GMV DC Air Handler

 

  A place where easy connection with the outdoor unit is available. 

  A place where is 1m or more away from other electric appliances such as television, audio 

device, etc. 

  Avoid a location where there is heat source, high humidity or inflammable gas. 

  Do not place the unit near a laundry, a bath, a shower or a swimming pool. 

  Be sure that the installation conforms to the installation dimension diagram. 

  The space around the unit is adequate for ventilation. 

4.2.3 Location 

 

This air handler is designed for indoor installation only. Do not install it outdoors.   

When installing the air handler, take consideration to minimize the length of refrigerant tubing as 

much as possible. Do not install the air handler in a location either above or below the condenser that 
violates the instructions provided with the condenser. Service clearance is to take precedence. Allow 
a minimum of 24” in front of the unit for service clearance. When installing in an area directly over a 
finished ceiling (such as an attic), an emergency drain pan is required directly under the unit. See 
local and state codes for requirements. When installing this unit in an area that may become wet, 
elevate the unit with a sturdy, non-porous material. In installations that may lead to physical damage 
(i.e. a garage) it is advised to install a protective barrier to prevent such damage. 

This air handler is designed for a complete supply and return ductwork system. These duct type 

indoor units are used to supply conditioned air to one room. Do not operate this product without all 
ductwork attached. 

Based upon the actual conditions, if air handler is installed as Fig.4.2.1(A), the air handler should 

be concealed in a specific room or space and make sure the air handler is not accessible to the 
general public. 

Based upon the actual conditions, if air handler is installed as Fig.4.2.1(B), make sure that there 

is enough space for care and maintenance and the height between the air handler and ground is 
above 2500mm. And the air handler is not accessible to the general public. 

 

   (A)                     (B) 

Fig.4.2.1 

 
 

Summary of Contents for GMV-ND09A/B-T

Page 1: ...nstructions Commercial Air Conditioners GMV DC Air Handler Models GMV ND09A B T U GMV ND12A B T U GMV ND18A B T U GMV ND24A B T U GMV ND30A B T U GMV ND36A B T U GMV ND42A B T U GMV ND48A B T U GMV ND...

Page 2: ...rvice center for professional support Users should not disassemble or maintain the unit by themselves otherwise it may cause relative damage and our company will bear no responsibilities 6 All the ill...

Page 3: ...turer 3 After verification the defect of product is directly caused by corrosive gas 4 After verification defects are due to improper operation during transportation of product 5 Operate repair mainta...

Page 4: ...red Controller 10 4 6 Ductwork 10 4 7 Electric Heater 11 5 Wiring Work 13 5 1 Connection of Wire and Patch Board Terminal 13 5 2 Power Cord Connection 14 5 3 Connection of Communication Wire between I...

Page 5: ...kage refrigerant leakage electric shock or fire etc 14 Do not insert fingers or objects into air outlet or air return grille 15 Open the door and window frequently to keep good ventilation for avoidin...

Page 6: ...tion Outdoor Side Condition Dry Bulb Temp Wet Bulb Temp Dry Bulb Temp Wet Bulb Temp Rated Cooling 26 7 80 0 19 4 67 0 35 95 0 23 9 75 0 Rated Heating 21 1 70 0 15 6 60 0 8 3 47 0 6 1 43 0 3 Preparatio...

Page 7: ...responsibilities for equipment installed in violation of any codes or regulations 3 1 4 Replacement Parts When reporting shortages or damages or ordering repair parts give the complete product No and...

Page 8: ...ctric fault occurs The electric grounding circuit may consist of an appropriate sized power cord which connected with the grounding piece located in the unit control box and also connecting to the bui...

Page 9: ...r unit and wired controller Twisted pair line with shielding function must be applied on the communication wire between indoor unit and indoor unit outdoor unit 3 3 1 Select communication line for ind...

Page 10: ...15 GMV ND24A B T U 4 0 15 GMV ND30A B T U 4 0 15 GMV ND36A B T U 5 0 15 GMV ND42A B T U 5 0 15 GMV ND48A B T U 8 7 15 GMV ND54A B T U 8 7 15 GMV ND60A B T U 8 7 15 1 Use copper wire only as unit s po...

Page 11: ...7 295 11 5 8 508 20 GMV ND60A B T U 630 24 3 4 540 21 1 4 1448 57 295 11 5 8 508 20 4 2 Location 4 2 1 Unit Inspection Upon delivery inspect the unit for damage Any damage must be reported immediately...

Page 12: ...nce When installing in an area directly over a finished ceiling such as an attic an emergency drain pan is required directly under the unit See local and state codes for requirements When installing t...

Page 13: ...8 GMV ND60A B T U 3 4 3 8 4 3 2 Piping Preparation 4 3 2 1 Solder Connection All cut ends are to be round burr free and cleaned Failure to follow this practice increases the chances for refrigerant l...

Page 14: ...ng HVAC codes The installation must include a P style trap that is located closely to the evaporator coil Do not over tighten the drain connection in order to prevent possible damage to the evaporator...

Page 15: ...r than those recommended E HEAT mode setting method under off status press ON OFF and Menu button for 5s to turn on or turn off E heat mode After that the wired remote control pop up box shows Setting...

Page 16: ...r kit 2 Check any physical damage do not install damaged heater kit 3 Remove the upper access panel from air handler 4 Remove cover plate from air handler 5 Slide the heater kit in to the slot and sec...

Page 17: ...lations and electrical standards 6 Keep cable away from refrigerant piping compressor and fan motor 7 The communication wires should be separated from power cord and connection wire between indoor uni...

Page 18: ...to the ring tongue terminal and tighten by crimping tool 4 Use the screwdriver for tightening the terminal Unit mm inch Fig 5 1 1 Fig 5 1 2 5 2 Power Cord Connection All indoor units must be unified o...

Page 19: ...box 5 For more reliable communication make sure connect the terminal resistor to the most downstream IDU of the communication bus terminal D1 and D2 as shown in Fig 5 3 2 terminal resistor is provide...

Page 20: ...ted to D1 D2 2 Wired controller is connected to H1 H2 3 One indoor unit can connect two wired controllers that must be set as master one and slave one 4 One wired controller can control 16 indoor unit...

Page 21: ...efaulted static pressure notch for all models at ex factory is 5 7 Routine Maintenance 1 Do turn off the unit and cut off the main power supply when cleaning the air conditioner to avoid electric shoc...

Page 22: ...compatibility Error dH Wired Controller PCB Error L3 Water Full Protection d1 Indoor Unit PCB Error dC Capacity DIP Switch Setting Error L4 Wired Controller Power Supply Error d3 Ambient Temperature S...

Page 23: ...heavy heat load of room e g too many people Door or windows is open Inlet and outlet of IDU are blocked Setting temperature is too high Refrigerant is insufficient e g refrigerant leakage Poor heatin...

Page 24: ......

Reviews: