10
Selection of Installation Location and Precautions
Model
Power supply
(V,Ph,Hz)
Capability
of circuit
breaker
(A)
Min.
sectional
area of earth
lead (mm
2
)
Min.
sectional
area of
power cord
(mm
2
)
The number
of the
cord(N)
GMV-Pdhm224W/Na-M 380~415,3
,50 32
6.0
6.0
5
GMV-Pdhm280W/Na-M 380~415,3
,50 32
6.0
6.0
5
GMV-Pdhm335W/Na-M 380~415,3
,50 40
10.0
10.0
5
GMV-Pdhm400W/Na-M 380~415,3
,50
40 10.0 10.0 5
GMV-Pdhm450W/Na-M
380~415,3 ,50
40
10.0
10.0
5
GMV-Pdhm504W2/Na-M 380~415,3 ,50
63
25.0
25.0
5
GMV-Pdhm560W2/Na-M 380~415,3 ,50
63
25.0
25.0
5
GMV-Pdhm615W2/Na-M 380~415,3
,50
80 35.0 35.0 5
GMV-Pdhm680W2/Na-M 380~415,3 ,50
80
35.0
35.0
5
GMV-Pdhm730W2/Na-M 380~415,3 ,50
80
35.0
35.0
5
GMV-Pdhm800W2/Na-M 380~415,3 ,50
80
35.0
35.0
5
GMV-Pdhm850W2/Na-M 380~415,3
,50
80 35.0 35.0 5
GMV-Pdhm900W2/Na-M 380~415,3 ,50
80
35.0
35.0
5
GMV-Pdhm960W3/Na-M 380~415,3 ,50
100
50.0
50.0
5
GMV-Pdhm1010W3/Na-M 380~415,3 ,50
100
50.0
50.0
5
GMV-Pdhm1065W3/Na-M 380~415,3 ,50
125
70.0
70.0
5
GMV-Pdhm1130W3/Na-M 380~415,3 ,50
125
70.0
70.0
5
GMV-Pdhm1180W3/Na-M 380~415,3
,50
125 70.0 70.0
5
GMV-Pdhm1250W3/Na-M 380~415,3 ,50
125
70.0
70.0
5
GMV-Pdhm1300W3/Na-M 380~415,3 ,50
125
70.0
70.0
5
GMV-Pdhm1350W3/Na-M 380~415,3 ,50
125
70.0
70.0
5
GMV-Pdhm1410W4/Na-M 380~415,3
,50
160 95.0 95.0
5
GMV-Pdhm1460W4/Na-M 380~415,3 ,50
160
95.0
95.0
5
GMV-Pdhm1515W4/Na-M 380~415,3 ,50
160
95.0
95.0
5
GMV-Pdhm1580W4/Na-M 380~415,3 ,50
160
95.0
95.0
5
GMV-Pdhm1630W4/Na-M
380~415,3 ,50
160
95.0
95.0
5
GMV-Pdhm1700W4/Na-M
380~415,3 ,50
160
95.0
95.0
5
GMV-Pdhm1750W4/Na-M
380~415,3 ,50
160
95.0
95.0
5
GMV-Pdhm1800W4/Na-M 380~415,3 ,50
160
95.0
95.0
5
Note
:
The specification of power cord mentioned hereby is defined as the required specification when wiring
with BV single core cable (2 ~ 4 pieces) under the cover of PVC pipe, and environment temperature shall be
at 40
℃
; Air switch shall be selected according to 40
℃
temperature condition, and shall in “D” type. if the
installation
conditions on site change
, please consider the modification on the required specification of
Power cord and Air switch, according to the specification manual provided by manufacture.
●
Grounding Requirement
As air
☆
-conditioning unit is of Class 1 electrical appliance, reliable grounding measures must be taken for