background image

Page 7

3.2 HOW 

TO 

FILL OR TOP UP YOUR

 SEALED 

SYSTEM

(filling loop)

Figure 3-2:

 Sealed system 

fi

 lling loop arrangement

To 

fi

 ll or top up your heating system, proceed as follows:

1.  Check the boiler and circulating pump are switched o

  and 

any air vents on the system are open.

2. Connect 

the 

fi

 lling loop* between the two 

fi

 lling valves.

3. Open 

the 

fi

 lling valve on the mains water end of the 

fi

 lling 

loop (the valve is open when the operating lever is in line with 

the valve).

4. Open 

the 

fi

 lling valve on the heating end of the 

fi

 lling loop to 

allow water to 

fl

 ow into the heating system (the valve is open 

when the operating lever is in line with the valve).

5.  When the pressure gauge shows the required cold system 

pressure (refer to Section 3.1) close the 

fi

 lling valve on the 

heating system.

6.  Vent each radiator to remove any air that may be trapped 

in them. Start with the lowest radiator in the system, i.e 

downstairs.

7.  Locate the circulating pump(s) and vent the pump(s) by 

following the manufacturer’s instructions. 

8.  Now, check the system pressure on the system pressure 

gauge. If necessary, re-open the 

fi

 lling valve on the system 

until the gauge shows the required pressure. Take care not 

to over-

fi

 ll! 

9.  Finally, close both 

fi

 lling valves and disconnect the 

fi

 lling loop 

at one end only. Take care, as the 

fi

 lling loop may contain 

water!

*If you cannot locate the 

fi

 lling loop, please contact your installer.

! NOTE !

If the system has been drained down or requires frequent 
topping up, then the level of inhibitor and/or anti-freeze will 
need to be checked by your installer.

! WARNING !

Only add water to the system when the system is cold and 
the boiler is switched o

 .

Do not over

fi

 ll

3.3 EXPANSION VESSEL

The expansion vessel should be checked annually, as part of your 

annual service, to ensure that there is a 1.0 bar air charge in the 

vessel. Failure to do this will invalidate the boiler guarantee. Refer 

to Section 1.6 for further details regarding servicing.

! NOTE !

The pressure gauge on the system does not show the air 
charge pressure in the expansion vessel.

! NOTE !

In order to properly care for your Grant boiler, an annual 
service by a competent person should always be 
undertaken.

3.4 

VENTILATION

Your Grant Euro

fl

 ame Condensing External boiler requires a fresh 

supply of air in order for the burner to 

fi

 re. The boiler draws this air 

through ventilation openings in the recessed top edge of the front 

door of the boiler casing.
These ventilation openings must not be obstructed under any 

circumstances.
You should periodically check that they are clear.
Do not attempt to ‘box in’ the boiler or build a compartment around 

it before contacting your installer.
Do not place any combustible material around or on the boiler or 

fl

 ue pipe.

3.5 

FLUE TERMINAL AND CONDENSATE

 DISPOSAL

FLUE TERMINAL

The 

fl

 ue terminal must not be damaged or obstructed in any way.

A wire mesh guard is required to cover the terminal if the terminal 

is less than 2 metres above ground level. If you think one is 

required, contact your installer.
You should periodically check for and remove any obstructions, 

e.g. cut back any bushes that may have grown over the terminal. 

Do not stack anything against or in front of the terminal.
In severe weather conditions, check that the terminal does not 

become blocked by snow or ice.

‘PLUMING’ FROM THE FLUE TERMINAL

Whilst operating, it is quite normal for the boiler to produce a white 

plume of condensation vapour from the 

fl

 ue terminal.

This is due to the high e

  ciency of the boiler and may be 

particularly evident with low outdoor temperatures.

CONDENSATE DISPOSAL

During the operation of the boiler, condensate is produced from 

the 

fl

 ue gases and this is drained to a suitable disposal point 

through the plastic waste pipe on the left hand side of the boiler.
The condensate drain must not be modi

fi

 ed or blocked.

Blockage of the condensate drain, caused by debris or freezing 

can cause automatic shutdown of the boiler. If you suspect 

freezing and the pipe run is accessible, you can try to free the 

obstruction by pouring hot water over the exposed pipe and 

clearing any blockage from the end of the pipe. If this fails to 

remedy the problem, you should contact your service engineer.

Section 3: Caring for your Boiler

Summary of Contents for EFCON5090MOD

Page 1: ...IRL DOC 0021 Rev 02 00 October 2022 Grant Euroflame Condensing External Condensing Oil Boiler Range User Instructions...

Page 2: ...tex Low NOx and Blue Flame boilers DOES NOT comply with ErP requirements or EU regulations and as a result Grant does not condone its use If your boiler uses Bio Kerosene B30K refer to the installatio...

Page 3: ...If your boiler fails to light 5 2 3 Turning o your boiler 5 2 4 About your fuel 5 2 5 Boiler controls 5 2 6 Heating system controls 6 2 7 Electricity supply 6 3 CARING FOR YOUR BOILER 6 3 1 Checking...

Page 4: ...lysis equipment Your installer should arrange for this to be carried out A list of OFFTEC registered commissioning engineers can be found on www oftec org 1 5 ACTIVATING THE GUARANTEE In order for you...

Page 5: ...ure that a fuse has not blown or that the electricity supply has not failed 7 Check to see if the overheat thermostat has operated see Section 2 5 If the burner still fails to light after carrying out...

Page 6: ...radiator As the correct operation of a TRV is based on it sensing the air temperature of the room it is fitted in take care not to cover the TRV head with curtains furniture etc Refer to the manufact...

Page 7: ...harge pressure in the expansion vessel NOTE In order to properly care for your Grant boiler an annual service by a competent person should always be undertaken 3 4 VENTILATION Your Grant Euroflame Con...

Page 8: ...out work on the install in the past if possible 3 6 FROST PROTECTION Your Grant Euroflame outdoor boiler does not have a frost thermostat fitted but can be added by a register electrical engineer if r...

Page 9: ...Signature Service 4 Date Engineer Company name Telephone number OFTEC Technician number Comments Signature Service 5 Date Engineer Company name Telephone number OFTEC Technician number Comments Signa...

Page 10: ...mments Signature Service 12 Date Engineer Company name Telephone number OFTEC Technician number Comments Signature Service 13 Date Engineer Company name Telephone number OFTEC Technician number Commen...

Page 11: ...Page 11 Notes NOTES...

Page 12: ...GRANT ENGINEERING IRELAND ULC Crinkle Birr Co O aly R42 D788 Ireland Tel 353 0 57 91 20089 Email info grantengineering ie www grant eu...

Reviews: