background image

5

R EPLACING EXISTING DEFROST TIMERS

The DTMV40 will replace all models of Paragon 8040,

8140,  8240  Series  or  Precision  6040,  6140,  6240

Series.

TERMINAL IDENTIFICATION:

The standard DTMV40 terminal identification is identical
to the Paragon 8145 with the addition of the “F” terminal.
Terminal  identification  labels  are  provided  for  the  other
models  to  be  placed  over  the  printed  numbers  on  the
printed circuit board. From the table on page 4, select the
proper label, apply to printed circuit board, and wire per
the original wiring or the wiring diagrams indicated.

MODE SELECTION (Light Blue DIP Switch):

First determine what model is being replaced (Grasslin or
Competitors). The mode selector DIP switch (located at
lower right side of the board) determines the configura-
tion  of  terminals  2&4.  In  position  “

A

”,  the  terminals  are

normally closed (only when the timer is energized), and
will open during a defrost. In position “

B

”, terminals 2&4

are normally open, and will close during a defrost. Select
proper  position  from  table  below  and  wiring  diagrams
indicated. To select mode simply slide the switch as fol-
lows:

Mode
Mode

 

A

–  position  switch  to  left;   

B

–  position switch to right;

Note:

When Mode “

B

” is selected the

DTMV40 will operate as follows:

Refrigeration  Mode

–  RED  &

GREEN  LED’s  will  turn  OFF  (1&3
and 2&4 break while 1&F make)

Defrost  Mode

–  RED  &  GREEN

LED’s  will  turn  ON  (1&3  and  2&4
make while 1&F break)

8045 REPLACEMENT:

The DTMV40 with 8045 terminal ID label applied differs
from the 8045 in that terminals 

1

and 

N

are combined.

This  means  that  the  DTMV40  model  must  be  the  same
voltage  as  the  defrost  circuit  (defrost  heater,  contactor
coil, or hot gas valve). If used in an application where the
defrost circuit is 120V and the refrigeration circuit is 240V,

the  DTMV40  must  be  configured  for  120V  application
(RED DIP Switch Down) with 120V power connected to 

1-

N

and 

X.

Note 1 – (8143 Replacement):

When replacing a

Paragon 8143 or Precision 6143, wire the termina-
tion thermostat to terminal 

N

of the DTMV40 and

the  adjacent  blank  terminal.  The  Paragon  and
Precision  timers  are  wired  to  terminal 

N

and  the

blank  terminal.  If  the  termination  thermostat  is
wired to terminal 

N

of the DTMV40 (with the 8143

label  attached),  temperature  termination  will  not
occur  and  may  result  in  burnout  of  the  DTMV40.
See wiring diagrams 8 & 9.

8240/6240 SERIES REPLACEMENT:

The DTMV40 may

be used to replace the Paragon 8240 or Precision 6240
series  defrost  timers  with  integral  pressure  termination
by the addition of a remote pressure switch wired to ter-
minals 

Xp

and 

p

of the DTMV40 (with an 8240 series ter-

minal label applied). There must be no external voltage
connected  to  the  pressure  switch.  Set  pressure  switch
cut-in  to  the  same  value  as  set  on  the  Paragon  or
Precision defrost timer being replaced. Set cut-out 6 to
14psi below cut-in. See wiring diagrams 10, 11, and 12.
Recommended Pressure Switches: Johnson/Penn P170,
Ranco  010  series,  or  Danfoss  KP1  series.  Pressure
range approximately 35-110psi, CUT-IN ON PRESSURE
RISE.

NOTE 2 – (8243 Replacement)

: When replacing a

Paragon  8243  or  Precision  6243,  the  DTMV40
white  tabs  (trippers)  for  setting  defrost  time  and
defrost  duration  must  be  reversed.  Pull  ALL  tabs
outward for refrigeration. Press the tabs inward at
the desired defrost initiation times, and for desired
duration.

Please  Note:

The  DTMV40  replaces  all  prior  Grasslin

defrost timer models such as DT040, DT140, DTMV, and
DTSX.

SPECIFICATIONS

Maximum Contact Switch Rating:

40A Resistive @ 120VAC, 208~240VAC

2HP @ 208~240VAC; 1HP @ 120VAC

16FLA, 90LRA @ 120VAC

12FLA, 52LRA @ 240VAC

“F” Terminal: 30A Resistive @ 120~240VAC

1HP @ 120VAC; 2HP @ 208~240VAC

Wiring Connections: Screw box lug terminals.

 

 

Up to one #8 AWG wire

Environmental Ratings:

Operating Temperature Range: –40°F to 131°F (–40°C to 55°C)

Operating Humidity: 0 - 95% RH, non-condensing

Dimensions: 8.795” x 6.631” x 2.935” (H x W x D)

Shipping Weight: 3 lbs.

Agency Approvals: UL Listed