Advanced Programming
332305B
47
A2 - Low Level Alarm Time
Pump ON mode only.
Programs the amount of time in MM: SS (minutes and
seconds) the pump can run between a Low Level Warn-
ing and a Low Level Fault to help protect unit from run-
ning dry.
The maximum recommended length of time is 3:00 min-
utes.
Fault, and Low Level LED illuminate. (
Max Model Dis-
play shown in illustration below
).
NOTE:
When programming a time of less than 10 min-
utes you
must
program a leading zero in the first num-
ber field and press the ENTER button to save the zero
selection.
1. To set the time use the UP or
DOWN ARROW button to
scroll through numerals 0 to 9
until the desired number
appears in the first MM (min-
utes) field.
2. Press the ENTER button to lock in the
selection. The next MM number field to
the right flashes indicating it is ready for
programming.
3. Use the UP or DOWN
ARROW button to scroll
through numerals 0 to 9 until
the desired number appears
in the second MM number
field.
4. Press the ENTER button to lock in the
selection.
The next number field to the right
flashes and the LED lights under SS; indicating it is
ready to program the seconds fields.
5. Repeat steps 1 - 4 to set the SS (seconds) fields.
6. After pressing the ENTER button to set
the last SS field, all the programmed ON
Time information is saved.
Unit exits Advanced Programming.
A3 - Vent Valve Time
The Vent Valve Time is the amount of time the vent
valve stays open after a cycle is completed.
The recommended Vent Valve Time is 5 minutes.
To bypass the Vent Valve Time enter a value of 00:00.
Vent Valve time must be less than the programmed OFF
time (page 35). If it is not set to a value less than the
programmed OFF time, the G3 will automatically adjust
the time to a value 2 seconds less than the set OFF
time.
F
IG
. 23