2.14 OFF CYCLE AIR CIRCULATION 

 

#4 LO SPEED 

All models have the #4 Lo speed switch for optional constant air circulation 
during the furnace off cycle. 

 

“FAN ON” 

When “FAN ON” is selected on the thermostat, the blower will run constantly 
at the #1 Hi speed providing heat, cooling or neither as selected. 

 

3.0 BURNER 

SPECIFICATIONS 

 

Model Burner 

Input 

Nozzle 

Pump 

Air 

Setting

 

Turbulator

Output 

Heating CFM@ 

Blower Speed 

USGPH L/h 

Btu/h 

(psi) 

Btu/h  kW 0.2"wc 0.5"wc  0.2"wc  0.5"wc 

K4C-E1-0090-03 

Riello 40 F3 

0.61 2.31 85,400 0.50

80B 

150 

2.8 0.5 

74,000

22 

990 

990 

4  3 

0.73 2.76 102,200 

0.60

60W 3.5 

1.0 

88,000

26 

1180 

1090 

K4C-G3-K098-03 

Beckett AFG-F0 

0.61 

2.31 85,400 0.50

70W  150 

6/0 - 

73,000

21 

1050 

1050 

3 2 

Beckett AFG-F3 

0.73 2.76 102,200 

0.60

70W 

150 

7/0  

88,000

26 

1150 

1100 

2 1 

0.79 2.99 110,600 

0.65

70W 9/0 

 

93,000

27 

1150 

1100 

K4C-N1-K098-03 Beckett 

NX-LH 

0.61 2.31 85,400 0.50

60A 

150 

2.3 - 

75,000

22 

1050 

1050 

3 2 

0.73 2.76 102,200 

0.60

60A 3.5 

88,000

26 

1150 

1100 

0.81 3.07 113,400 

0.65

60A 4.0 

98,000

29 

1150 

1100 

Direct Vent 

K4C-V1-0090-03 Riello 

BF3 

0.61 2.31 85,400 0.50

80W 

150 

5.0 0.5 

74,000

22 

990 

990 

4  3 

0.73 2.76 102,200 

0.60

60W 6.0 

1.5 

88,000

26 

1180 

1090 

 

The turbulator & air settings found in this section should be used as a guide. 

 

With ECM motors, the last 2 digits of the model number are E3 instead of 03. 

 

4.0  BLOCKED VENT SWITCH 

 

Oil-fired appliances installed in Canada require a blocked vent shut-off system when installed 
on a chimney.  A safety switch is included with the furnace to perform this function.  It is the 
installer’s responsibility to install the switch in accordance with the instructions provided.  Not 
applicable for Direct Vent systems.

 

 

Field Controls Model: WMO-1 (Manual Reset) 

 

Switch Operation 

Blocked vent switches are flue gas safety devices for detecting spillage of flue gases due to a 
blocked flue or inadequate draft.  After detecting a problem, the switch de-energizes the 
system’s burner control. 

 

NEVER reset the switch unless the cause of the blockage has been corrected. 

 
 

Summary of Contents for COMPACT- multi

Page 1: ...EDERAL CODES THAT MAY DIFFER FROM THIS MANUAL Please read this complete manual before beginning installation These instructions must be kept with the furnace for future reference CERTIFIED TO CAN CSA Std B140 0 Std B140 4 CONFORMS TO UL 727 GRANBY FURNACES INC PO Box 637 12118 Hwy 209 Parrsboro Nova Scotia Canada B0M 1S0 www granbyindustries com ...

Page 2: ...tion 4 2 3 Installation Codes 4 2 4 Multi Position 5 2 5 Placement Venting 5 2 6 Assemble Install Burner 7 2 7 Changing Nozzle 7 2 8 Set Burner for Efficient Operation 7 2 9 Blower Setting 8 2 10 Air Conditioning 8 2 11 Humidifier 8 2 12 Thermostat Anticipator Setting 8 2 13 Fan Control 8 2 14 Off Cycle Air Circulation 9 3 0 Burner Specification 9 4 0 Blocked Vent Switch 9 5 0 Oil Tanks Piping 10 ...

Page 3: ...s manual in a safe place for future reference Follow manual carefully for the correct way to install and operate this unit Do not operate this appliance until operating instructions have been read and fully understood DANGER Do not use this furnace as a construction heater Use of this furnace as a construction heater exposes it to abnormal conditions contaminated combustion air and lack of air fil...

Page 4: ... bottom of the furnace See Figure 7 1 3 REGULAR MAINTENANCE Check complete operation at least once a year In Canada see B139 Section 14 Maintenance for recommended servicing procedure Heat exchanger ducts are accessed through breech access panels at front of unit Replace stainless steel gas baffles after cleaning Cerafelt 1 4 gaskets may have to be replaced 1 4 WARNINGS NEVER burn garbage or paper...

Page 5: ...ocal state or provincial codes Improper installation will result in voiding of warranty 2 2 CAUTION DO NOT START THE BURNER UNTIL ALL FITTINGS COVERS AND DOORS ARE IN PLACE DO NOT TAMPER WITH THE FURNACE OR CONTROLS CALL A QUALIFIED BURNER TECHNICIAN FOR YOUR SAFETY DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPOURS AND LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE 2 3 INSTALLATION C...

