85
Performance Parameters of the Unit
Multple Model
GMV-Pdhm850W2/Na-M GMV-Pdhm900W2/Na-M GMV-Pdhm960W3/Na-M
Uses combination of
GMV-Pdhm400W/Na-M
;
GMV-Pdhm450W/Na-M
GMV-Pdhm450W/Na-M
;
GMV-Pdhm450W/Na-M
GMV-Pdhm280W/Na-M
;
GMV-Pdhm280W/Na-M
;
GMV-Pdhm400W/Na-M
Power Supply
3phase,380
~
415V,50HZ,4wires system
kW
85.0 90.0 96.0
Cooling
Btu/h
290,020.0 307,080.0 327,552.0
kW
95.0 100.0 108.0
Capacity
Heating
Btu/h
324,140.0 341,200.0 368,496.0
Cooling kW
26.8
28.6
27.5
Power
Input
Heating kW
25.1
27.8
26.6
Cooling W/W
3.17
3.15
3.49
COP
Heating W/W
3.78
3.60
4.06
Capacity Control
%
5
~
100 5
~
100 5
~
100
Type
-
Hermetically sealed scroll type
Compressor
NO.
-
6 6 7
Air Flow Rate
m
3
/min
232+232 190+190+232
Dimensions
(
H×W×D
)
mm
(1670×1340×770)+
(1670×1340×770)
(1670×1340×770)+
(1670×1340×770)
(1670×930×770)+
(1670×930×770)+
(1670×1340×770)
Net Weight
kg
402+402 402+402
260+260+402
Sound Pressure Level
dB(A)
63
63
64
Type
-
R410A
Refrigerant
Charge kg
16.0+16.0 16.0+16.0
12.0+12.0+16.0
Refrigerant Oil
-
Refer to the nameplate of the compressor
Liquid mm
Φ
19.1
Φ
19.1
Φ
19.1
Suction
Gas
mm
Φ
34.9
Φ
34.9
Φ
34.9
Discharge
Gas
mm
Φ
28.6
Φ
28.6
Φ
28.6
Piping
Connections
Oil
Balance
mm
Φ
12.7
Φ
12.7
Φ
12.7
Number of Max.
Connectable Indoor Unit
-
50 53 56
Ratio of the Connectable
Indoor Unit
-
50%
~
135
%
Recommended Power
Cord
mm
2
×NO.
35.0
×
5 35.0
×
5 50.0
×
5