Grant Vortex Eco Series User Instructions Download Page 7

Page 7

3  CARING FOR YOUR

 BOILER

3.1 

CHECKING SEALED SYSTEM 

 PRESSURE

If your boiler is operating on a sealed system, your installer will 

have pressurised the system and should have told you (or set 

it on the pressure gauge*) the system pressure when cold. This 

pressure is normally between 0.5 and 1.0 bar, which will increase 

slightly when the system is hot.
*Your installer should have shown you where the system pressure 

gauge is located.

Figure 3-1:

 Pressure gauge during normal boiler operation

You should frequently check that the system pressure is correct. 

If the pressure (when the heating system is cold) is below the set 

pressure mentioned above, you can re-pressurise the system by 

following the instructions given in Section 3.2.
If the system requires re-pressurising frequently, ask your installer 

or service engineer to check the heating system for leaks and to 

check the expansion vessel air charge.

AIR VENTS

The boiler and/or system will be fitted with an air vent to remove 

air from the system. 
Any air trapped in the radiators should be removed by venting the 

radiators using the vent screw at the top of each radiator. Only 

vent a radiator if the top is cool and the bottom is hot. Excessive 

venting will reduce the system pressure, so only vent when 

necessary and check the system pressure as mentioned above.
Re-pressurise the system if necessary.

PRESSURE RELIEF (SAFETY) VALVE

The sealed system will be fitted with a safety valve to release 

excess pressure from the system. If water or steam is emitted 

from the safety valve discharge pipe, switch off the boiler and 

contact your installer or service engineer immediately.
If a Grant Vortex Eco Wall Hung External Sealed System boiler is 

fitted, this safety valve will be located inside the boiler casing.

0

1

2

3

4

Normal Operating

Pressure** Range

**This is the 

pressure inside 

the heating 

system while the 

system is hot.

3.2 

HOW TO FILL OR TOP UP YOUR

 

SEALED SYSTEM

(filling loop)

Figure 3-2:

 Sealed system filling loop arrangement

To fill or top up your heating system, proceed as follows:

1. 

Check the boiler and circulating pump are switched off and 

any air vents on the system are open.

2. 

Connect the filling loop* between the two filling valves.

3. 

Open the filling valve on the mains water end of the filling 

loop (the valve is open when the operating lever is in line with 

the valve).

4. 

Open the filling valve on the heating end of the filling loop to 

allow water to flow into the heating system (the valve is open 

when the operating lever is in line with the valve).

5.  When the pressure gauge shows the required cold system 

pressure (refer to Section 3.1) close the filling valve on the 

heating system.

6.  Vent each radiator to remove any air that may be trapped 

in them. Start with the lowest radiator in the system, i.e 

downstairs.

7.  Locate the circulating pump(s) and vent the pump(s) by 

following the manufacturer’s instructions. 

• 

If a Grant Vortex Eco Wall Hung External Sealed 

System boiler is fitted to the boiler, refer to Appendix 

A1 or A2 (as appropriate) at the back of the boiler’s 

installation and servicing instructions for the pump 

venting procedure.

8.  Now, check the system pressure on the system pressure 

gauge. If necessary, re-open the filling valve on the system 

until the gauge shows the required pressure. Take care not 

to over-fill! 

9. 

Finally, close both filling valves and disconnect the filling loop 

at one end only. Take care, as the filling loop may contain 

water!

*If you cannot locate the filling loop, please contact your installer.

! NOTE !

If the system has been drained down or requires frequent 

topping up, then the level of inhibitor and/or anti-freeze will 

need to be checked by your installer.

! WARNING !

Only add water to the system when the system is cold and 

the boiler is switched off.

Do not overfill

Section 3: Caring for your Boiler

Summary of Contents for Vortex Eco Series

Page 1: ...UK DOC 0164 Rev 1 0 January 2020 Grant Vortex Eco Wall Hung External and Wall Hung External System Condensing Oil Boiler Range User Instructions...

Page 2: ...erning likely damage to equipment or tools as a consequence of not following the instructions in the caution NOTE Used for emphasis or information not directly concerned with the surrounding text but...

Page 3: ...If your boiler fails to light 5 2 3 Turning off your boiler 5 2 4 About your fuel 5 2 5 Boiler controls 6 2 6 Heating system controls 6 2 7 Electricity supply 6 3 CARING FOR YOUR BOILER 7 3 1 Checking...

Page 4: ...installer should arrange for this to be carried out If required Grant UK can provide details of OFTEC registered commissioning engineers in your area 1 5 ACTIVATING THE GUARANTEE In order for your boi...

Page 5: ...set to ON 2 Check that the programmer if fitted is working and is set to ON CH or HW 3 Check that all thermostats are set to the desired setting and are calling for heat 4 Check if the burner Lock Ou...

Page 6: ...ammer for further details ROOM THERMOSTAT This thermostat allows you to control the room temperature at which the boiler will fire to provide central heating to your property The room thermostat is us...

Page 7: ...s u r e R a n g e This is the pressure inside the heating system while the system is hot 3 2 HOW TO FILL OR TOP UP YOUR SEALED SYSTEM filling loop Figure 3 2 Sealed system filling loop arrangement To...

Page 8: ...exposed pipe and clearing any blockage from the end of the pipe If this fails to remedy the problem you should contact your service engineer 3 6 FROST PROTECTION All Grant Vortex Outdoor boilers come...

Page 9: ...Signature Service 4 Date Engineer Company name Telephone number OFTEC Technician number Comments Signature Service 5 Date Engineer Company name Telephone number OFTEC Technician number Comments Signa...

Page 10: ...mments Signature Service 12 Date Engineer Company name Telephone number OFTEC Technician number Comments Signature Service 13 Date Engineer Company name Telephone number OFTEC Technician number Commen...

Page 11: ...Page 11 Notes NOTES...

Page 12: ...GRANT ENGINEERING UK LIMITED Hopton House Hopton Industrial Estate Devizes Wiltshire SN10 2EU Tel 44 0 1380 736920 Fax 44 0 1380 736991 Email info grantuk com www grantuk com...

Reviews: