensor failure inspection a Environment temperature sen...

Page 35: ...ng wire of the air conditioner 7 The power cord and power connection wires cant be pressed by hard objects 8 If power cord or connection wire is broken it must be 9 For the air conditioner without plug an air switch must be installed in the circuit The air switch should be all pole parting and the contact parting distance should be more than 3mm 10 Check if there is electric leakage on the unit bo...

Page 36: ...installation manual first Before repair the appliance read the service manual first Appliance filled with flammable gas R290 Appliance shall be installed operated and stored in a room with a floor area larger The appliance shall be stored in a room without continuously operating ignition sources an operating gas appliance or an operating electric heater The appliance shall be stored in a well vent...

Page 37: ...ion of Environment 1 Ensure that electric product with radiation is power off in the maintenance area All the persons in the room shall turn off the mobile phone 2 Check if there is refrigerant leakage in the maintenance area Ensure that all the leak testers are suitable for this air conditioner 3 Ensure that the room area reaches the requirement 4 Check if the maintenance area is ventilated Keep ...

Page 38: ... cut of the power of the air conditioner before opening the sealing cover If it is necessary to use power supply perform leak test to prevent potential danger 8 Do not replace the case which may affect the protective grade V reach the requirement of the suppler 2 Maintenance of Refrigeration System 1 Do not lengthen or cut the connecting pipe 2 If the system component such as evaporator condenser ...

Page 39: ...detector No Remove panel Leakage Leakage test for the complete unit Remove front case Remove the shielding box of electric box The qualified parts provided by manufacturer Release the refrigerant referigerant Leakage test Recharge Pressure test Yes Replace main board ...

Page 40: ...anual Replace pipeline or repair welding 7 Release the Yes Recharge refrigerant Leakage test refrigerant Pressure test Clean the system Leakage Replace pipeline or weld pipeline system parts Leakage No Yes Assembly is finished ...

Page 41: ...ts for electric connection Safety precaution 1 Must follow the electric safety regulations when installing the unit 3 For appliances with type Y attachment the instructions shall contain the substance of the following If the supply cord is damaged it 4 Properly connect the live wire neutral wire and grounding wire of power socket 5 Be sure to cut off the power supply before proceeding any work rel...

Page 42: ...n connector heat discharge pipe Optional Window kit Bracket Rain guard Insect guard net Window panel Exhaust cover Adjustment panel Extension panel screw remote control pipe hoop pipe clip rubber plug sponge A sponge B FAN AUTO OPER AIR HEALTH FILTER TURBO ON OFF X FAN HOUR HUMIDITY ON OFF MODE FAN X FAN TURBO TEMP TIMER SLEEP LIGHT Preparation before Installation Note check if the accessories are...

Page 43: ...x the drainage pipe clip on the right of rear side plate near drainage port with a screw As show in Fig 3 2 Remove the rubber plug at drainage port As show in Fig 4 3 Put the drainage pipe into drainage port and screw it up and then bind it with pipe hoop Q Q Fig 5 1 Use the continuous drainage option from the lower hole NOTICE When using the continuous drainage option from the bottom hole install...

Page 44: ... from the middle hole NOTICE 1 Remove the continuous drain cap 1 by turning it counter clockwise then remove the rubber stopper 2 from the spout As show in Fig 7 2 Screw the drain connector to included in the package the spout by turning clockwise As show in Fig 8 3 Insert the drainage hose into drain connector As show in Fig 9 ATTENTION When using continuous drainage option from the middle hole p...

Page 45: ...ble to shut the exhaust cover 1 Open the window sash and place the window panel on the window sill As show in Fig 13 2 Secure the window panel to the window stool with 2 screws As show in Fig 14 Inner width of the window 20 5 520mm 38 5 980mm Use the window panel and the adjustment panel 1 Open the window sash and place the window panel on the window sill As show in Fig 15 3 Secure the window pane...

Page 46: ...ow panel As show in Fig 23 Side A will now be at the top as indicated in the diagram when it is installed in the window 3 Cut the foam seal A adhesive type to the proper length and attach it to the window frame As show in Fig 24 4 Install the window panel into the window frame As show in Fig 25 Make sure that the exhaust cover is attached to the window panel Inner height of the window 20 5 520mm U...

Page 47: ...indow frame Q As show in Fig 29 3 Secure the window panel to the window frame with 4 screws As show in Fig 30 5 Close the window sash securely against the Window panel As show in Fig 31 6 Stuff the foam seal B between the glass and the window to prevent air and insects from getting into the room As show in Fig 32 7 Attach the bracket with a screw Recommended As show in Fig 33 Please lay a tabular ...

