18 308393
Shutdown and Care
Check the Gun Washer Electrical Continu-
ity
WARNING
FIRE AND EXPLOSION HAZARD
There must be electrical continuity be-
tween the gun washer’s fluid tank, divid-
er plate, frame, and main ground wire.
To reduce the risk of static sparking, fire,
or explosion, check the electrical conti-
nuity between all gun washer metallic
parts and true earth ground after servicing the gun
washer. Make sure the gun washer is properly
grounded before operating it again.
Check your local electrical code for detailed grounding
instructions for your area and type of equipment.
If electrical continuity is lost, check the grounding con-
nections and reconnect them as needed. See Fig. 7 for
the gun washers grounding circuits.
Fig. 7
Grounding Circuits
Jumper Wire from Lid
to Fluid Manifold
Jumper Wire from Fluid Drain
Valve to Pump Grounding Bar
Ground Wire to
True Earth Ground
Jumper Wire from Pump Outlet to
Pump Grounding Bar
Jumper Wire from Pump In-
let to Pump Grounding Bar
Model 112635 shown
03307