background image

10

Multi Pass Oil Boilers

The Multi Pass range of automatic pressure jet oil boilers have
been designed for use with a central heating system with indirect
domestic hot water cylinder. They are not suitable for use with
either a direct cylinder or a 'primatic' cylinder.

The boilers are suitable for use on sealed central
heating systems.

Five Kitchen models are available and are listed below
together with their maximum outputs.

50/70

20.5 kW (70 000 Btu/h)

70/90

26.4 kW (90 000 Btu/h)

90/140

41.0 kW (140 000 Btu/h)

140/160

46.6 kW (160 000 Btu/h)

160/200

59.0 kW (200 000 Btu/h)

Four blue cased Boiler House models are available and
are listed below together with their maximum outputs.

70/90

26.4 kW (90 000 Btu/h)

90/140

41.0 kW (140 000 Btu/h)

140/160

46.6 kW (160 000 Btu/h)

160/200

59.0 kW (200 000 Btu/h)

All models (except the 70/90 and 90/140) are despatched
pre-set at their maximum output and for use with kerosene.
The 70/90 and 90/140 are pre-set to mid range output.

The boilers are supplied as Conventional flue models, if a
Balanced flue version is ordered, a Balanced Flue Kit is
required. The following flue kits are available from Grant
UK. Refer to Sections 4.8 and 4.9 for further details.

Yellow system - Standard low level concentric balanced flue

Short low level concentric balanced flue
225 mm, 450 mm and 675 mm extensions
90° extension elbow
45° extension elbow
45° elbow

Green system - Standard external high level/vertical flue

starter kit (room sealed)
Short external high level/vertical flue starter
kit (room sealed)
150 mm, 250 mm 450 mm and 950 mm extensions
195 - 270 mm adjustable extension
45° elbow
High level terminal
Vertical terminal

White system - High level concentric balanced flue kit

225 mm, 450 mm and 950 mm extensions
275 - 450 mm adjustable extension
45° elbow
Vertical concentric balanced flue kit
225 mm, 450 mm and 950 mm extensions
275 - 450 mm adjustable extension
45° elbow

3 - GENERAL BOILER INFORMATION

Boiler description

3.1

Kitchen boilers are supplied with the control panel and
burner factory fitted. The burners for Boiler House
models are supplied in a separate carton. A burner
supply cable is supplied pre-wired to all burners.

All burners are pre-set for use with kerosene and are
supplied ready to connect to a single pipe fuel supply
system with a loose flexible fuel line (600 mm) and 

3

/

8

"

to 

1

/

4

" BSP male adaptor supplied with the boiler. If

required, an additional flexible fuel line (600 mm) and

3

/

8

" to 

1

/

4

" BSP male adaptor are available from Grant

Engineering (UK) Limited, for two-pipe oil supply
systems.

All models are suitable for use with Class C2 kerosene
to BS 2869:1998.

All models, except the 50/70, are also suitable for use
with Class D gas oil to BS 2869:1998.

Note: Only Kerosene may be used with low level
balanced flues
unless the flue terminal is higher
than 2.0 m above outside ground level.

If the fuel to be used is Gas Oil or the boiler output is
to be changed, it may be necessary to change the
burner nozzle, head and baffle settings. Refer to the
Technical Information in Sections 2.2 and 2.3. To
change the nozzle on Kitchen models, remove the
burner from the boiler then remove the nozzle as
described in Section 7.4. For Boiler House models,
unpack the burner and remove the nozzle as described
in Section 7.4. To remove the baffles refer to Sections
7.2 and 7.3, then refer to Figs. 30 to 34 for baffle
settings. The installer must amend the boiler data label
accordingly.

The temperature of the water leaving the boiler to heat
the radiators and hot water cylinder is User adjustable
from 65 to 85°C.

The boiler is fitted with an overheat thermostat (which
allows it to be used on a sealed central heating system)
which will automatically switch off the boiler if the heat
exchanger exceeds a pre-set temperature of 111°C ± 3°C.

For Kitchen models the control panel is fitted with an
ON/OFF switch, boiler thermostat control knob and
the manual reset button for the overheat thermostat. An
optional plug-in programmer is available which allows
the User to set the operating times for central heating
and hot water, (plug-in programmer not available for
140/160 and 160/200 models).

For Boiler House models a combined boiler and
overheat thermostat is fitted with a boiler thermostat
control knob and the manual reset button for the
overheat thermostat.

Summary of Contents for 140/160

Page 1: ...50 70 70 90 90 140 140 160 and 160 200 This appliance is deemed a controlled service and specific regional statutory requirements may be applicable After installing the boiler leave these instructions...

Page 2: ...Health and safety information 50 12 EC declaration of conformity 51 Date CO2 Net flue gas temp Smoke No Service engineer Tel No Date Commissioningengineer Tel No Boiler model output Btu h Fuel type K...

Page 3: ...e that There is sufficient fuel of the correct type in the supply tank and all fuel supply valves are open The water supply is on The electricity supply to the boiler is off The boiler On Off switch i...

Page 4: ...the flue terminal is more than 2 0 m above ground level Do not wait until the fuel runs out before you order some more Sludge in the bottom of the tank may be drawn into the fuel lines If it is possib...

Page 5: ...l re appear when the supply is restored The boiler requires a 230 240 V 50 Hz supply It must be protected by a 5 Amp fuse Warning This appliance must be earthed If your boiler is operating on a sealed...

Page 6: ...tem Open system 28 m 1m 65 to 85 C 111 C 3 C Less than 50 C 230 240 V 50 Hz Fused at 5 Amp BSP Male on end of flexible fuel line Minimum flue draught 8 7 N m 0 035 in wg Maximum flue draught 37 N m 0...

Page 7: ...boilers are despatched for use with kerosene Multi Pass oil boilers using Class C2 kerosene 2 2 kW 14 7 17 6 20 5 20 5 23 5 26 4 32 2 36 7 41 0 41 0 47 0 47 0 52 8 58 6 Model Btu h 50 000 60 000 70 00...

Page 8: ...32 2 41 0 41 0 47 0 47 0 52 8 58 6 Model Btu h 70 000 80 000 90 000 110 000 140 000 140 000 160 000 160 000 180 000 200 000 94 6 94 7 94 6 94 1 94 3 Btu h 76 900 87 900 98 900 116 745 148 470 148 768...

Page 9: ...200 499 650 160 180 36 54 A B C D E F G H Model Kitchen Dimension mm 860 605 A B C E F G Model Boiler House Dimension mm 720 895 460 460 445 480 625 655 D H 65 68 499 650 145 135 160 185 1000 550 580...

Page 10: ...supplied in a separate carton A burner supply cable is supplied pre wired to all burners All burners are pre set for use with kerosene and are supplied ready to connect to a single pipe fuel supply sy...

Page 11: ...rs and oil storage tanks 3 GENERAL BOILER INFORMATION Regulations to comply with 3 2 Regional statutory requirements may deem this appliance to be a controlled service Where this is the case it is a l...

Page 12: ...rom Grant Engineering UK Limited 3 GENERAL BOILER INFORMATION 6 Flexible pipes should be inspected annually when the boiler is serviced and replaced every two years 7 The use of a Tankmaster and Tiger...

Page 13: ...13 Multi Pass Oil Boilers 3 GENERAL BOILER INFORMATION Fig 3 Two pipe system Fig 2 Single pipe system...

Page 14: ...manufacturers instructions supplied with the Tiger Loop The Tiger Loop must be mounted vertically Note To prevent any possibility of fuel fumes entering the building the Tiger Loop must be fitted out...

Page 15: ...pump 6 Connect the 3 8 to 1 4 BSP adaptor to the flexible fuel line 7 Flexible fuel lines and adaptors are available from Grant Engineering UK Ltd 8 Boiler House models Fit the burner as described in...

Page 16: ...llowing electrical system checks must be carried out Short circuit Polarity Earth continuity and Resistance to earth See Figs 9 and 10 A sufficient permanent air supply to the boiler should be provide...

Page 17: ...vide the necessary draught of at least 8 7 N m2 0 035 in wg as measured close to the boiler connection If a draught of 37 N m2 0 15 in wg or more is measured then a draught stabiliser should be fitted...

Page 18: ...l supplied in the literature pack Place the panel in position in the rear case top panel and secure in place using the washers and nuts previously removed Note The first section of flue must be in sin...

Page 19: ...19 Multi Pass Oil Boilers Fig 11 Typical conventional flue with brick chimney 3 GENERAL BOILER INFORMATION...

Page 20: ...20 Multi Pass Oil Boilers 3 GENERAL BOILER INFORMATION Fig 12 External flue Green system...

Page 21: ...s adjustable to suit the following wall thicknesses Rear 215 to 450 mm approximately Side 120 to 350 mm approximately Extension kits are available which extend the flue by 950 mm 450 mm 225 mm or 275...

Page 22: ...m a terminal facing the terminal G From a surface facing the terminal H Vertical from terminals on the same wall I Horizontal from terminals on the same wall J Below an opening air brick window etc K...

Page 23: ...rost protection 3 9 Boiler location 3 10 2 Flow and return connections should be diagonally opposed i e to opposite sides of the boiler If the boiler is to be positioned against a wall the water conne...

Page 24: ...perature of the central heating water is 85 C See Figs 14 15 and 16 3 12 1 Gravity domestic hot water See Fig 14 3 GENERAL BOILER INFORMATION Heating system diagrams 3 12 3 12 2 Fully pumped See Fig 1...

Page 25: ...the system must be able to withstand pressures up to 3 bar 9 Radiator valves must comply with the requirements of BS 2767 10 1972 10 One or more drain taps to BS 2879 must be used to allow the system...

Page 26: ...npack the boiler 4 1 4 BOILER INSTALLATION Prepare the wall balanced flue 4 2 See Figs 18 and 19 If the boiler is to be used with a balanced flue make the hole in the wall for the flue as shown in Fig...

Page 27: ...The outer pipes must overlap by a minimum of 25 mm Extensions The vertical height and horizontal length of the flue may also be increased using extensions The extensions are available in fixed length...

Page 28: ...position if access will be restricted Note Iftheboileristobepositionedagainstasidewall thewaterconnectionsmaybetakenfromonesideonly see paragraph 1 for thermostat pocket position 3 Ensure that all th...

Page 29: ...stud on the burner fixing flange on the front of the boiler see Fig 21 Leave the small nut in position ensure it is located up against the mounting flange Note Do not remove the fixing flange from the...

Page 30: ...securely attached to the boiler mounting flange 4 BOILER INSTALLATION Fig 22 EOGB Sterling 90 Burner components 1 Lock out lamp and reset button 2 Control box 3 Ignition transformer 4 Ignition cables...

Page 31: ...dequately supported Do not switch on the electricity supply at this stage 4 BOILER INSTALLATION Note Not applicable to 140 160 or 160 200 models Important Ensure the electrical supply to the boiler ha...

Page 32: ...to the incoming neutral of switched mains supply using a single connector not supplied Refer to Section 8 For other systems not covered contact Grant Engineering UK Ltd DO NOT connect the neutral wire...

Page 33: ...burner cover two screws if it was not previously removed To gain access on Kitchen models it may be necessary to remove the plinth loosen the screw securing the right hand side of the plinth then with...

Page 34: ...is approximately 25 C higher than at the the flue 12 Check the smoke number if satisfactory check the CO2 Riello RDB burner Use the hexagonal key supplied to adjust the burner air damper see Fig 21 a...

Page 35: ...leaning cover note that the flue gas temperature reading will be considerably higher than that measured in the flue thus resulting in an inaccurate efficiency reading To obtain an accurate flue gas te...

Page 36: ...d annually when the boiler is serviced and replaced every two years If in doubt replace the pipes Warning Before servicing set the boiler On Off switch to Off Kitchen models only isolate the electrici...

Page 37: ...Loosen the electrode clamp screw and withdraw the electrode assembly Wipe clean and check for any cracks in the ceramic insulation Replace if necessary Check the electrode settings Riello burner Elec...

Page 38: ...ot removed remove the screws securing the fan housing cover R H side of burner and remove the cover Inspect the fan and housing and clean as necessary Replace the cover EOGB burner fan The fan wheel a...

Page 39: ...0 000 Btu h output Secure plates in position B for 60 000 Btu h output Secure plates in position C for 50 000 Btu h output Fig 31 70 90 Baffle arrangement Note Secure plates in position A for 70 000 B...

Page 40: ...Boilers 7 BOILER SERVICING Fig 32 90 140 Baffle arrangement Note Secure plate in position as shown for 140 000 Btu h output Remove plate completely for 110 000 Btu h output Fig 33 140 160 Baffle arran...

Page 41: ...41 Multi Pass Oil Boilers 7 BOILER SERVICING Fig 34 160 200 Baffle arrangement Left Right...

Page 42: ...42 Multi Pass Oil Boilers 8 WIRING DIAGRAMS Fig 35 Fig 36 Kitchen boiler control panel wiring diagram 50 70 70 90 and 90 140 8 1 Kitchen boiler control panel wiring diagram 140 160 and 160 200 8 2...

Page 43: ...Controller Add Link L 5 8 Boiler Terminal Block L641 Cylinder Stat 1 C T6160 Room Stat 2 1 3 Pump E N L V4043H Zone Valve Motor HTG V4043H Zone Valve Motor DHW Grey Blue Blue Brown Brown Green Yellow...

Page 44: ...trolled by mid position valve L641 Cylinder Stat 1 C 2 Overheat stat 1 C 2 Control stat 1 C 2 L N E 240 V 50 HZ T6160 Room Stat 2 1 3 V4073A Mid Position Zone Valve Pump E N L Blue Green Yellow White...

Page 45: ...ol thermostat Mains supply Supply to burner Note No connection to terminal 1 Note No connection to terminal 2 L N E L N E Connector to link neutral wires not supplied Fig 43 Dual thermostat wiring dia...

Page 46: ...t light not lit Motor runs Burner runs to lock out Fuse has blown Appliance thermostat has not reset Appliance overheat device has operated Control relay or photocell defective No oil being delivered...

Page 47: ...ir damper setting and the condition of the fan Check room ventilation is adequate see Section 3 7 Check the nozzle size and type Fuel pressure may be too low check and adjust Insufficient draught clea...

Page 48: ...4 5 F 3002837 RBS149 13 Seal kit 3008878 RBS140 14 Needle valve 3007582 RBS109 15 Regulator 3008651 RBS120 Key No Description Riello Part No Grant Part No Key No Description Riello Part No Grant Part...

Page 49: ...2 1 125 02 SBS05 11 Transformer D01 052F0030 SBS11 12 Drive coupling B03 00 111 27823 SBS12 13 KA brake plate B03 00 118 85801 SBS13 14 Burner head 140 160 B03 00 117 28401 SBS14 15 Burner head 160 20...

Page 50: ...ilicone elastomer Description Sealant and adhesive Known Hazards Irritation to eyes Precautions Avoid inhalation of vapour contact with eyes and prolonged or repeated contact with skin After handling...

Page 51: ...51 Multi Pass Oil Boilers...

Page 52: ...wing European Directives 1 89 336 EEC Electromagnetic Compatibility Directive Referred to the generic standards EN 55014 1993 EN 50082 1 1992 2 73 23 EEC Electrical Equipment Safety Regulations Direct...

Reviews: