Ducted Type Split Air-Conditioner Units(Inverter Series)
9
For instance, do not have the return-air opening installed on top of the
user (offices, rest area, etc.).
2.4.1Installation of Air-out Duct
Installation of the rectangular duct.
Fig.10
2.5 Indoor unit static pressure notch adjustment
These can set different static pressure notch by the wired controller.
Please refer to the owner’s manual or wired controller for the setting in details.
Different static pressure notch is for different static pressure. The corresponding
relationship is as below:
Static pressure notch
Static pressure(pa)
01
0
02
30
03
60
04
90
05(Defaulted)
120
06
150
07
180
08
210
09
250