Multi VRF Indoor
Unit Service Manual
75
3) When the “Control Mode” is set to “L”, the “Memory Mode” and “Master/Slave Indoor Unit” is forbidden
to be set unless the “Control Mode” is then set to “I”.
4) The DIP switch shall be set exactly in position but not stay in the middle. Setting to “ON” represents “0”
of the binary system and “1” to the opposite side.
5) After the setting, please note the address code of the unit(√).
4.2.2 Address Code
The address DIP switch must be set properly for the multi VRF indoor units, otherwise it would lead to
communication trouble. The address code consists of 4 binary bits and is related to the address ranging from
1-16.
NOTES!
To use multiple indoor units in parallel, make sure to change the setting of address code before installation
and guarantee that the address code of each indoor unit must be different (The address code is located on the
mainboard of indoor unit). If wired controller is used, make sure to set the address of wired controller to the
position same as the address code on corresponding indoor unit. (The address of wired controller is located on
the back of wired controller)
Below is factory default setting:
The default address code is 0000, that is, the address is 1, shown as the igure above.
Address Code
The address code of the address DIP switch is in binary format. When the switch is set to “ON”, it indicates
“1” of the binary system, and “0” when set to the oppoiste side.
Address Code Table (4-position DIP Switch)
Switch 4
Switch 3
Switch 2
Switch 1
Address
0
0
0
0
1
0
0
0
1
2
0
0
1
0
3
0
0
1
1
4
0
1
0
0
5
0
1
0
1
6
0
1
1
0
7
0
1
1
1
8
1
0
0
0
9
1
0
0
1
10
1
0
1
0
11
1
0
1
1
12
1
1
0
0
13
1
1
0
1
14
1
1
1
0
15
1
1
1
1
16
Example 1: If the address code is “1110”, that is, switch 4 is set to “ON”, and switch 3,2 and 1 are all set to
the opposite side, in this case, the address is “8”.
Example: If the address code is “0101”, that is, the switch 3 and 1 are set to “ON” while switch 4 and 2 are
set to the opposite side, in this case, the address is “11”.
Summary of Contents for GMV-R series
Page 1: ...T1 R410A 50Hz GC201110 I...
Page 4: ...Multi VRF Indoor Unit Service Manual 1 PRODUCT PRODUCT...
Page 40: ...Multi VRF Indoor Unit Service Manual 37 CONTROL CONTROL...
Page 42: ...Multi VRF Indoor Unit Service Manual 39 CONTROL 1 1 Cooling Operation...
Page 43: ...40 Multi VRF Indoor Unit Service Manual CONTROL 1 2 Heating Operation...
Page 44: ...Multi VRF Indoor Unit Service Manual 41 CONTROL 1 3 Fan Operation 1 4 Dry Operation...
Page 54: ...Multi VRF Indoor Unit Service Manual 51 INSTALLATION...
Page 80: ...Multi VRF Indoor Unit Service Manual 77 MAINTENANCE...
Page 134: ...Multi VRF Indoor Unit Service Manual 131 Exploded View of GMV R56P NaB K GMV R71P NaB K...
Page 141: ...138 Multi VRF Indoor Unit Service Manual Exploded View of GMV R56PS NaB K GMV R71PS NaB K...
Page 145: ...142 Multi VRF Indoor Unit Service Manual Exploded View of GMV R224P NaB M...
Page 147: ...144 Multi VRF Indoor Unit Service Manual Exploded View of GMV R280P NaB M...
Page 155: ...152 Multi VRF Indoor Unit Service Manual Exploded View of GMV L R36G NaB K GMV L R45G NaB K...
Page 157: ...154 Multi VRF Indoor Unit Service Manual Exploded View of GMV L R50G NaB K GMV L R56G NaB K...
Page 159: ...156 Multi VRF Indoor Unit Service Manual Exploded View of GMV L R22G NaC K GMV L R28G NaC K...
Page 161: ...158 Multi VRF Indoor Unit Service Manual Exploded View of GMV L R36G NaC K GMV L R45G NaC K...
Page 163: ...160 Multi VRF Indoor Unit Service Manual Exploded View ofGMV L R71G Na K GMV L R80G Na K...
Page 165: ...162 Multi VRF Indoor Unit Service Manual Exploded View of GMV L R22G NaG K GMV L R28G NaG K...
Page 173: ...170 Multi VRF Indoor Unit Service Manual 2 Exploded View of GMV R71Zd NaB K GMV R90Zd NaB K...
Page 175: ...172 Multi VRF Indoor Unit Service Manual 3 Exploded View of GMV R112Zd NaB K GMV R125Zd NaB K...
Page 188: ...JF00301272...