Multi Variable Air Conditioners Fresh Air Series Indoor Unit
2
(25) Volatile liquid, such as diluent or gas will damage the unit appearance. Only use soft cloth with a little neutral
detergent to clean the outer casing of unit.
(26) If anything abnormal happens (such as burning smell), please power off the unit and cut off the main power
supply, and then immediately contact Gree appointed service center. If abnormality keeps going, the unit
might be damaged and lead to electric shock or fire.
GREE will not assume responsibility of personal injury or equipment damage caused
by improper installation and commission, unnecessary service and incapable of following
the rules and instructions listed in this manual.
2 Product Introduction
2.1 Unit Introduction
VRF fresh air series indoor unit is a kind of air processing unit that inhales the fresh air
from outdoor side and then processes it to provide for the user in the room. According to
the different selected air volume, there are two kinds of connection method for the VRF
fresh air series indoor unit:
(1) If the selected air volume
≤1471 CFM, connect with normal indoor units by blow
method, or connect with the fixed outdoor unit as shown in
(
2
)
.
Model of Indoor Unit
Model of Outdoor Unit
GMV-NDX42P/A-T(U)
Connecting condition with GMV-**WM/B-F(U) series modular outdoor unit:
The total capacity of connected fresh air series indoor units and conventional
VRF indoor units must be within 50%~100% of the capacity of outdoor unit,
among which, the total capacity of connected fresh air indoor units cannot
exceed 30% of the capacity of outdoor unit.
GMV-NDX48P/A-T(U)
GMV-NDX54P/A-T(U)
GMV-NDX72P/A-T(U)
GMV-NDX96P/A-T(U)
NOTICE!
When fresh air series indoor units and conventional VRF indoor units will be
connected, please follow the capacity requirement strictly. The total capacity of connected
fresh air indoor units cannot exceed 30% of the capacity of outdoor unit, while the total
capacity of indoor units shall be within 50%~100% of the capacity of outdoor unit.
Otherwise, the comfortableness will be affected or even the unit will be damaged.