Installation

312668ZAC

7

Installation

This dispense valve must be calibrated after installation 

(beginning on page 14). Dispense amounts vary with 

fluid pressure, temperature, and type of fluid 

dispensed.

This dispense valve is designed for indoor use only, for 

use with industrial grade batteries (see page 21), and is 

not designed for in-line installation.

Grounding

Pump:

 follow the manufacturer’s recommendations.

Hose Reels or consoles

: connect to a true earth 

ground.

Fluid hoses:

 use only conductive hoses when 

dispensing petroleum products.

To maintain grounding continuity when flushing or 

relieving pressure, hold a metal part of the valve firmly 

to the side of a grounded metal pail, then trigger the 

valve.

Pre-Installation Procedure

1. Install the battery. See 

Replace the Battery

, 

page 21.

2. Follow the 

Pressure Relief Procedure

, page 10.

3. Close the shut off valve (B) (F

IG

. 1, page 6).

4. Ground the hose and reel or counsel. See 

Grounding

.

NOTE: Leave at least two engaged threads bare when 

using PTFE tape, the bare threads ensure ground is 

maintained.

Installation Procedure

For existing installations, skip to 

Electronic Control (1) 

and Gasket (2) Installation

, page 8.

Flush the System 

1. Close the fluid shut off valve (B) at each dispense 

position (F

IG

. 3).

2. Make sure that the main fluid outlet valve at the 

pump is closed.

3. Adjust the air pressure to the pump motor.

a. Adjust the air regulator attached to the motor 

air inlet.

b. Open the air valve.

c. Slowly open the main fluid valve.

4. Flush the system:

a. Place the hose end (no dispense valve 

connected) into a container for waste oil.

b. Secure the hose in the container so it does not 

come out during flushing.

c. For multiple dispense positions, start with the 

dispense position furthest from the pump, and 

work toward the pump.

5. Slowly open the shut off valve (B) at the dispense 

position and flush out a sufficient amount of oil to 

ensure that the entire system is clean (F

IG

. 3).

6. Close the shut off valve (B) (F

IG

. 3).

7. Repeat steps and 6 at all of the dispense 

positions.

The equipment must be grounded to reduce the risk 

of static sparking. Static sparking can cause fumes 

to ignite or explode. Grounding provides an escape 

wire for the electric current.

NOTICE

For new installations, or when there is contaminated 

fluid in the lines, flush the lines before installing the 

meter valve, to avoid valve leakage. 

Summary of Contents for 24F883

Page 1: ...ld washer solvent For professional use only Not approved for use in European explosive atmosphere locations Model 1000 psi 6 9 MPa 69 bar Maximum Working Pressure See page 3 for model information Impo...

Page 2: ...Menus 12 Resettable Total 12 Units of Measurement 13 Calibration 14 Auto Preset Amount 14 Shut Off Default Amount 15 LDP5 Meter Operation 16 Dispensing Fluid in Manual Mode 16 Dispensing Fluid in Auto...

Page 3: ...Guard Swivel Cover Inlet Rigid Flex NPT BSPT BSPP LDP5 255277 X X LDP5 256216 X X X X LDP5 258694 X X X X LDP5 24F883 X X LDP5 24F884 X X X X LDP5 24F886 X X X X LDP5 24F889 X X LDP5 24F890 X X X X L...

Page 4: ...mediately EQUIPMENT MISUSE HAZARD Misuse can cause death or serious injury Do not operate the unit when fatigued or under the influence of drugs or alcohol Do not exceed the maximum working pressure o...

Page 5: ...not plug or unplug power cords or turn lights on or off when flammable fumes are present Use only grounded hoses Stop operation immediately if static sparking occurs or you feel a shock Do not use eq...

Page 6: ...mp See Kits and Accessories page 27 for available kits Mounting Bracket Mounting bracket P N 196471 is available for resting dispense valve on the counsel FIG 2 FIG 1 B D E C A NOTICE Do not use this...

Page 7: ...r existing installations skip to Electronic Control 1 and Gasket 2 Installation page 8 Flush the System 1 Close the fluid shut off valve B at each dispense position FIG 3 2 Make sure that the main flu...

Page 8: ...3 Apply thread sealant to the male threads of the hose fitting 4 Thread the hose fitting into the swivel 4 and tighten firmly FIG 5 NOTE Make sure to let the sealant cure according to the manufacture...

Page 9: ...will affect the performance of the nozzle 4 Open all of the dispense position shut off valves B ans start the pump to pressurize the system See LDP5 Meter Operation page 16 for proper operation of th...

