59
GMV6 DC Inverter VRF Units Technical Sales Guide
TC—Total capacity of outdoor unit; PI—Power input of outdoor unit
combination
outdoor air temp
indoor air temperature
℃
DB
16
18
20
21
22
24
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
℃
DB
℃
WB
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
70%
-19.8
-20
20.1
9.15
18.9
8.86
17.7
8.31
17.0
8.11
16.4
7.94
15.5
7.65
-18.8
-19
20.3
9.17
18.9
8.76
17.7
8.25
17.0
8.05
16.4
7.88
15.5
7.49
-16.7
-17
20.3
8.97
19.0
8.57
17.7
8.06
17.0
7.86
16.4
7.66
15.5
7.15
-13.7
-15
20.3
8.77
19.0
8.40
17.7
7.86
17.0
7.46
16.4
7.30
15.5
6.80
-11.8
-13
20.3
8.56
19.0
8.15
17.7
7.50
17.0
7.22
16.4
6.92
15.5
6.45
-9.8
-11
20.4
8.31
19.0
7.85
17.8
7.10
17.1
6.83
16.4
6.56
15.5
6.10
-9.5
-10
20.4
8.18
19.0
7.63
17.8
6.90
17.1
6.64
16.4
6.38
15.5
5.94
-8.5
-9.1
20.4
8.06
19.0
7.42
17.8
6.72
17.1
6.47
16.4
6.21
15.5
5.78
-7
-7.6
20.3
7.69
19.0
7.08
17.7
6.42
17.0
6.18
16.4
5.94
15.5
5.54
-5
-5.6
20.2
7.18
18.9
6.62
17.6
6.02
16.9
5.79
16.4
5.59
15.5
5.23
-3
-3.7
20.2
6.76
18.9
6.24
17.6
5.68
16.9
5.47
16.4
5.29
15.5
4.94
0
-0.7
20.2
6.15
18.9
5.71
17.6
5.19
16.9
5.00
16.4
4.84
15.5
4.53
3
2.2
20.2
5.62
18.9
5.20
17.6
4.76
16.9
4.59
16.4
4.44
15.5
4.16
5
4.1
20.2
5.31
18.9
4.91
17.6
4.51
16.9
4.34
16.4
4.21
15.5
3.94
7
6
20.2
5.01
18.9
4.65
17.6
4.26
16.9
4.11
16.4
3.99
15.5
3.74
9
7.9
20.2
4.74
18.9
4.39
17.6
4.04
16.9
3.89
16.4
3.78
15.5
3.55
11
9.8
20.2
4.48
18.9
4.16
17.6
3.83
16.9
3.70
16.4
3.59
15.5
3.37
13
11.8
20.2
4.24
18.9
3.94
17.6
3.63
16.9
3.51
16.4
3.40
15.5
3.20
15
13.7
20.2
4.01
18.9
3.73
17.6
3.44
16.9
3.33
16.4
3.23
15.5
3.05
18
16.8
20.2
3.81
18.9
3.55
17.6
3.28
16.9
3.17
16.4
3.08
15.5
2.91
20
18.5
20.2
3.63
18.9
3.38
17.6
3.13
16.9
3.03
16.4
2.95
15.5
2.80
24
20.5
20.2
3.47
18.9
3.23
17.6
3.00
16.9
2.90
16.4
2.84
15.5
2.69
60%
-19.8
-20
17.4
8.45
16.3
8.10
15.1
7.35
14.6
7.07
14.2
6.86
13.3
6.33
-18.8
-19
17.4
8.39
16.3
8.00
15.1
7.21
14.6
6.93
14.2
6.71
13.3
6.19
-16.7
-17
17.4
8.18
16.3
7.68
15.1
6.89
14.6
6.63
14.2
6.42
13.3
5.93
-13.7
-15
17.5
7.92
16.4
7.31
15.2
6.57
14.6
6.32
14.2
6.11
13.3
5.64
-11.8
-13
17.5
7.49
16.4
6.92
15.2
6.23
14.6
6.00
14.2
5.80
13.3
5.37
-9.8
-11
17.5
7.09
16.4
6.55
15.2
5.91
14.7
5.69
14.2
5.50
13.3
5.09
-9.5
-10
17.5
6.89
16.4
6.38
15.2
5.75
14.7
5.54
14.2
5.35
13.3
4.95
-8.5
-9.1
17.5
6.71
16.4
6.21
15.2
5.61
14.7
5.40
14.2
5.21
13.3
4.83
-7
-7.6
17.5
6.41
16.4
5.94
15.2
5.36
14.6
5.17
14.2
5.00
13.3
4.64
-5
-5.6
17.4
6.00
16.3
5.56
15.1
5.04
14.6
4.85
14.2
4.72
13.3
4.39
-3
-3.7
17.4
5.66
16.3
5.25
15.1
4.78
14.6
4.60
14.2
4.47
13.3
4.15
0
-0.7
17.4
5.17
16.3
4.81
15.1
4.37
14.6
4.22
14.2
4.11
13.3
3.82
3
2.2
17.4
4.74
16.3
4.42
15.1
4.03
14.6
3.88
14.2
3.79
13.3
3.52
5
4.1
17.4
4.49
16.3
4.18
15.1
3.81
14.6
3.68
14.2
3.59
13.3
3.35
7
6
17.4
4.25
16.3
3.96
15.1
3.62
14.6
3.49
14.2
3.41
13.3
3.18
9
7.9
17.4
4.02
16.3
3.75
15.1
3.43
14.6
3.32
14.2
3.24
13.3
3.03
11
9.8
17.4
3.82
16.3
3.57
15.1
3.27
14.6
3.16
14.2
3.08
13.3
2.89
13
11.8
17.4
3.61
16.3
3.38
15.1
3.10
14.6
3.00
14.2
2.93
13.3
2.74
15
13.7
17.4
3.44
16.3
3.21
15.1
2.96
14.6
2.86
14.2
2.80
13.3
2.62
18
16.8
17.4
3.29
16.3
3.05
15.1
2.82
14.6
2.73
14.2
2.68
13.3
2.51
20
18.5
17.3
3.14
16.3
2.92
15.1
2.70
14.6
2.63
14.2
2.58
13.3
2.41
24
20.5
17.3
3.02
16.3
2.80
15.1
2.61
14.6
2.54
14.2
2.49
13.3
2.33