7
Multi Pass Oil Boilers
Kerosene Notes:
1
The data given above is approximate only and is based on the boiler being used with a low level balanced flue.
2
The above settings may have to be adjusted on site for the correct operation of the burner.
3
Gas Oil is not suitable for use with low level balanced flue models, unless the flue terminal is higher than 2.0 m above
outside ground level.
4
The installer must amend the boiler data label if the type of fuel or nozzle used is changed.
5
The 50/70, 70/90and 90/140 models use Riello burners. The 140/160 and 160/200 models use EOGB Sterling 90
burners.
6
* Indicates the factory set output.
7
** Net thermal efficiency (BSRIA).
8
The net flue gas temperatures given above are ± 10%.
9
When commissioning, or when the output or fuel is changed, the air damper must be adjusted to obtain the correct
CO
2
level and the installer must amend the data label.
10 When downrating the 50/70 model to 50 000 or 60 000 Btu/h, an LD2 head must be fitted.
11 *** Flue gas temperatures taken at combustion door test point will be approximately 25°C higher.
2 - BOILER TECHNICAL INFORMATION
Note: All boilers are despatched for use with kerosene.
Multi Pass oil boilers using Class C2 kerosene
2.2
(kW)
14.7
17.6
20.5
20.5
23.5
26.4
32.2
36.7
41.0
41.0
47.0
47.0
52.8
58.6
Model
(Btu/h)
50 000
60 000
70 000
70 000
80 000
90 000
110 000
125 000
140 000
140 000
160 000
160 000
180 000
200 000
95.4
95.2
96.0
96.0
95.7
95.8
94.5
94.1
93.8
(Btu/h)
52 400
63 000
73 000
73 000
83 780
94 200
116 400
132 800
149 140
149 140
169 600
169 600
190 800
212 000
(kW)
15.3
18.5
21.4
21.4
24.5
27.6
34.1
38.9
43.7
43.7
49.7
49.7
55.9
62.1
Nozzle
0.50/60°S
0.60/60°S
0.60/60°S
0.60/60°EH
0.75/60°EH
0.75/60°EH
1.00/60°ES
1.10/80°EH
1.25/60°S
1.25/60°S
1.35/60°S
1.35/60°S
1.50/60°S
1.65/60°S
Oil
press.
(bar)
7.00
7.00
9.00
8.50
7.00
9.50
8.00
8.50
8.25
7.50
8.25
8.25
8.00
9.25
Smoke
No.
0 - 1
0 - 1
0 - 1
0 - 1
0 - 1
0 - 1
0 - 1
0 - 1
0 - 1
0 - 1
0 - 1
0 - 1
0 - 1
0 - 1
Fuel flow
rate
(kg/h)
1.33
1.60
1.87
1.87
2.13
2.40
3.18
3.24
3.80
3.80
4.34
4.34
4.76
5.39
Flue gas
temp.***
(°C)
168
166
167
167
166
168
180
185
184
185
195
195
195
195
CO
2
(%)
12.0
12.0
12.0
12.0
12.0
12.0
12.0
12.0
12.0
12.0
12.0
12.0
12.0
12.0
Flue gas mass
flow rate
(kg/h)
21.5
25.5
29.6
30.0
34.4
38.7
47.4
54.0
60.5
60.4
68.3
68.3
77.3
86.4
Burner
head
LD2
LD2
LD3
LD3
LD3
LD3
LD3A
LD3A
LD3A
K/KA
K/KA
C/KA
C/KA
C/KA
Heat Output
Net Heat Input
Net
eff **
(%)
*
*
*
(Btu/h)
50/70
70/90
90/140
140/160
160/200
*
*