Multi Variable Air Conditioners Ducted Type Indoor Unit
9
corrupt the unit.
(2) It is not allowed to connect the condensate drain pipe into rain pipe to prevent rain water from
pouring in and cause property loss or personal injury.
(3) Condensate drain pipe should be connected into special drain system for air conditioner.
(4) The drainage pipe should be short and the gradient downwards should be at least 1%~2% in
order to drain condensation water smoothly.
(5) The diameter of drainage hose should be bigger or equal to the diameter of drainage pipe joint.
(6) Install drainage pipe according to the following Fig. and arrange insulation to the drainage pipe.
Improper installation may lead to water leakage and damp the furniture and other things in the
room.
(7) You can buy normal hard PVC pipe used as the drainage pipe. During connection, insert the
end of PVC pipe into the drainage hole and then tighten it with drainage hole and wire binder.
Can‘t connect the drainage hole and drainage hole with glue.
(8) When the drainage pipelines are used for several units, the position of pipeline should be about
100mm(4inch) lower than the drainage port of each unit. In this case, thicker pipes should be
applied.
Fig.4.3.1
4.3.2 Drainage pipe installation
(1) Insert the drain hose into the drain hole and tighten it with tapes, as shown in Fig.4.3.2.
Model with water pump will be provided with drain hose, while other models please prepare the
drain hose by yourself.
(2) Tighten the pipe clamp, with the distance between screw nut and hose smaller than 4mm
(3/16inch).
Fig.4.3.2