Multi Variable Air Conditioners Duct Type Indoor Unit

 

 

14 

(8) The horizontal pipe can be connected to vertical pipe in the same level; please select the 

connection way as shown in following fig. 

NO1: Connection of drainage pipe joints (Fig4.3.6) 

NO2: Connection of downspout elbow (Fig4.3.7) 

NO3: Inserting pipe connection (Fig4.3.8) 

 

Fig 4.3.6                                                  Fig 4.3.7                                Fig 4.3.8 

(9) The installation height of raising pipe for drainage should be lower than 850mm. The 

gradient from raising pipe towards drainage direction should be at least 1%~2%. If the 

raising pipe is vertical with the unit, the raising height should be less than 800mm. 

 

Fig 4.3.9 

(10) Drain pipes should have a downward slope of at least 1%~2%, in order to prevent 

pipes from sagging, install hanger bracket at intervals of 1000~1500mm. 

 

Fig 4.3.10 

4.3.3 Test of Drainage System 

(1)   After the electrical installation is finished, perform test for the drainage system. 

(2)   During the test, check whether water flows correctly through the pipeline and observe 

carefully that there’s no water leakage at the junction. 

(3)   If this unit is installed for a new house, we suggest you perform the test before fitting the 

ceiling. 

Summary of Contents for GMV-ND22PLS/A-T

Page 1: ...Air Conditioners please read this owner s manual carefully before operation and retain it for future reference If you have lost the Owner s Manual please contact the local agent or visit www gree com...

Page 2: ...ensuring reliability of complete unit maintaining normal communication and preheating refrigerant When the unit won t be used for a long time cut off the power of the complete unit However please pre...

Page 3: ...n and Drainage System Testing 12 4 4 Installation of Air Duct 15 4 5 Installation of Wired Controller 18 5 Wiring Work 19 5 1 Connection of Wire and Patch Board Terminal 19 5 2 Power Cord Cnnection 20...

Page 4: ...eck the power supply carefully This air conditioner must be properly grounded through the receptacle to avoid electric shock The grounding wire shouldn t be connected with gas pipe water pipe lightnin...

Page 5: ...lack of oxygen Never start or stop the air conditioner by inserting or removing the power cord Do not turn off the air conditioner until it runs for at least 5 minutes Otherwise oil return of the com...

Page 6: ...off the unit at once and disconnect power supply Then contact GREE service center If the air conditioner continues to operate despite of abnormal condition the unit may be damaged and it may cause ele...

Page 7: ...ating 20 15 7 6 Indoor Unit Working Temperature Range 16 C 32 C 2 3 Unit Functions Unit Functions Wired Controller XK46 Standard Wired Controller XK49 Optional Remote Controller YAP1F Standard Remote...

Page 8: ...trol the indoor unit 2 M4X25 Screw Cross recessed small pan head screw 3 To fix the wired controller 3 Drain Hose Assembly 1 To connect with the hard PVC drain pipe 4 Special Nut 1 To be used for conn...

Page 9: ...rwise these electrical appliances may have image interference and noise Even if the distance is 1m when there is strong electric wave noise may still occur Fig 3 2 Notes Installation of the unit must...

Page 10: ...is installed in places with intense magnetic field or strong interference it is necessary to use shielded wire 3 3 2 Select communication line for indoor unit and outdoor unit Fig 3 3 2 Wire Type Tota...

Page 11: ...T 6 1 0 1 0 Notes Use copper wire only as unit s power cord Operating temperature should be within its rated value If the power cord is more than 15m long please increase properly the sectional area o...

Page 12: ...tric box and below unit s lower level 1 Below are the outline dimension applicable to indoor units of GMV ND22PLS A T GMV ND63PLS A T Fig 4 4 1 Below are dimensions of A B C etc for different models U...

Page 13: ...260 222 1016 220 1050 695 GMV ND80PLS A T GMV ND90PLS A T 1379 565 1340 655 260 207 1153 220 1188 716 GMV ND100PLS A T GMV ND112PLS A T GMV ND125PLS A T GMV ND140PLS A T 1 Drill bolt holes and install...

Page 14: ...nger bracket The washer fixing plate will prevent the washer from falling 3 The usage of paper pattern Refer to paper pattern of installation for ceiling opening dimension The center of ceiling openin...

Page 15: ...rainage pipe should be short and the gradient downwards should be at least 1 2 in order to drain condensation water smoothly 2 The diameter of drainage hose should be bigger or equal to the diameter o...

Page 16: ...lamp with the distance between screw nut and hose smaller than 4mm metal clamp accessory drain hose accessory Fig 4 3 2 Fig 4 3 3 3 Use sealing plate to make the pipe clamp and hose insulated as shown...

Page 17: ...ds drainage direction should be at least 1 2 If the raising pipe is vertical with the unit the raising height should be less than 800mm Fig 4 3 9 10 Drain pipes should have a downward slope of at leas...

Page 18: ...n order to prevent air leakage The design and construction of air duct should comply with national requirements The edge of air return duct is suggested to be more than 150mm away from the wall Add a...

Page 19: ...utlet and Air return Opening 1 Range of Capacity 2 2 6 3kW Fig 4 4 3 Air Outlet Fig 4 4 4 Air return Opening Model Size of Air Outlet Size of Air return Opening A B C D GMV ND22PLS A T 121 528 580 161...

Page 20: ...return air is desired just change the place of the rectangular flange and the return air cover plate 3 Connect one end of the return air duct to the return air outlet of the unit by rivets and the ot...

Page 21: ...f the fresh air duct is not be used 2 Install the round flange so that the fresh air duct can be connected as Fig 4 4 10 3 Sealing and heat preservation should be done for both the air pipe and round...

Page 22: ...e communication wires should be separated from power cord and connection wire between indoor unit and outdoor unit Adjust the static pressure via wired controller according to site circumstance 5 1 Co...

Page 23: ...wiring clamp 5 3 Connection of Communication Wire between Indoor Unit and Outdoor Unit or indoor unit 1 Detach the electric box lid 2 Let the Communication cable pass through the wiring through holes...

Page 24: ...remote controller 3 Wired controller and receiving light board can be installed at the same time When operating through a remote controller both wired controller and the receiving light board can rec...

Page 25: ...e 2 If the unit used in the environment with much dust please clean it regularly usually once every two weeks 6 2 Maintenance before the Seasonal Use 1 Check if the air inlet and air outlet of indoor...

Page 26: ...ty Input voltage is too low Defect of main PC board The unit stops after running for a while The inlet or outlet of ODU or IDU are blocked by obstacle Poor cooling effect The filter is dirty Too heavy...

Page 27: ...Multi Variable Air Conditioners Duct Type Indoor Unit 24...