Page 48: ...in Fig 11 3 Lead the exhaust hose outdoors As shown in Fig 12 4 Slide and open the exhaust cover on the window panel and attach the window adapter Optional As shown in Fig 13 clockwise clockwise joint A joint B C heat discharge pipe 9 5 Installation and Disassembly of heat Discharge Pipe groove clasp the side with TOP is upwards heat discharge As shown in Fig 13 V V Note of Install heat discharge ...

Page 49: ... As shown in Fig 17 2 Remove joint A Press the clasp and lift joint A upwards to remove it As shown in Fig 18 3 Remove the window adapter Pull out and remove the window adapter by pushing down two PUSH markings and slide and close the exhaust cover in the window panel Optional joint B C PUSH PUSH upwards clasp disassemble joint A _ X 9 6 Operation test ...

Page 50: ...ure sensor is open short circuited F2 OFF 3S and blinks twice Compressor and draw water motor stop operation Fan stop operation after 2min 1 The wiring terminal between indoor evaporator temperature sensor and main board is loosened or poorly contacted 2 Theres short circuit due to the trip over of the parts on main board 3 Indoor evaporator temperature sensor is damaged Please check it by referri...

Page 51: ...oor fan keeps on running other loads stop operation 1 Heat exchangers are too dirty or the air inlet outlet is blocked 2 Fan motor is not working Abnormal fan speed fan speed is too low or the fan doesnt run 3 Compressor doesnt work normally Strange noise or leakage occurs Temperature of the shell is too high 4 System is blocked inside dirt block ice block oil block Y valve not fully open 5 Draw w...

Page 52: ...oosened or poorly contacted Insert the temperature sensor tightly Yes Is malfunction eliminated Is there short circuit due to trip over of the parts Make the parts upright Is malfunction eliminated Replace the mainboard with the same model End No Is the temperature sensor normal according to the Resistance Table Replace it with a temperature sensor with the same model Yes Is malfunction removed No...

Page 53: ...door outdoor heat exchanger too dirty or are the air inlet and outlet blocked Normal fluctuation is within 10 of the rated voltage on the nameplate Malfunction is eliminated No No No No No No No No No No No No No Malfunction is eliminated Malfunction is eliminated Malfunction is eliminated Malfunction is eliminated Malfunction is eliminated Malfunction is eliminated Troubleshooting for E5 malfunct...

Page 54: ...r wires for water level switch are connected tightly Adjust connection Whether malfunction is eliminated Whether malfunction is eliminated Replace water level switch Replace the main board with the same model Discharge water by referring to instruction manual Whether malfunction is eliminated Yes Yes Yes Yes Yes No No No End No No ...

Page 55: ... Remove blockage in the system System is blocked inside dirt block ice block oil block Y valve no fully open Compressor doesn t work normally Strange noise or leakage occurs Make compressor run normally Casing is too hot Replace a main board with the same model Malfunction is eliminated Malfunction is eliminated Malfunction is eliminated Malfunction is eliminated Troubleshooting for F0 malfunction...

Page 56: ...tor is not working Abnormal fan speed fan speed is too low or the fan doesn t run End Remove blockage in the system System is blocked inside dirt block ice block oil block Y valve no fully open Compressor doesn t work normally Strange noise or leakage occurs Make compressor run normally Casing is too hot Replace a main board with the same model Malfunction is eliminated Malfunction is eliminated M...

Page 57: ...rk normally Strange noise or leakage occurs Make compressor run normally Casing is too hot Replace a main board with the same model Malfunction is eliminated Malfunction is eliminated Malfunction is eliminated Malfunction is eliminated Malfunction is eliminated Troubleshooting for E8 malfunction Yes No No No No No No No No No No Yes Malfunction is eliminated Yes No No Yes Yes Yes Yes Yes Yes Yes Y...

Page 58: ...or buttons have no action Replace batteries for remote controller Repair or replace remote controller Water inside water chassis is full Dual8 nixie tube displays H8 and buzzer gives Z Discharge condensate water Malfunction of water level switch Check water level switch and connection refer Possible Causes Discriminating Method Air conditioner Status Troubleshooting Set temperature is improper Obs...

Page 59: ...asure the capacity of fan capacitor with an the deviation range indicated on the nameplate of fan capacitor Replace the compressor capacitor Power voltage is a little low or high Use universal meter to measure the power supply voltage The voltage is a little high or low Suggest to equip with voltage regulator Coil of compressor is burnt out Use universal meter to measure the resistance between com...

Page 60: ...58 Maintenance Service Manual The component picture is only for reference please refer to the actual product GPC12AL K5NNA3A 11 Exploded View and Parts List ...

Page 61: ...ar Grill 01476050 1 24 Diversion Circle Upper 10376065 1 25 Right Side Plate 200086000002 1 26 Clamp 7101600502 2 27 Rear Plate 2002450001001 1 28 Cable Cross Plate 2611622601 1 29 Cover of drainage hole 2224609703 1 30 Rubber Plug 76716054 1 31 Filter Sub assy 1 1112604201 1 32 Front Grill 2241607401 1 33 Centrifugal Fan 10316071 1 34 Motor Holder Upper 26156104 1 35 Fan Motor 15010100013402 1 36...

Page 62: ...2000350002501 1 64 Air Louver 1 1051610001 1 65 Air Louver 2 1051610101 2 66 Air Louver 3 1051610201 2 67 Front Panel 200003000009 1 68 Decorative Strip 2300010007101 1 69 Front Panel Sub Assy 209004000025 1 70 Capillary Sub assy 030006060314 1 71 Inhalation Tube Sub assy 030010000240 1 72 Discharge Tube 035008060733 1 73 Supporting Strip 01796007 1 74 Detecting Plate 75 Power Cord 4002046423 1 76...

Page 63: ...r reference please refer to the actual product 38 39 36 29 27 25 24 23 46 40 44 37 33 32 31 20 16 14 18 17 13 12 10 7 8 4 6 1 2 3 73 71 67 66 65 64 63 59 56 55 54 53 52 47 11 9 15 21 22 28 30 51 50 45 58 60 61 62 72 70 68 69 41 5 34 75 76 81 78 79 80 77 35 57 26 19 42 43 74 49 48 ...

Page 64: ...023 1 23 Rear Grill 01476040 1 24 Diversion Circle Upper 10376065 1 25 Right Side Plate 200086000002 1 26 Clamp 7101600502 2 27 Rear Plate 2002450001001 1 28 Cable Cross Plate 2611622601 1 29 Cover of drainage hole 2224609703 1 30 Rubber Plug 76716054 1 31 Filter Sub assy 1 1112604201 1 32 Front Grill 2241607401 1 33 Centrifugal Fan 10316071 1 34 Motor Holder Upper 26156104 1 35 Fan Motor 15010100...

Page 65: ...g Lever 2000350002501 1 64 Air Louver 1 1051610001 1 65 Air Louver 2 1051610101 2 66 Air Louver 3 1051610201 2 67 Front Panel 200003000009 1 68 Decorative Strip 2300010007101 1 69 Front Panel Sub Assy 209004000025 1 70 Capillary Sub assy 030006060315 1 71 4 Way Valve Assy 030152060181 1 72 Magnet Coil 430004017 1 73 Supporting Strip 01796007 1 74 Detecting Plate 75 Power Cord 4002046423 1 76 Remot...

Page 66: ...sy 2 2 Remove left right side plate Z Step Procedure Srews Left right side plate Remove left side plate unscrew 2 screws as diagram shown to remove left side plate Remove right side plate unscrew 2 screws of right side plate to remove it 3 Remove rear plate Q plate to remove the rear plate and cable cross plate and cable cross plate and rubber plug Real plare Screws Cable cross plate Cover of drai...

Page 67: ...over assy Procedure Q front panel to remove the front panel sub assy Unscrew 4 screws to remove the electric box cover assy and wire clamp Screws Screws Screws Electric box cover Wire Clamp Electric box cover assy Front panel sub assy Remove the 4 screws to remove the top cover assy Top cover assy Screws ...

Page 68: ...porting board 3 Unscrew 7 screws to remove the cover of propeller housing Unscrew 5 screws to remove the evaporator assy Screws Screws Screws Evaporator assy Cover of Propeller Housing Remove Supporting Board 3 Remove Cover of Propeller Housing Remove Evaporator Assy Supporting Board 3 ...

Page 69: ... 3 screws to remove the diversion circle and cold plasma generator assy Unscrew 5 screws to remove the nut assy and gasket and centrifugal and motor holder upper Cold Plasma Generator Diversion Circle Screws Nut Nut assy Gasket Gasket M6 Centrifugal Fan Motor Holder upper Screws Fan Motor Rear Grill Cold Plasma Generator assy b a c ...

Page 70: ...s Diversion Circle Rear Grill Unscrew 6 screws to remove the Unscrew 6 screws to remove the diversion circle and rear grill Step Procedure Unscrew screws to remove the nut assy and gasket and centrifugal and motor holder Nut Nut assy Gasket Gasket M6 Centrifugal Fan Motor Holder Screws Fan Motor b a c ...

Page 71: ...ve condenser assy Unscrew 4 screws to remove supporting board 1 and supporting strip Supporting board 1 Screws Screws 4 way valve interface 4 way valve interface Capillary Sub assy Screws Condenser Assy Supporting Strip Unscrew screws to remove the 4 way valve interface and capillary sub assy Unscrew screws to remove condenser assy ...

Page 72: ...h sub assy Unscrew 3 screws to remove the water level switch sub assy Unscrew 3 bolts of compressor chassis then take out gasket to remove compressor Unscrew 2 screws of bottom of sub assy to remove motor sub assy Screws Water level switch sub assy Bolts Screws Z Bolts Compressor ...

Page 73: ...71 Maintenance Service Manual Step Procedure 18 Remove chassis sub assy Q to remove the 4 caster wheels Screws Chassis Sub assy Caster wheels ...

Page 74: ... 16 84 85 84 2 29 39 40 39 2 4 63 62 6 17 86 87 86 30 41 42 41 5 64 65 64 4 18 88 89 87 8 31 43 44 42 8 6 66 67 66 2 19 90 89 6 32 45 44 6 7 68 69 68 20 91 92 91 4 33 46 47 46 4 8 70 71 69 8 21 93 94 93 2 34 48 49 48 2 9 72 71 6 22 95 96 95 35 50 51 50 10 73 74 73 4 23 97 98 96 8 36 52 53 51 8 11 75 76 75 2 24 99 98 6 37 54 53 6 12 77 78 77 25 Fahrenheit display temperature δēε Fahrenheit δēε Cels...

Page 75: ... 2 73 2 358 112 0 717 4 60 23 35 9 779 74 2 28 113 0 697 3 57 18 36 9 382 75 2 206 114 0 678 2 54 31 37 9 003 76 2 133 115 0 66 1 51 59 38 8 642 77 2 064 116 0 642 0 49 02 39 8 297 78 1 997 117 0 625 1 46 6 40 7 967 79 1 933 118 0 608 2 44 31 41 7 653 80 1 871 119 0 592 3 42 14 42 7 352 81 1 811 120 0 577 4 40 09 43 7 065 82 1 754 121 0 561 5 38 15 44 6 791 83 1 699 122 0 547 6 36 32 45 6 529 84 1...

Page 76: ... 31 35 13 04 74 3 04 113 0 93 3 76 24 36 12 51 75 2 94 114 0 904 2 72 41 37 12 76 2 844 115 0 88 1 68 79 38 11 52 77 2 752 116 0 856 0 65 37 39 11 06 78 2 663 117 0 833 1 62 13 40 10 62 79 2 577 118 0 811 2 59 08 41 10 2 80 2 495 119 0 77 3 56 19 42 9 803 81 2 415 120 0 769 4 53 46 43 9 42 82 2 339 121 0 746 5 50 87 44 9 054 83 2 265 122 0 729 6 48 42 45 8 705 84 2 194 123 0 71 7 46 11 46 8 37 85 ...

Page 77: ...0 93 102 3 13 14 342 8 25 49 19 64 10 54 103 3 04 13 323 9 26 47 08 65 10 18 104 2 96 12 306 2 27 45 07 66 9 83 105 2 87 11 289 6 28 43 16 67 9 49 106 2 79 10 274 29 41 34 68 9 17 107 2 72 9 259 3 30 39 61 69 8 85 108 2 64 8 245 6 31 37 96 70 8 56 109 2 57 7 232 6 32 36 38 71 8 27 110 2 50 6 220 5 33 34 88 72 7 99 111 2 43 5 209 34 33 45 73 7 73 112 2 37 4 198 3 35 32 09 74 7 47 113 2 30 3 199 1 3...

Page 78: ...522218 Fax 86 756 8669426 E mail gree gree com cn www gree com HONG KONG GREE ELECTRIC APPLIANCES SALES LIMITED Add Unit 2612 26 F Miramar Tower 132 Nathan Road TST Kowloon HK Tel 852 31658898 Fax 852 31651029 For product improvement specifications and appearance in this manual are subject to change without prior notice ...

Reviews: