Heat Recovery DC Inverter Multi VRF Unit
40
Fig 41 Connection of communication for multi-module system and multi-module converter system
Note:
①
For modular outdoor units, if there are multiple outdoor modules, the master unit must be the
first outdoor module on the communication wire and cannot be connected to i ndoor units. (The
master unit is set by SA8 on the main board of outdoor unit.)
②
For modular outdoor units, if there are multiple outdoor modules, indoor units must be
connected to the last outdoor slave module.
③
Communication wire and power cord must be laid separately to avoid interference.
④
Communication wire shall be long enough
. It’s not recommended to connect wire by peeling
away its outer layer.
⑤
Heat pump mode exchanger must be connected in series and the last mode exchanger must
be connected with a matching resistance (provided among the accessory parts of outdoor unit).
Connect the matching resistance to the D1, D2 terminals of wiring board XT2 of mode exchanger.
⑥
Adopt the one-to-one connection method for the connection between heat pump mode
converter and downstream iindoor unit. Each brach is corresponding to one communication terminal.
“1D1,1D2” indicates the terminal position of comunication wire for the downstream indoor unit of the
first branch; “2D1, 2D2” indicates the terminal position of comunication wire for the downstream
indoor unit of the second branch and by this analogy.
Please note that there’s corresponding mark at