- 24 -
765041559
Rev. 002
The alarm system is divided into 2 systems. The one system only triggers local alarms, which means that the
error codes are only shown at the display.
The other alarm system triggers both alarms at the display, but it also activates the remote alarm outlet.
Each alarm system operates independently of each other.
If a change of the setting is required, get access to the menu by pushing
P + 1
for more than 3 seconds.
The values are changed by pushing the + or
-
keys. The new setting is saved by pushing
P
. To exit
the menu, push
.
Menu access P + 1
Dry refrigeration
dC
H0/H1
Activation of dry refrigeration.
(
H0
=on;
H1
=off)
Rapid thaw
UF
on/off
Activation of rapid thaw. (on/off)
Local alarm setting
LAL LHL
°C
Setting the upper alarm limit. At
alarm, the display shows:
A2
LHd
min.
Time delay for the upper alarm limit.
dA
On/off
Activation of local door alarm. At alarm, the
display shows:
A1
(1=on / 0=off)
dAd
min.
Time delay for the door alarm.
BU
On/off
Activation of buzzer. The buzzer
sounds at alarms A1, A2. (1=on /
0=off)
External alarm setting
EAL EHL
°C
Setting the upper alarm limit. At
alarm, the display shows:
A3
ELL
°C
Setting the lower alarm limit. At
alarm, the display shows:
A4
EHd
min.
Time delay for the upper alarm limit.
ELd
min.
Time delay for lower alarm.
Temperature offset
(sensor calibration)
CAL CA
K
-5…+5 K
Escorting alarm limits
ALL FAS/ESC
Activation of escorting alarm limits.
FAS
= fixed limits /
ESC
= limits
following the setpoint
No. of defrosts
dEF 4
Number of defrosts in 24 hours.