Gree FXA2A-D Owner'S Manual Download Page 20

BU Module 

16 

 

Fig. 22 

 

If the thermal insulation of the refrigerant pipe is not removed, please do not bend the pipe. 
Otherwise, it maybe leads the pipe to crack. It is better to make an incision with a knife in the 
thermal insulation and removes it. After elbow operation is finished, recover the thermal 
insulation with binding band. 

3)

 

The process of install refrigerant pipes 

 

Remove the screw caps from the pipes. 

 

Align the flared end of copper tube with the center of pipe joint. Tighten the nuts by hands. (If 
the flared end of copper tube and the center of pipe joint are not in coaxial, it is hard to tighten 
the nuts by hands, please do not tighten it with spanners, because the screw thread may be 
broken by force). 

 

Tighten the flaring nuts with torque wrench until you hear a “click”. (The spanner and torque 
wrench should be perpendicular to the refrigerant pipeline). 

 

The following table for the torque required to tighten the nuts. 

Table 10 

Pipe 

diameter 

(mm/inch) 

Thickness of 

copper 

tube(mm/inch) 

Tightening 

torque 

(N·m/1bf·ft) 

Φ

6.35(1/4) 

0.8(1/32) 15

30(11~22)

Φ

9.52(3/8) 

0.8(1/32) 35

40(26~29)

Φ

12.7(1/2) 

0.8(1/32) 45

50(33~37)

Φ

15.9(5/8) 

1.0(1/25) 60

65(44~48)

Φ

19.05(3/4) 

1.0(1/25) 70

75(52~55)

 

                                                                           

 Fig. 23 

CAUTION

 

1)

 

During the connection of the indoor unit and BU module to the refrigerant pipe, never pull any joints of 
the indoor unit and the BU module by force; otherwise the capillary pipe or other pipe may crack, 
which then would result in leakage. 

2)

 

The refrigerant pipe should be supported by brackets, that is, don’t let the unit withstand the weight of 
it. 

3)

 

For the Super Free Match system, each pipe should be labeled to tell which system it belongs to avoid 
mistaken inaccurate piping. 

 
 
 

Summary of Contents for FXA2A-D

Page 1: ...sing Gree air conditioners please read this owner s manual carefully before operation and keep it for future reference GREE reserves the right to interpret this manual which will be subject to any cha...

Page 2: ...ors is conflict with the modes of outdoor units it will be indicated on the display of the wired controller in five seconds and then the indoor unit will stop In this case please harmonize their work...

Page 3: ...f FXB5A D 10 4 Installation Instruction 11 5 Installation of Refrigerant Pipes 12 5 1 Allowable Length and Drop Height of Connecting Pipe 12 5 2 Installation of Piping Adapter FXA2A D FXA3A D and FXB5...

Page 4: ......

Page 5: ...he nameplate Make sure the power supply is safe 8 This air conditioner must be properly grounded through the receptacle to avoid electric shock The ground wire shouldn t be connected with gas pipe wat...

Page 6: ...he power supply Otherwise it may cause electric shock or damage 28 Do not spray water on the air conditioner or it will cause malfunction or electric shock 29 The air conditioner is not support to ins...

Page 7: ...well Otherwise it is very compact and has a flexible choice about the installation location such as the ceiling of parlor corridor balcony storeroom and etc 2 1 Names of Main Parts a FXA2A D b FXA3A...

Page 8: ...es the running command and all indoor units stop once the outdoor unit is turned off Fig 2 2 4 Working Temperature Range Table 2 B D e r u t a r e p m e t e d i s t u O s t r o S 0 5 m u m i x a M 122...

Page 9: ...en s reach please keep the unit away from children 3 The BU module is for indoor use If installing in the outdoors the location must be away from wind and rain Otherwise it maybe causes water leakage...

Page 10: ...ine dimension Fig 3 mm Table 3 Sorts Indoor unit side mm inch Outdoor unit side mm inch Port A Port B Liquid pipe 6 35 1 4 6 35 1 4 9 52 3 8 Gas pipe 9 52 3 8 9 52 3 8 15 9 5 8 2 Installation and serv...

Page 11: ...Fig 5 mm Table 4 Sorts Indoor unit side mm inch Outdoor unit side mm inch Port A Port B Port C Liquid pipe 6 35 1 4 6 35 1 4 6 35 1 4 9 52 3 8 Gas liquid 9 52 3 8 9 52 3 8 9 52 3 8 15 9 5 8 2 Install...

Page 12: ...tline dimension Fig 7 mm Table 5 Sorts Indoor unit side mm inch Outdoor unit side mm inch Port A Port B Liquid pipe 6 5 1 4 6 5 1 4 9 7 3 8 Gas pipe 16 3 5 8 16 3 5 8 16 3 5 8 2 Installation and servi...

Page 13: ...n Fig 9 mm Table 6 Sorts Indoor unit side mm inch Outdoor unit side mm inch Port A Port B Port C Liquid pipe 6 5 1 4 6 5 1 4 6 5 1 4 9 7 3 8 Gas liquid 16 3 5 8 16 3 5 8 16 3 5 8 16 3 5 8 2 Installati...

Page 14: ...f FXB5A D 1 Outline dimension Fig 11 mm Table 7 Sorts Indoor unit side mm inch Outdoor unit side mm inch Liquid pipe 6 35 1 4 9 52 3 8 Gas pipe 9 52 3 8 15 9 5 8 2 Installation and service space NO Na...

Page 15: ...he condensed water can be discharged 2 Reference to the size of hanger metal and drill 4 holes in the installation location 3 Hang the hanger bolts Fig 13 4 Fix the modules securely with the hanger bo...

Page 16: ...2 L5 2A L2 L3 3B 40 131 Maximum allowable length Between outdoor and indoor units H1 30 99 Between outdoor units and BU modules H2 30 99 Between BU and BU modules H3 15 49 Between indoor and indoor un...

Page 17: ...en the nuts with hands Then tighten the flaring nuts with torque wrench until you hear a click Fig 17 3 Sealing the unconnected port If the port of BU module indoor side does not connected to one indo...

Page 18: ...BU module wrap the pipes to be brazed with sufficient wet cloths After brazing use wet cloths to cool off the pipes to be brazed sufficient Fig 19 3 Sealing the unconnected port If the port of BU modu...

Page 19: ...with the process requirements Rosin joint or pin hole is not allowed 3 During the installation do not damage the pipeline The pipeline s radius of bending must be over than 200mm 8inch The pipes cann...

Page 20: ...uts with torque wrench until you hear a click The spanner and torque wrench should be perpendicular to the refrigerant pipeline The following table for the torque required to tighten the nuts Table 10...

Page 21: ...Pieces Sectional area 3 0 75 mm2 Transmission line Pieces Sectional area 2 1 5 mm2 Recommended cable of indoor unit Pieces Sectional area 4 0 75mm2 Capacity of the air switch GWHD 48S ND3CO 40A GWHD...

Page 22: ...cause the hazard of electric shock 4 The reliable ground terminal should be provided and the ground wire cannot be connected to any of the following places a Water pipe b Coal gas pipe c Sewage pipe...

Page 23: ...k of the air conditioner 3 Press the ends of the cable tightly onto the round terminals corresponding to the size of the screws 4 Pass the screw through the round terminals and fix it onto the termina...

Page 24: ...ber ring In order to protect the power cable and transmission line from damaging by the hole the rubber ring cannot fall from that otherwise it may cause electrical shock or fire etc 4 Connect the pow...

Page 25: ...ting indoor units make sure to connect refrigerant pipes and power cables to the same connection ports marked with matching signs A B C D and E 5 If the connecting wire is connected to the terminal in...

Page 26: ...ht be water bends 2 The drainage pipeline is form of the hard PVC pipes for common purposes which can be purchased locally The diameter of the PVC pipes is not less than 31mm 1 1 4inch and the pipelin...

Page 27: ...onnected Flash 4 times Indoor unit E is connected Flash 5 times Indoor unit A gas tube temperature sensor error Flash 1 time b7 b7 indoor unit address Indoor unit A liquid tube temperature sensor erro...

Page 28: ...GREE ELECTRIC APPLIANCES INC OF ZHUHAI Add West Jinji Rd Qianshan Zhuhai Guangdong China 519070 Tel 86 756 8522218 Fax 86 756 8669426 E mail gree gree com cn www gree com 66174100032...

Reviews: