4.4 Installation of Air Duct
NOTICE!
①
. There should be insulating layer on air-out duct, air-return duct and fresh air
duct to avoid heat loss and moisture. Adhere a nail on the air duct and then add
thermal sponge with a layer of tin. Fasten it with a nail cover and then seal the
junction with tin tapes, you can also use other materials that have good
insulation quality.
②
. Each air-out duct and air-return duct should be fixed on a pre-made board with
iron frame. The junction of air duct should be well-sealed in order to prevent air
leakage.
③
. The design and construction of air duct should comply with national
requirements.
④
. The edge of air-return duct is suggested to be more than 150mm (5-7/8in.) away
from the wall. Add afilter to the air-return opening.
⑤
. Please consider noise-damping and vibration damping for the design and
construction of air duct. Besides, noise source must be away from people. For
instance, do not have the air-return opening installed on top of the user (offices,
rest area, etc.).
4.4.1 Installation of Air-out Duct
(1) Installation of the Rectangular Duct
Fig 4.4.1
No.
Name
No.
Name
1
Hanger Rod
5
Static Pressure Box
2
Fresh Air Duct
6
Main Supply Air Duct
3
Canvas Duct
7
Supply Air Outlet
4
Fresh Air Inlet
Summary of Contents for GMV-NDX42P/A-T