77
Troubleshooting
Trouble and State Display of Mainboard LED of Outdoor Unit
。
Definition:
z
LED6
:
Power lamp (red), bright when energized.
z
LED5
:
Operation lamp (green), bright if no error, which indicates that the unit is started; “Dark”
indicates the unit is stopped.
z
LED4
、
LED3
、
LED2
、
LED1
:
Error / state indicator (yellow)
1. Trouble of elements
Display of LED
Trouble name
LED6 LED5 LED4 LED3 LED2 LED1
Display of
wired remote
controller
High-pressure sensor error
○
○
Fc
Low-pressure sensor error
○
○
○
Fd
Outdoor environment temperature
sensor error
○
●
●
●
F4
System 1 coil-inlet sensor error
○
●
●
F5
System 1 coil-inlet sensor error
○
●
●
F6
System 1 coil-inlet sensor error
○
●
F7
System 2 coil inlet temp. sensor fault
○
●
○
●
F5
System 2 coil-middle sensor error
○
●
○
F6
System 2 coil-exit sensor error
○
●
●
○
F7
Inverter/Digital exhaust temperature
sensor error
○
●
F9
Fixed-frequency compressor 1
exhaust temperature sensor error
○
●
●
F8
Fixed-frequency compressor 2
exhaust temperature sensor error
○
●
○
F8
Fixed-frequency compressor
3exhaust temperature sensor error
○
●
○
○
F8
Inverter/Digital oil temperature / top
sensor error
○
Fb
Fixed-frequency compressor 1 oil
temperature / top sensor error
○
●
FA
Fixed-frequency compressor 2 oil
temperature / top sensor error
○
●
○
FA
Fixed-frequency compressor 3 oil
temperature / top sensor error
○
○
●
FA
Legend: bright
○
; dark
●
;blink
2.System trouble
Display of LED
Trouble name
LED6 LED5 LED4 LED3 LED2 LED1
Display of
wired remote
controller
High-pressure protection
○
●
●
●
E1
Low-pressure protection
○
●
●
●
E3
Exhaust protection
○
●
●
E4
Overcurrent Protection
○
●
●
●
E5
Oil temperature 85 protection
℃
○
○
E4
No-refrigerant protection
○
○
●
E3
Legend: bright
○
; dark
●
;blink
Summary of Contents for GMV-Pdhm1800W4/Na-M
Page 65: ...63 56 4 way valve A 57 power input of mainboard...
Page 93: ......
Page 94: ......
Page 95: ......