17
COMBUSTION TEST
All your tests must be done with the burner cover on
ADJUSTMENTS
After 10 minutes of normal operation, adjust the breech draft with the
barometric control to obtain a value of -0.01’’ WC, after proceed to take
a smoke test and adjust the burner to obtain a reading of “1” on the smoke
scale. Take a CO
2
test and note the result.
To reach the maximum smoke test value, a 10- f u l l slow steady
pump action is required
- Open the air band adjustment on the burner to
reduce
your CO2 lecture
by 1%.
CO2 test can be done
mechanically
, activate 18 full
slow steady pump action.
OR
do an electronical CO
2
test
§
Re adjust
§
You now have a small “slight trace” of smoke
.
Relation between % of CO
2
and O
2
CO
2
(%)
O
2
(%)
Excess Air (%)
13.5
2.6
15.0
13.0
3.3
20.0
12.5
4.0
25.0
12.0
4.6
30.0
11.5
5.3
35.0
11.0
6.0
40.0