background image

Multi Variable Air Conditioners Fresh Air Series Indoor Unit 

18 

5.1 Connection of Wire and Patch Board Terminal 

(1)   The connection of wire (as shown in fig 5.1.1) 

1) Strip about 25mm (1in.) insulation of the wire end by stripping and cutting tool. 

2) Remove the wiring screws on the terminal board. 

3) Shape the tail of wire into ring by needle nose plier, and keep the gauge of ring in 

accordance with screw. 

4) Use the screwdriver for tightening the terminal. 

(2)   The connection of stranded wire (as shown in fig 5.1.2) 

1) Strip  about 10mm (3/8in.)  insulation  of the end  of stranded  wire by stripping  and 

cutting tool. 

2) Loosen the wiring screws on terminal board. 

3) Insert the wire into the ring tongue terminal and tighten by crimping tool. 

4) Use the screwdriver for tightening the terminal. 

 

 

Fig 5.1.1                                                          Fig 5.1.2 

5.2 Power Cord Connection 

 

1

Every unit should be equipped with a circuit breaker for short-circuit and overload protection.

 

2

During  operation,  all  indoor  units  connected  to  the  same  outdoor  unit  system  must  be  kept  energized 

status. 

Otherwise, the unit can’t operate normally. 

 

 

Fig 5.2.1 

 

Summary of Contents for GMV-NDX42P/A-T

Page 1: ...Manual Original Instructions Commercial Air Conditioners Multi Variable Air Conditioners Fresh Air Series Indoor Unit Models GMV NDX42P A T U GMV NDX48P A T U GMV NDX54P A T U GMV NDX72P A T U GMV NDX96P A T U ...

Page 2: ...he following items and contact our authorized service centers as soon as possible Nameplate model cooling capacity product code ex factory date Malfunction status detail description of conditions before and after malfunction occurs 6 All units have been strictly tested and proved to be qualified before ex factory To avoid unit damage or even operation failure which may be caused by improper disass...

Page 3: ...Installation and Test of Drain Pipe 12 4 4 Installation of Air Duct 15 4 5 Installation of Wired Controller 17 5 Wiring Work 17 5 1 Connection of Wire and Patch Board Terminal 18 5 2 Power Cord Connection 18 5 3 Connection of Communication Line of IDU and ODU 19 5 4 Connect Communication Wire of Wired Controller 19 5 5 Illuminate for Connection of Wired Controller and Indoor Units Network 20 6 Rou...

Page 4: ...the unit or cut off the power supply before cleaning the unit otherwise electric shock or injury may happen 15 Never spray or flush water towards unit otherwise malfunction or electric shock may happen 16 Do not expose the unit to the moist or corrosive circumstances 17 Under cooling mode please don t set the room temperature too low and keep the temperature difference between indoor and outdoor u...

Page 5: ... different selected air volume there are two kinds of connection method for the VRF fresh air series indoor unit 1 If the selected air volume 1471 CFM connect with normal indoor units by blow method or connect with the fixed outdoor unit as shown in 2 Model of Indoor Unit Model of Outdoor Unit GMV NDX42P A T U Connecting condition with GMV WM B F U series modular outdoor unit The total capacity of...

Page 6: ...X96P A T U 2 2 Rated Working Condition Indoor Side Condition Outdoor Side Condition Dry Bulb Temp Wet Bulb Temp Dry Bulb Temp Wet Bulb Temp Rated Cooling 35 C 95 F 28 C 82 F 35 C 95 F 28 C 82 F Rated Heating 7 C 45 F 6 C 43 F 7 C 45 F 6 C 43 F 2 3 Working Temperature Range Outdoor Ambient Dry Bulb Working Temperature Range 7 C 45 C 19 F 113 F NOTICE The ex factory set temperature is 18 C 64 F in c...

Page 7: ...he refrigerant pipe 4 M10 Nut Nut with Washer M10X8 4 PC To be used together with the hanger bolt for installing the unit 5 M10 Nut M10X8 4 8 PC To be used together with the hanger bolt for installing the unit 6 M10 Washer Spring Washer M10X2 6 4 PC To be used together with the hanger bolt for installing the unit 7 M10 Washer M10XΦ30X 2 5 4 PC To be used together with the hanger bolt for installin...

Page 8: ...ain water out easily 4 There is no obstacle at inlet or outlet Please ensure good air circulation 5 In order to make sure the space for maintenance please install the indoor unit according to the dimension described below 6 Keep the unit away from heat source inflammable gas or smoke 7 This is a concealed ceiling type unit 8 This series indoor unit can be allowed to supply air for only one room 9 ...

Page 9: ...ent children touching the unit 3 3 Requirements for Communication Line NOTICE If the unit is installed in the place with strong electromagnetic interference shielded wire must be applied on the communication wire between indoor unit and wired controller Twisted pair line with shielding function must be applied on the communication wire between indoor unit and indoor unit outdoor unit 3 3 1 Select ...

Page 10: ...08 230V 1Ph 60Hz 1 7 15 GMV NDX72P A T U 208 230V 1Ph 60Hz 6 3 15 GMV NDX96P A T U 208 230V 1Ph 60Hz 6 3 15 1 Specification of circuit breaker and power cord is selected on the basis of unit s maximum power max current 2 Specification of power cord is based on the working condition where ambient temperature is 40ºC 104 and multi core cable with copper conductor working temperature is 90 ºC 194 e g...

Page 11: ... selection requirements Power cord size is based on BV single core wire 2 4pc at 40 104 F Cambient temperature when laying across plastic pipe Air switch is D type and used at 40 C 104 F If actual installation condition varies please lower the capacity appropriately according to the specifications of power cord and air switch provided by manufacturer Install cut off device near the unit The minimu...

Page 12: ...62 7 32 300 11 13 16 754 29 11 16 1400 55 1 8 700 27 9 16 Fig 4 1 2 Below are dimensions of A B C etc for different models Unit mm in Item Model A B C D E F G H I GMV NDX54P A T U 1353 53 1 4 632 24 7 8 992 39 1150 45 1 4 192 7 1 2 327 12 7 8 1483 58 3 8 791 31 1 8 385 15 3 16 GMV NDX72P A T U 1353 53 1 4 632 24 7 8 992 39 1150 45 1 4 192 7 1 2 327 12 7 8 1483 58 3 8 791 31 1 8 385 15 3 16 GMV NDX...

Page 13: ...rding to the 4 spots on the paper pattern The punching diameter may refer to the diameter of expansion bolt about 60mm 2 3 8in to 70mm 2 3 4in depth as shown in Fig 4 1 4 Fig 4 1 3 Fig 4 1 4 2 Insert the expansion bolt M10 into the hole and then drive the iron nail into the bolt as shown in Fig 4 1 5 NOTICE The length of bolt can be based on the height of room Bolt should be prepared by the user F...

Page 14: ...nt After the indoor unit is installed remember to check the horizontal status of the whole unit It should be horizontal from front to back and slant 1 from left to right following the drainage direction as shown in Fig 4 1 7 Fig 4 1 7 4 2 Pipe Connection 1 Direct the flaring of copper pipe to the center of screwed connection and then screw the flaring nut tight as shown in Fig 4 2 2 Use a torque w...

Page 15: ...hen connecting the pipe insert the end of PVC pipe into the drain hole and then tighten it up with a drain hose and cable tie Do not use adhesives to connect drain hole and drain hose When the drain pipe is used for several equipments the shared pipe should be about 100mm lower than the drain hole of each equipment In this case use thicker pipe Fig 4 3 1 4 3 2 Drainage pipe installation 1 Insert t...

Page 16: ...rain pipe use water sealed joint Fig 4 3 5 6 Install the trap as shown in following Fig 4 3 6 Fig 4 3 6 7 Install one trap for each unit 8 Convenience for cleaning trap in the future should be considered when installing it 9 The horizontal pipe can be connected to vertical pipe in the same level please select the connection way as shown in following fig NO1 Connection of drainage pipe joints Fig 4...

Page 17: ...m 39 3 8 59in Fig 4 3 10 4 3 3 Test of Drainage System 1 Please test drainage system after electric work is finished Inject approximately 1L purified water to drain pan from air vent ensure that not to splash the water over the electrical components e g water pump etc 2 During the test please carefully check the drainage joint make sure no any leakage occur 3 It s strongly recommend to do the drai...

