3-18
Settings and Measurement
(b) EU Value
Specifies output after conversion. Set two points, the Upper and
Lower parameters.
(c) Dec pt
This parameter specifies the decimal point position of the numeral
to be specified as the EU value(s).
(d) Unit
Selects the converted unit, which can be specified as a user-
defined character string consisting of alphanumerics. The Unit
parameter can also be specified by selecting the Select Unit
setting.
(e) Select
Selects the type of engineering unit.
(f) Choose
Selects the converted unit. The Unit displayed here is the type of
unit selected by the Select setting.
To specify a unit that is not displayed here, specify a user-defined
character string as the Unit setting. Moreover, the setting specified
here is displayed as the Unit setting.
Upper Value
Lower Value
+2.5000
–2.5000
+10.000
Specified Value
EU Value
–10.000
+5 V
CH.1 10V
–5 V
+20.00 rpm
CH.1 Scaling 1
–20.00 rpm
Setting Example
Misc. ................................... Span
: Set the detailed span for each channel.
Annotation
: Set a comment for each channel.
(For details , see the text input on page 3-33.)
Perform Auto Zero ADJ: Moves the current input voltage to zero
position voltage value.
Reset Auto Zero ADJ : Cancels the zero position voltage value and
displays input voltage.