71
GMV6 DC Inverter VRF Units Technical Sales Guide
GMV-400WM/H-X
TC—Total capacity of outdoor unit; PI—Power input of outdoor unit
combination
outdoor air
temp
indoor air temperature
℃
DB
16
18
20
21
22
24
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
℃
DB
℃
WB
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
135%
-19.8
-20
37.4
10.80
37.2
11.55
37.1
12.19
37.2
12.61
37.1
13.06
37.1
13.85
-18.8
-19
37.7
10.97
37.7
11.76
37.5
12.28
37.5
12.75
37.5
13.12
37.4
13.95
-16.7
-17
38.4
11.25
38.3
11.98
38.1
12.52
38.2
12.85
38.1
13.27
38.0
14.06
-13.7
-15
39.0
11.50
39.0
12.19
38.8
12.67
38.8
13.04
38.8
13.45
38.7
14.13
-11.8
-13
39.6
11.72
39.6
12.32
39.4
12.75
39.5
13.17
39.4
13.49
39.3
14.18
-9.8
-11
40.3
11.89
40.3
12.49
40.1
12.88
40.1
13.21
40.1
13.51
40.0
14.16
-9.5
-10
40.6
11.94
40.6
12.51
40.4
12.87
40.4
13.20
40.4
13.54
40.3
14.10
-8.5
-9.1
41.0
12.02
40.8
12.54
40.8
12.88
40.7
13.20
40.8
13.51
40.7
14.13
-7
-7.6
41.4
12.07
41.3
12.55
41.3
12.90
41.2
13.17
41.2
13.47
41.1
14.05
-5
-5.6
44.0
12.64
44.0
12.89
43.9
13.48
43.8
13.74
43.9
14.06
43.7
14.53
-3
-3.7
44.6
12.64
44.6
13.12
44.5
13.36
44.5
13.65
44.4
13.88
44.3
14.38
0
-0.7
45.6
12.56
45.6
12.94
45.5
13.17
45.5
13.38
45.4
13.64
45.3
14.04
3
2.2
48.5
12.89
48.4
13.24
48.2
13.43
48.2
13.64
48.2
13.85
48.1
14.23
5
4.1
51.0
13.21
50.8
13.55
50.8
13.71
50.7
13.92
50.7
14.12
50.5
14.48
7
6
53.5
13.52
53.4
13.83
53.4
13.99
53.2
12.66
53.2
14.37
51.1
13.83
9
7.9
56.2
13.80
56.1
14.11
56.1
14.24
56.0
14.43
54.8
14.17
51.1
13.00
11
9.8
59.1
14.08
59.0
14.35
58.7
14.39
56.7
13.85
54.8
13.31
51.1
12.25
13
11.8
62.2
14.34
62.1
14.62
58.7
13.49
56.7
12.98
54.8
12.50
51.1
11.50
15
13.7
65.2
14.59
62.4
13.84
58.7
12.72
56.7
12.25
54.8
11.78
51.1
10.85
18
16.8
65.2
13.81
62.4
13.18
58.7
12.06
56.7
11.64
54.8
11.14
51.1
10.31
20
18.5
65.2
13.15
62.4
12.59
58.7
11.51
56.7
11.12
54.8
10.59
51.1
9.85
24
20.5
65.2
12.57
62.4
12.11
58.7
11.07
56.7
10.69
54.8
10.11
51.1
9.49
120%
-19.8
-20
37.2
11.84
37.1
12.57
37.1
13.12
37.0
13.47
37.1
13.88
37.0
14.69
-18.8
-19
37.5
11.99
37.5
12.71
37.4
13.04
37.4
13.59
37.4
14.00
37.3
14.78
-16.7
-17
38.2
12.20
38.1
12.89
38.1
13.30
38.0
13.71
38.0
14.09
38.0
14.82
-13.7
-15
38.9
12.39
38.8
13.02
38.7
13.46
38.8
13.84
38.7
14.16
38.7
14.85
-11.8
-13
39.5
12.55
39.4
13.10
39.4
13.50
39.4
13.85
39.3
14.20
39.3
14.79
-9.8
-11
40.2
12.66
40.1
13.21
40.0
13.52
40.1
13.90
40.0
14.17
40.0
14.80
-9.5
-10
40.5
12.67
40.4
13.21
40.3
13.54
40.4
13.86
40.3
14.02
40.3
14.71
-8.5
-9.1
40.8
12.73
40.8
13.25
40.7
13.52
40.7
13.83
40.7
14.15
40.6
14.71
-7
-7.6
41.3
12.77
41.2
13.18
41.1
13.47
41.2
13.76
41.1
14.05
41.0
14.53
-5
-5.6
44.0
13.31
43.9
13.78
43.8
14.06
43.8
14.31
43.8
14.58
43.7
15.06
-3
-3.7
44.6
13.27
44.5
13.67
44.4
13.87
44.4
14.12
44.3
14.41
44.3
14.82
0
-0.7
45.6
13.11
45.5
13.45
45.4
13.78
45.4
13.85
45.3
14.09
45.3
14.47
3
2.2
48.4
13.37
48.2
13.69
48.2
13.84
48.1
14.05
48.1
14.24
47.1
14.20
5
4.1
50.8
13.66
50.7
13.97
50.7
14.11
50.5
14.29
50.5
14.48
47.1
13.34
7
6
53.4
13.94
53.4
14.23
53.2
14.36
52.4
14.19
50.7
13.64
47.1
12.55
9
7.9
56.1
14.22
56.0
14.49
54.1
13.86
52.4
13.34
50.7
12.83
47.1
11.82
11
9.8
59.0
14.47
57.5
14.22
54.1
13.04
52.4
12.56
50.7
12.08
47.1
11.14
13
11.8
61.1
14.33
57.5
13.33
54.1
12.24
52.4
11.80
50.7
11.36
47.1
10.48
15
13.7
61.1
13.49
57.5
12.56
54.1
11.55
52.4
11.13
50.7
10.72
47.1
9.89
18
16.8
61.1
12.75
57.5
11.89
54.1
10.97
52.4
10.55
50.7
10.15
47.1
9.39
20
18.5
61.1
12.08
57.5
11.35
54.1
10.50
52.4
10.06
50.7
9.68
47.1
8.94
24
20.5
61.1
11.49
57.5
10.88
54.1
10.12
52.4
9.65
50.7
9.29
47.1
8.57