TEST PROCEDURES
External Total Static Pressure Reading
Total Static Pressure = Supply Pressure (Ps) + Return Pressure (Pr)
Pr
Ps
A/C Coil Total Resistance Reading
A/C coil total resistance = Coil Pressure (Pc) - Supply Pressure (Ps)
Ps
Pr
Pc
Temperature Rise Reading ***
Temperature rise = Supply Temp. (Ts) - Return Temp. (Tr)
Tr
Ts
*** Probe must not be in direct sight of heat exchanger.