Cassette Type Air Conditioner Unit
9
they should be modified according to the related national standard.
⑥
. Take 2 pieces of power cord of 0.75mm² as the communication lines between
indoor and outdoor unit, with their longest lengths of 50 m. Please select the
appropriate line length as per the actual installation conditions. The
communication lines can not be twisted together. For the unit (
≤
30k
), it’s
recommended to use 8m long communication line.
⑦
. Take 2 pieces of power cord of 0.75 mm² as the communication lines between the
wired controller and the indoor unit, with their longest lengths of 30m. Please
select the appropriate line length as per the actual installation conditions. The
communication lines can not be twisted together. It’s recommended to use 8m
long communication line.
⑧
. The wire size of the communication line should be no less than 0.75mm²
. It’s
recommended to take 0.75 mm² power cords as the communication line.
4 Installation of the Unit
4.1 Installation of the Indoor Unit
4.1.1 Indoor unit dimension
For the units: 18k
A
B
C
D
E
F
G
H
I
J
Bottom face of ceiling
Fig. 4.1