Page 10: ...p until it clicks into the locked position To unlock the trigger FIG 9 press on the smooth part of the trigger until it clicks out of the locked position When the trigger is released the fluid flow st...

Page 11: ...displayed Further dispensing is allowed by pulling back the trigger and the display resumes counting Asleep Awake Mode Asleep is a battery saving mode where the display goes blank after 45 seconds of...

Page 12: ...ght corner on the screen c Third screen Calibration Menu FIG 14 page 14 CAL blinks on the screen d Fourth screen Auto Preset Amount Menu FIG 15 page 14 AUTO blinks and the currently stored auto preset...

Page 13: ...ement Menu is not already displayed complete steps 1 3 in Setup Menus page 12 2 GAL QTS PTS or LITERS blinks indicating the Units of Measurement Menu screen is displayed 3 Do one of the following a Pr...

Page 14: ...e exactly one 1 liter of fluid into a calibrated one 1 liter container For proper calibration the exact amount must be dispensed b Press and hold the Manual Reset button until CAL stops blink ing c Wh...

Page 15: ...et button b Press and hold the Auto Reset button to lock in the amount The Shut Off Default Amount Menu displays OR Press and hold the Auto Reset button to lock in the currently displayed auto preset...

Page 16: ...DP5 Meter Operation Dispensing Fluid in Manual Mode 1 Press and hold the Man ual Reset button If the display is blank Asleep it wakes up and displays the amount dis played before it fell asleep If the...

Page 17: ...e amount are dis played The factory default is 5 00 NOTE To change the stored preset dispense amount see Auto Preset Amount page 14 2 Dispensing or changing the displayed preset amount is done by one...

Page 18: ...eleased NOTE When the trigger unlocks the automatic nozzle prevents the fluid in the extension from running out Viewing Totals To view the non resettable and resettable totals follow these instruction...

Page 19: ...tracks the amount dispensed Options with any error code displayed as shown at right Press the Manual Reset button The error code is cleared the unit switches to Manual mode and the dispensed amount i...

Page 20: ...e unit checks for flow every second and repeats the error code until the trigger is released and the error code cleared Err 5 The unit has dispensed the shut off default amount and has stopped fluid f...

Page 21: ...th the meter settings See FIG 23 Replace the Filter 1 Follow the Pressure Relief Procedure page 10 2 Unscrew the hose from the swivel 4 FIG 24 3 Remove the o ring 8b and the filter 8a from inside of t...

Page 22: ...age 10 Drain and dispose of fluids according to applicable regulations Refer to the material manufacturer s Safety Data Sheet Remove motors batteries circuit boards LCDs liquid crystal displays and ot...

Page 23: ...o Reset button Slow or no fluid flow Filter is clogged 1 Relieve pressure by following the Pressure Relief Procedure page 10 2 Clean or replace the filter See Replace the Filter page 21 3 If the probl...

Page 24: ...If flat the plate and seal are okay If the plate is not flat the meter is damaged Contact your Graco distributor for repairs or replacement Meter leaks from Automatic nozzle NOTE It is important to di...

Page 25: ...949 1 2 34 8b 8a 8 6 4 4 5 3 26c 26c 26a 26a 26b 26b 35 32 38 17 1 11a 11b 11c 11d 11e 11f 2 11 3 Housing surface 3 must be clean to ensure proper adhesive bonding of gasket 2 6 Apply thread sealant w...

Page 26: ...T nozzle flexible extension for oil and anti freeze includes 26a 26c models 255751 255277 258693 258694 2F881 24F883 24F885 24F886 24F887 24F889 24F891 24F892 1 26a EXTENSION 1 26b NOZZLE dispenser 1...

Page 27: ...d Antifreeze Part No Description PSI MPa bar 112353 Diaphragm pump for fuel dis pense valve only 50 psi 0 34 MPa 3 4 bar 235998 Mini Fire Ball 225 3 1 600 psi 4 1 MPa 41 bar 237601 Fire Ball 425 3 1 6...

Page 28: ...ile rubber zinc CS LCP Battery 9 volt alkaline Pressure loss at 5 gpm 90 psi 0 62 MPa 6 2 bar Accuracy 0 5 percent Units of Measurement pints quarts gallons liters factory set to quarts Maximum totali...

Page 29: ...California Proposition 65 312668ZAC 29 California Proposition 65 CALIFORNIA RESIDENTS WARNING Cancer and reproductive harm www P65warnings ca gov...

Page 30: ...in material or workmanship repairs will be made at a reasonable charge which charges may include the costs of parts labor and transportation THIS WARRANTY IS EXCLUSIVE AND IS IN LIEU OF ANY OTHER WAR...

Reviews: