Heat Recovery DC Inverter Multi VRF Unit
53
status
status
status
05_Detect
internal
communicati
on
db
On
05
On
C2
On
System
detects
“driven
communication error between
master
unit
and
inverter
compressor”.
db
On
05
On
C3
On
System
detects
“driven
communication error between
master unit and inverter fan”.
db
On
05
On
CH
On
IDU/ODU “high proportion of
rated capacity”.
db
On
05
On
CL
On
IDU/ODU “low proportion of
rated capacity”.
Elimination methods of above errors can be found in Troubleshooting.
Step 10: progress 06 is “Detect outdoor components”
If no error is detected, system will display as below and then start next progress.
Debugging code
Progress code
Status code
Meaning
Progress
LED1
LED2
LED3
Code Display status Code
Display
status
Code Display status
06_Detect
outdoor
components
db
On
06
On
OC
On
No error is detected in
outdoor components. Start
next progress.
If error is detected, system will stay at current progress. Error has to be solved manually. Below
is relevant error:
Debugging code
Progress code
Status code
Meaning
Progress
LED1
LED2
LED3
Code
Display
status
Code
Display
status
Code
Display
status
06_Detect
outdoor
electrical
components
db
On
06
On
Error code
On
System detects error in
outdoor electrical
components.
Elimination methods of above error can be found in Troubleshooting.
Step11: progress 07 is “Detect indoor
electrical
components”
If no error is detected, system will display as below and then start next progress.
Debugging code
Progress code
Status code
Meaning
Progress
LED1
LED2
LED3
Code
Display
status
Code
Display
status
Code
Display
status
07_Detect
indoor electrical
components
db
On
07
On
OC
On
No error is detected in
indoor electrical
components. Start next
progress.
If error is detected, system will stay at current progress. Error has to be solved manually. Below
is relevant error:
Debugging code
Progress code
Status code
Meaning
Progress
LED1
LED2
LED3
Code
Display
status
Code
Display
status
Code
Display
status
07_Detect indoor
electrical
components
db
On
07
On
XXXX/Error
code
On
System detects error in
indoor components.