Heat Recovery DC Inverter Multi VRF Unit
27
Figure 29
Please refer to the following table for circuit breaker and air switch of modular outdoo r units.
GMV-Q***WM/B-X series
Model
Combination
0Power
spec.
Air switch
capacity in
total (A)
Air switch
capacity for
combined units
(A)
Min. sectional area
of ground wire
(mm²)
Recommended
conducting wire
(sectional area
mm²×pc)
GMV-Q224WM/B
-X
GMV-Q224WM/B-X
380
~
415V
3N
~
50/60Hz
20
20
2.5
2.5×5
GMV-Q280WM/B
-X
GMV-Q280WM/B-X
380
~
415V
3N
~
50/60Hz
25
25
4.0
4.0×5
GMV-Q335WM/B
-X
GMV-Q335WM/B-X
380
~
415V
3N
~
50/60Hz
32
32
4.0
4.0×5
GMV-Q400WM/B
-X
GMV-Q400WM/B-X
380
~
415V
3N
~
50/60Hz
40
40
6.0
6.0×5
GMV-Q450WM/B
-X
GMV-Q450WM/B-X
380
~
415V
3N
~
50/60Hz
40
40
6.0
6.0×5
GMV-Q504WM/B
-X
GMV-Q224WM/B-X
+
GMV-Q280WM/B-X
380
~
415V
3N
~
50/60Hz
40
20 + 25
2.5 + 4.0
2.5×5 + 4.0×5
GMV-Q560WM/B
-X
GMV-Q280WM/B-X
+
GMV-Q280WM/B-X
380
~
415V
3N
~
50/60Hz
50
25 + 25
4.0 + 4.0
4.0×5 + 4.0×5
GMV-Q615WM/B
-X
GMV-Q280WM/B-X
+
GMV-Q335WM/B-X
380
~
415V
3N
~
50/60Hz
50
25 + 32
4.0 + 4.0
4.0×5 + 4.0×5
GMV-Q680WM/B
-X
GMV-Q280WM/B-X
+
GMV-Q400WM/B-X
380
~
415V
3N
~
50/60Hz
63
25 + 40
4.0 + 6.0
4.0×5 + 6.0×5
GMV-Q730WM/B
-X
GMV-Q280WM/B-X
+
GMV-Q450WM/B-X
380
~
415V
3N
~
50/60Hz
63
25 + 40
4.0 + 6.0
4.0×5 + 6.0×5
GMV-Q785WM/B
-X
GMV-Q400WM/B-X
+
GMV-Q400WM/B-X
380
~
415V
3N
~
50/60Hz
80
40 + 40
6.0 + 6.0
6.0×5 + 6.0×5