Page 18: ...air duct should be well sealed in order to prevent air leakage The design and construction of air duct should comply with national requirements The edge of air return duct is suggested to be more than 150mm 5 7 8in away from the wall Add afilter to the air return opening Please consider noise damping and vibration damping for the design and construction of air duct Besides noise source must be awa...

Page 19: ...r Duct Fig 4 4 2 No Name No Name 1 Fresh Air Duct 6 Transition Pipe 2 Canvas Duct 7 Supply Air Duct 3 Fresh Air Blinds 8 Diffuser 4 Hanger Rod 9 Diffuser Connector 5 Supply Air Outlet 4 4 2 Shape and Size of Air outlet and Air return Opening Fig 4 4 3 Air Outlet Fig 4 4 4 Air Return Opening ...

Page 20: ...ould be replaced by exclusive cable 5 All the electrical work should be performed by professional personnel as per local law regulation and this manual 6 Connect the unit to the special earthing device and make sure the unit is earthed soundly 7 Air switch and circuit breaker is required to be set Air switch should have both magnetic trip and thermal trip functions so as to protect the unit when s...

Page 21: ...he terminal 2 The connection of stranded wire as shown in fig 5 1 2 1 Strip about 10mm 3 8in insulation of the end of stranded wire by stripping and cutting tool 2 Loosen the wiring screws on terminal board 3 Insert the wire into the ring tongue terminal and tighten by crimping tool 4 Use the screwdriver for tightening the terminal Fig 5 1 1 Fig 5 1 2 5 2 Power Cord Connection 1 Every unit should ...

Page 22: ...s 3 Connect the communication wire to terminal D1 and D2 of indoor 4 bit wiring board as shownin fig5 3 1 4 Fix the communication cable with clamp of electric box 5 For more reliable communication make sure connect the terminal resistor to the most downstream IDU of the communication bus terminal D1 and D2 as shown in fig 5 3 2 terminal resistor is provided with each ODU Fig 5 3 1 Fig 5 3 2 5 4 Co...

Page 23: ... 4 1 Fig 5 4 2 2 Fig 5 4 2 shows the installation of remote controller 3 Wired controller and receiving light board can be installed at the same time When operating through a remote controller both wired controller and the receiving light board can receive the signals as shown in Fig 5 4 3 Fig 5 4 3 5 5 Illuminate for Connection of Wired Controller and Indoor Units Network 1 Communication wire of ...

Page 24: ...door unit cannot share the same wired controller with other types of VRF indoor unit When two wired controllers are controlling the indoor units you need to set an address for each wired controller Address No 1 refers to master wired controller while address No 2 refers to sub master wired controller They should not share the same address For specific setting methods please refer to installation m...

Page 25: ...IDU Use a vacuum cleaner to remove dust If the filters are dirty wash them with warm water and mild detergent and dry the filters in the shade 2 If the unit used in the environment with much dust please clean it regularly usually once every two weeks 6 2 Maintenance before the Seasonal Use 1 Check if the air inlet and air outlet of indoor and outdoor unit are blocked 2 Check if securely grounded 3...

Page 26: ...er Full Protection d1 Indoor Unit PCB Error dC Capacity DIP Switch Setting Error L4 Wired Controller Power Supply Error d3 Ambient Temperature Sensor Error dL Outlet Air Temperature Sensor Error L5 Freeze protection d4 Inlet Pipe Temperature Sensor Error dE Indoor Unit CO2 Sensor Error L7 No Master Indoor Unit Error d6 Outlet Pipe Temperature Sensor Error dy Water Temperature Sensor Error L8 Power...

Page 27: ... or blocked Too heavy heat load of room e g too many people Door or windows is open Air inlet and outlet of IDU are blocked Set temperature is too high or refrigerant leaks The performance of room temperature sensor gets worse Poor heating effect The filter is dirty or blocked Door or window is open Set temperature is too low Refrigerant leaks Outdoor ambient temperature is lower than 5 23 Error o...

Page 28: ......

Reviews: