1 Safety Precautions   

 

(1)  This product can’t be installed at corrosive, inflammable or explosive environment or the place 

with special requirements, such as kitchen. Otherwise, it will affect the normal operation or 
shorten the service life of the unit, or even cause fire hazard or serious injury. As for above 
special places, please adopt special air conditioner with anti-corrosive or anti-explosion 
function. 

(2)  Follow this instruction to complete the installation work. Please carefully read this manual 

before unit startup and service. 

(3)  Wire size of power cord should be large enough. The damaged power cord and connection 

wire should be replaced by exclusive cable.   

(4)  After connecting the power cord, please fix the electric box cover properly in order to avoid 

accident.   

(5)  Never fail to comply with the nitrogen charge requirements. Charge nitrogen when welding 

pipes.   

(6)  Never conditioners short-circuit or cancel the pressure switch to prevent unit damage.   
(7)  Please firstly connect the wired controller before energization, otherwise wired controller 

cannot be used.   

(8)  Before using the unit, please check if the piping and wiring are correct to avoid water leakage, 

refrigerant leakage, electric shock, or fire etc. 

(9)  Do not insert fingers or objects into air outlet/inlet grille.   
(10) Open the door and window and keep good ventilation in the room to avoid oxygen deficit when 

the gas/oil supplied heating equipment is used.   

(11) Never start up or shut off the air conditioner by means of directly plug or unplug the power 

cord.   

(12) Turn off the unit after it runs at least five minutes; otherwise it will influence oil return of the 

compressor.   

(13) Do not allow children operate this unit.   
(14) Do not operate this unit with wet hands.   
(15) Turn off the unit or cut off the power supply before cleaning the unit, otherwise electric shock or 

injury may happen.   

(16) Never spray or flush water towards unit, otherwise malfunction or electric shock may happen.   
(17) Do not expose the unit to the moist or corrosive circumstances.   
(18) Under cooling mode, please don't set the room temperature too low and keep the temperature 

difference between indoor and outdoor unit within 5°C(41°F).   

(19) User is not allowed to repair the unit. Fault service may cause electric shock or fire accidents. 

Please contact Gree appointed service center for help.   

(20) Before installation, please check if the power supply is in accordance with the requirements 

specified on the nameplate. And also take care of the power safety.   

(21) Installation should be conducted by dealer or qualified personnel. Please do not attempt to 

install the unit by yourself. Improper handling may result in water leakage, electric shock or fire 
disaster etc..   

(22) The control box should be installed inside. 
(23) Be sure to use the exclusive accessory and part to prevent the water leakage, electric shock 

and fire accidents.   

(24) Make sure the unit can be earthed properly and soundly after plugging into the socket so as to 

avoid electric shock. Please do not connect the ground wire to gas pipe, water pipe, lightning 
rod or telephone line.   

(25) Electrify the unit 8 hours before operation. Please switch on for 8 hours before operation. Do 

not cut off the power when 24 hours short-time halting (to protect the compressor).   

(26) If refrigerant leakage happens during installation, please ventilate immediately. Poisonous gas 

will emerge if the refrigerant gas meets fire.   

(27) Volatile liquid, such as diluent or gas will damage the unit appearance. Only use soft cloth with 

a little neutral detergent to clean the outer casing of unit.   

(28) If anything abnormal happens (such as burning smell), please power off the unit and cut off the 

main power supply, and then immediately contact Gree appointed service center. If 
abnormality keeps going, the unit might be damaged and lead to electric shock or fire.   

Summary of Contents for GMV-ND07T/B-T

Page 1: ...anual Original Instructions Commercial Air Conditioners Multi Variable Air Conditioners Compact Cassette Type Indoor Unit Models GMV ND07T B T U GMV ND09T B T U GMV ND12T B T U GMV ND15T B T U GMV ND1...

Page 2: ...l keep this manual 6 If this unit fails to operate normally please contact our service center as soon as possible and provide the following information 1 Content on the nameplate model number cooling...

Page 3: ...turer 3 After verification the defect of product is directly caused by corrosive gas 4 After verification defects are due to improper operation during transportation of product 5 Operate repair mainta...

Page 4: ...Drainage System Testing 9 4 4 Panel Installation 12 4 5 Installation of Wired Controller 14 5 Wiring Work 14 5 1 Connection of Wire and Patch Board Terminal 15 5 2 Power Cord Connection 15 5 3 Connec...

Page 5: ...ply before cleaning the unit otherwise electric shock or injury may happen 16 Never spray or flush water towards unit otherwise malfunction or electric shock may happen 17 Do not expose the unit to th...

Page 6: ...Side Condition Outdoor Side Condition Dry Bulb Temp C F Wet Bulb Temp C F Dry Bulb Temp C F Wet Bulb Temp C F Rated Cooling 26 7 80 19 4 67 35 95 24 75 Rated Heating 21 1 70 15 6 60 8 3 47 7 1 45 3 Pr...

Page 7: ...should be able to withstand the weight of unit 2 The water can be drained conveniently from drainage pipe 3 There should be no obstruction near air inlet and air outlet 4 Follow the installation dista...

Page 8: ...nication cable must be adopted 3 3 1 Select Communication Line for Indoor Unit and Wired Controller Fig 3 3 1 Material type Total length of communication line between indoor unit and wired controller...

Page 9: ...s necessary to use shielded wire 3 4 Wiring Requirement Power Cord Size and Air Switch Capacity Model Power Supply MCA A MOP A GMV ND07T B T U 208 230V 1ph 60Hz 2 15 GMV ND09T B T U 2 15 GMV ND12T B T...

Page 10: ...T U GMV ND12T B T U GMV ND15T B T U GMV ND18T B T U 670 26 3 8 570 22 7 16 570 22 7 16 495 19 1 2 600 23 5 8 4 1 2 Suspend the Indoor Unit 1 Drill bolt holes and install bolts 1 Stick the reference c...

Page 11: ...nd lower sides of the hanger bracket The washer fixing plate will prevent the washer from falling 3 The usage of paper pattern Refer to paper pattern of installation for ceiling opening dimension The...

Page 12: ...flaring port of copper pipe at the center of screwed joint and then tighten the flaring nut with hand as shown in fig 4 2 1 2 Use a torque wrench to tighten up the flaring nut until the wrench gives o...

Page 13: ...qual to the diameter of drainage pipe joint 6 Install drainage pipe according to the following Fig 4 3 1 and arrange insulation to the drainage pipe Improper installation may lead to water leakage and...

Page 14: ...he unit Unit mm inch Fig 4 3 2 Drainage pipes assembled by T shaped joints 8 The horizontal pipe can t be connected to vertical pipe in the same level please select the connection way as shown in foll...

Page 15: ...g the installation distance from soft drain pipe to the gasket is C when the bolt is tightened It is not allowed to apply PVC or other related glue in the joints of two ends of drain pipe Fig 4 3 8 Un...

Page 16: ...fter 60s of energizing In this case the water pump operates automatically Check if the water pump drains normally through drainage port The water pump will stop automatically after running for 10mins...

Page 17: ...he panel direction so as to keep the mark and fittings on the same corner as shown in Fig 4 4 4 Fig 4 4 4 2 Temporality hang the panel to body there are four hangers on each corner of the panel hang t...

Page 18: ...or it may cause electric shock 2 Please carefully read the wiring diagram before carry out the wiring work incorrect wiring could cause malfunction or even damage the unit 3 The unit should be powere...

Page 19: ...ch insulation of the end of stranded wire by stripping and cutting tool 2 Loosen the wiring screws on terminal board 3 Insert the wire into the ring tongue terminal and tighten by crimping tool 4 Use...

Page 20: ...g board as shown in Fig 5 3 1 Fig 5 3 1 Fig 5 3 2 4 Fix the communication cable with clamp of electric box 5 For more reliable communication make sure connect the terminal resistor to the most downstr...

Page 21: ...munication wire of indoor unit and outdoor unit or indoor unit is connected to D1 D2 2 Wired controller is connected to H1 H2 3 One indoor unit can connect two wired controllers that must be set as ma...

Page 22: ...Multi Variable Air Conditioners Compact Cassette Type Indoor Unit 18 Fig 5 5 1...

Page 23: ...air outlet of indoor and outdoor unit are blocked 2 Check if securely grounded 3 Check if all the power cord and communication cable are securely connected 4 Check if any error code displayed after en...

Page 24: ...too low Operation button is off Error of control loop The unit stops after running for a while There is obstacle in front of condenser Error of control loop Perform cooling when outdoor ambient temper...

Page 25: ...21...