Page 6: ...8 16 x 4 eyebolts and 3 8 nuts are use to suspend the furnace Determine the appropriate side and remove the knockouts Four weld nuts 3 8 16 UNC are concealed behind knockouts on either side of the furnace For installations where the furnace will be supported from below use 4 long 3 8 UNC bolts as adjustable legs Eyebolts complete with locking nuts are available The locking nuts should be threaded ...

Page 7: ... to high If the Compact multi is used in a down flow position with the Scotty SS a diverter base is available for easier duct connections SUB BASE The sub base kit is used to provide the proper support and clearances for a furnace that is used in the downflow position and is mounted on a floor with the supply ducting running beneath the floor K4C KA 0500 00 DIVERTER BASE The diverter base is used ...

Page 8: ...ur nuts PUMP BY PASS For one pipe system factory setting no plug PLUG WIRING Refer to wiring label and Figure 4 for correct burner connections THERMOSTAT Connect thermostat terminals 2 7 CHANGING NOZZLE NOZZLE CHANGE If a new nozzle of a different size is installed change the heating blower speed according to the operating decal or section 3 0 BURNER SPECIFICATIONS 2 8 SET BURNER FOR EFFICIENT OPE...

Page 9: ...ing nor cooling are required Set blower speeds to match the installation requirements On the model number the last 2 digits represent the type of motor 03 for a PSC 1 3HP motor and E3 for a 1 2HP ECM high efficiency motor 2 10 AIR CONDITIONING An air conditioning coil may be installed on the supply side only Coils installed on the return side will cause condensation on the heat exchanger that will...

Page 10: ... 50 60A 150 2 3 75 000 22 1050 1050 3 2 0 73 2 76 102 200 0 60 60A 3 5 88 000 26 1150 1100 2 1 0 81 3 07 113 400 0 65 60A 4 0 98 000 29 1150 1100 2 1 Direct Vent K4C V1 0090 03 Riello BF3 0 61 2 31 85 400 0 50 80W 150 5 0 0 5 74 000 22 990 990 4 3 0 73 2 76 102 200 0 60 60W 6 0 1 5 88 000 26 1180 1090 3 2 The turbulator air settings found in this section should be used as a guide With ECM motors t...

Page 11: ... vent switch should shut down the burner within 10 minutes or sooner 4 Once the system has cooled the blocked vent switch can manually be reset 5 This procedure should be tested a second time 6 After testing the blocked vent switch the chimney should be cleared of obstruction and the heating system tested on a long run cycle If the block vent switch shuts down the system check to ensure there is e...

Page 12: ...covers are secured in place 7 0 GENERAL SPECIFICATIONS CLEARANCE TO COMBUSTIBLES UPFLOW DOWNFLOW POSITION Top 1 25 mm Front 24 610 mm Rear Front Breech 2 51 mm Rear Rear Breech 24 610 mm Side Non Access 2 51 mm Side Access 24 610 mm Return Air Side Ductwork 1 25 mm Flue Pipe 9 229 mm Floor Combustible Upflow only Downflow must have sub base K4C KA 0500 00 Horizontal Position Top 6 152 mm Front 24 ...

Page 13: ... 1 4 1124 mm Width 19 1 2 495 mm Width w Filter Bracket 21 1 2 546 mm PLENUM DIMENSIONS Cold air return 20 x 16 508 x 406 mm Hot air supply 18 1 4 x 21 5 8 464 x 549 mm Height to plenum 44 1118 mm A C COIL LOCATION Minimum height above the heat exchanger 10 254 mm OPENING HEIGHTS from floor Burner c l 24 610 mm Smoke pipe c l 37 940 mm SMOKE VENT PIPE 5 Chimney 4 Direct Vent CLEANOUTS Front covers...

Page 14: ...t wrong Adjust barometric regulator for 0 03 wc draft pressure at breech Oil burner keeps turning off Dirty air filter Change air filter Restricted air supply return Check all air return supply registers Limit control Check ductwork for blockage Motor over heating Check motor speed correct for nozzle on furnace label settings Dirty nozzle Call technician to replace nozzle Burner reset cuts out No ...

Page 15: ...R MOST RECENT UPDATES PLEASE VISIT www granbyindustries com The following form MUST be completed for the warranty to be valid Installed by Address Telephone Date START UP TEST RESULTS Nozzle Pressure Air Turbulator CO2 Smoke Number Breech Draft Stack Temperature Test Performed By Staple Printout Here Staple Smoke Spot Here ...

Page 16: ......

Page 17: ......

Page 18: ......

Page 19: ......

Page 20: ......

Page 21: ......

Page 22: ......

Page 23: ......

Page 24: ... 16 Rear Cabinet Cleanout Cover K40 CB 0150 00 K4C 17 Divider Assembly K4C CB 0050 00 K4C 18 Base Pan K00 CB 0028 00 K4C 19 Blower Key K00 CB 0028 00 K4C 19 Blower Key 3BU 10 00DD 00 K4C 20 G10 DD Blower 3BM 33 4SDD 00 K4C 21 Motor 1 3 hp Direct Drive 4 Speed 3BM 50 ECM0 02 K4C 22 Motor 1 2 hp Direct Drive ECM 4CA 00 505M 23 K4C 23 Motor Run Capacitor 5 micro farad Not Shown K00 BM 1033 00 K4C 24 ...

Reviews: