Granville-Phillips Convectron 275 series Instruction Manual Download Page 23

4   Operation

23

Series 275 Convectron Gauge Bridge Amp PC Board
Instruction Manual - 275331

4.4  Preparing For Convectron

 

Gauge Operation

Install pressure limiting devices calibrated to a level that the vacuum system can safely withstand. In 
addition, install pressure relief valves or rupture disks that will release pressure at a level 
considerably below the maximum safe pressure level of the system.

Suppliers of pressure relief valves and pressure relief disks can be located via an internet search, and 
are listed in the 

Thomas Register

 under “Valves, Relief” and “Discs, Rupture.” Confirm that these 

safety devices are properly installed before operating the Series 275 Mini-Convectron Module. In 
addition, check that (1) the proper gas cylinders are installed, (2) gas cylinder valve positions are 
correct on manual systems, and (3) the automation settings are correct on automated gas delivery 
systems.

NOTE:  Vacuum gauges with compression fittings may be forcefully ejected if the vacuum system 
is pressurized.

4.5  Understanding Convectron Gauge Pressure Measurement In Gases Other Than 

Nitrogen or Air

Convectron Gauges are Pirani type thermal conductivity gauges. These gauges measure the heat loss 
from a heated sensor wire maintained at constant temperature. The bridge amplifier PC board 
converts this measurement into gas pressure voltage readings. For gases other than nitrogen or air the 
heat loss varies at any given true pressure and can result in inaccurate pressure readings.

It is important to understand that the pressure indicated by a Convectron Gauge depends on the type 
of gas, the orientation of the gauge axis, and on the gas density in the gauge. Convectron Gauges are 
normally factory calibrated for N

2

 (air has approximately the same calibration). With proper 

precautions, the Convectron Gauge may be used for pressure measurement of certain other gases. 

NOTE:  The information in this section applies only when the Convectron Gauge is calibrated 
for N

2

 and the Convectron Gauge is mounted with its axis horizontal. 

At pressures below a few Torr, there is no danger in measuring pressure of gases other than N

2

 and 

air, merely inaccurate readings. A danger arises if the N

2

 calibration is used without correction to 

measure higher pressure levels of some other gases. For example, N

2

 at 24 Torr causes the same heat 

loss from the Convectron sensor as argon will at atmospheric pressure. If the pressure indication of 
the Convectron Gauge is not properly corrected for argon, an operator attempting to fill a vacuum 
system with 1/2 atmosphere of argon would observe a pressure reading of only 12 Torr when the 
actual pressure had risen to the desired 380 Torr. Continuing to fill the system with argon to 760 Torr 
would result in a 24 Torr pressure reading. 

Depending on the pressure of the argon gas source, the chamber could be dangerously pressurized 
while the display continued to read about 30 Torr of N

2

 equivalent pressure.

NOTE:  This type of danger is not unique to the Convectron Gauge and likely exists with other 
thermal conductivity gauges using convection to extend the range to high pressures.

To measure the pressure of gases other than air, or N

2

 with a Convectron Gauge calibrated for N

2

you must use the conversion curves listed specifically for Convectron Gauges to translate between 
indicated pressure and true pressure. Do not use other data. 

Never

 use the conversion curves 

Using the N

2

 calibration to pressurize a vacuum system above about 1 Torr with 

certain other gases can cause dangerously high pressures which may cause 
explosion of the system. See Section 4.5 before using with other gases.

Summary of Contents for Convectron 275 series

Page 1: ...Series 275 Instruction Manual Granville Phillips Convectron Vacuum Gauge Bridge Amp PC Board with Analog Output Signal Instruction manual part number 275331 Revision D November 2016...

Page 2: ...All other trademarks and registered trademarks are the properties of their respective owners Customer Service Technical Support MKS Pressure and Vacuum Measurement Solutions MKS Instruments Inc Granvi...

Page 3: ...ier PC Board 17 3 2 1 Install the Interconnect Cable 18 Chapter 4 Operation 21 4 1 Theory of Operation 21 4 1 1 General Precautions 22 4 2 Preparing for Pressure Measurement 22 4 3 Gas Type 22 4 4 Pre...

Page 4: ...4 Series 275 Convectron Gauge Bridge Amp PC Board Instruction Manual 275331 Notes...

Page 5: ...ure to comply with these requirements Read Instructions Read all safety and operating instructions before operating the product Retain Instructions Retain the Safety and Operating Instructions for fut...

Page 6: ...fety features are maintained Do not use this product if it has unauthorized modifications Replacement Parts When replacement parts are required be certain to use the replacement parts that are specifi...

Page 7: ...ill operation where a malfunction might cause high internal pressures provide an appropriate pressure relief device Series 275 Gauges should not be used above 1000 Torr 1333 mbar 133 kPa 19 psi true p...

Page 8: ...Shipping damage on returned products as a result of inadequate packaging is the Buyer s responsibility For Customer Service Technical Support MKS Pressure and Vacuum Measurement Solutions MKS Instrum...

Page 9: ...ty from the date of shipment for new Granville Phillips Products The MKS Instruments Inc General Terms and Conditions of Sale provides the complete and exclusive warranty for MKS Granville Phillips Di...

Page 10: ...1 Safety Instructions 10 Series 275 Convectron Gauge Bridge Amp PC Board Instruction Manual 275331 Notes...

Page 11: ...2 Kovar Kapton gold plated Tungsten and borosilicate glass Table 2 1 Specifications Function Description System Measuring range for Air or N2 See the Operation Chapter of this instruction manual for c...

Page 12: ...NPT pipe thread 1 2 inch compression fitting 1 8 NPT pipe thread 1 2 inch tubulation 6 4 cm 2 52 in VCR type female fitting 1 4 inch VCR type female fitting standard 1 2 inch VCR type female fitting...

Page 13: ...2 Specifications 13 Series 275 Convectron Gauge Bridge Amp PC Board Instruction Manual 275331 2 4 Bridge Amplifier PC Board Figure 2 2 Bridge Amplifier PC Board...

Page 14: ...2 Specifications 14 Series 275 Convectron Gauge Bridge Amp PC Board Instruction Manual 275331 Notes...

Page 15: ...ipe wrench to further tighten the press ring You may point the electrical pins of the gauge tube anywhere you wish in a 360 horizontal circle for optimum routing of the gauge tube cable 1 8 NPT Mount...

Page 16: ...module to the vacuum chamber 1 Attach a metal hose clamp or other metal clamp to the gauge stem 2 Install a 3 31 mm2 12 AWG or larger copper wire between the clamp and a metal ground lug bolt or stud...

Page 17: ...ction Manual 275331 3 2 Install the Bridge Amplifier PC Board Install the bridge amplifier PC board in your existing enclosure Dimensions are given in Figure 3 3 Figure 3 2 Ground Wire Attached to the...

Page 18: ...nect Cable 1 Connect the cable between the bridge amplifier PC board and the Convectron Gauge See Figure 3 4 2 Connect 12 Vdc power to the PCB pins 13 14 and 15 See Figure 3 4 3 Connect the analog out...

Page 19: ...3 Installation 19 Series 275 Convectron Gauge Bridge Amp PC Board Instruction Manual 275331 Figure 3 5 Convectron Gauge Bridge Amplifier Schematic...

Page 20: ...3 Installation 20 Series 275 Convectron Gauge Bridge Amp PC Board Instruction Manual 275331 Notes...

Page 21: ...ungsten The heated sensing wire loses more heat as the ambient gas pressure increases The more molecules contact the sensing wire the more power is required to keep the sensing wire at a constant temp...

Page 22: ...your vacuum system is air or N2 If you are using other gases you must follow the instructions in Section 4 5 You are reasonably familiar with the general theory of operation of thermal conductivity ga...

Page 23: ...r N2 air has approximately the same calibration With proper precautions the Convectron Gauge may be used for pressure measurement of certain other gases NOTE The information in this section applies on...

Page 24: ...true pressure of 2 x 10 2 Torr for CH4 the heat loss from the sensor is the same as at a true pressure of 3 x 10 2 for N2 see Figure 4 2 The curves at higher pressure vary widely from gas to gas becau...

Page 25: ...rom the 10 Torr N2 equivalent indicated pressure to the Helium curve and then move horizontally to the left to reveal a true pressure of 4 5 Torr Thus 4 5 Torr Helium pressure produces an indication o...

Page 26: ...4 Operation 26 Series 275 Convectron Gauge Bridge Amp PC Board Instruction Manual 275331 Figure 4 2 Convectron Gauge Indicated vs True Pressure Curve 10 4 to 10 1 Torr...

Page 27: ...4 Operation 27 Series 275 Convectron Gauge Bridge Amp PC Board Instruction Manual 275331 Figure 4 3 Convectron Gauge Indicated vs True Pressure Curve 10 1 to 1000 Torr...

Page 28: ...4 Operation 28 Series 275 Convectron Gauge Bridge Amp PC Board Instruction Manual 275331 Figure 4 4 Convectron Gauge Indicated vs True Pressure Curve 10 1 to 1000 Torr...

Page 29: ...4 Operation 29 Series 275 Convectron Gauge Bridge Amp PC Board Instruction Manual 275331 Figure 4 5 Convectron Gauge Indicated vs True Pressure Curve 10 4 to 10 1 mbar...

Page 30: ...4 Operation 30 Series 275 Convectron Gauge Bridge Amp PC Board Instruction Manual 275331 Figure 4 6 Convectron Gauge Indicated vs True Pressure Curve 10 1 to 1000 mbar...

Page 31: ...gnal The analog output voltage signal provides a specific voltage at specific pressures as illustrated in Figure 4 8 Use the pin numbers 11 and 12 of the connector on the bridge amplifier PC board see...

Page 32: ...4 Operation 32 Series 275 Convectron Gauge Bridge Amp PC Board Instruction Manual 275331 Figure 4 8 Analog Output Voltage Signal...

Page 33: ...ility For Customer Service Technical Support MKS Pressure and Vacuum Measurement Solutions MKS Instruments Inc Granville Phillips Division 6450 Dry Creek Parkway Longmont Colorado 80503 USA Tel 303 65...

Page 34: ...roduct has been dropped or damaged Replacement Parts When replacement parts are required be certain to use the replacement parts that are specified by Granville Phillips or that have the same characte...

Page 35: ...repair or replace the plumbing 3 Repair the leak or replace the vacum pump 4 Repair or replace the cable Pressure reading is inaccurate 1 The bridge amp PC board is not calibrated for the process gas...

Page 36: ...and Figure 3 5 5 3 3 Convectron Gauge Test Procedure The small diameter sensor wire inside the gauge tube can be damaged by even small voltages Do not perform electrical continuity tests with instrum...

Page 37: ...the sensor 1 Hold the gauge with the main body horizontal and the port projecting upward at an angle of 45 degrees Slowly fill it with solvent using a standard wash bottle with the spout inserted in t...

Page 38: ...r with the Convectron Gauge Attached 1 Bake the process chamber at the desired temperature for the desired time The Convectron gauge tube must not exceed 150 oC 2 Allow the system to cool to ambient t...

Page 39: ...ction manual part number 275173 Revision A August 2012...

Page 40: ...Customer Service Technical Support MKS Pressure and Vacuum Measurement Solutions MKS Instruments Inc Granville Phillips Division 6450 Dry Creek Parkway Longmont Colorado 80503 USA Tel 303 652 4400 Fax...

Reviews: