110
Situation
A+B+C+D
A+B
Situation 3
a≥300
b≥100
c≥100
d≥500
e≥200
f≥600
-
Situation 4
a≥300
b≥100
c≥100
d≥100
e≥200
f≥500
-
Situation 5
a≥300
b≥500
c≥100
d≥500
e≥200
f≥900
-
NOTES:
a. The installation space shown above is based on the cooling operation when the outdoor temperature
is 35°C. If the outdoor temperature exceeds 35°C or the heat load is large, and all outdoor units are
operating at an excess capacity, the space at the suction side should be increased.
b. When disassembling or installing the unit, the operation may be affected by obstacles, and the
distance from the unit to the wall surface may be appropriately increased.
c. When two or more units are installed and placed, the operation may be affected by the adjacent
units. The distance between the two adjacent units is “e” ≥ 100mm.
d. If the unit is installed in the space with four walls, wall height at both side of the unit shall have
no limit; wall height at return air side is below 500mm and at the front side is below 1,500mm.
The unit is installed in a space with only two walls, A and B, and the height of the B wall is not limited.
e. If the wall exceeds the above value, increase the space as follows.